6 Electrical installation
Installation manual
14
ETV23E
Daikin Altherma 3 H HT F
4P644729-1E – 2023.10
Item
Description
Remote indoor sensor
See:
▪ Installation manual of the remote
indoor sensor
▪ Addendum
book
for
optional
equipment
Wires: 2×0.75 mm²
[9.B.1]=2 (
External sensor
=
Room
)
[1.7]
Room sensor offset
Human Comfort
Interface
See:
▪ Installation and operation manual of
the Human Comfort Interface
▪ Addendum
book
for
optional
equipment
Wires: 2×(0.75~1.25 mm²)
Maximum length: 500 m
[2.9]
Control
[1.6]
Room sensor offset
WLAN module
See:
▪ Installation manual of the WLAN
module
▪ Addendum
book
for
optional
equipment
▪ Installer reference guide
Use the cable delivered with the
WLAN module.
[D]
Wireless gateway
LAN adapter
See:
▪ Installation manual of the LAN
adapter
▪ Addendum
book
for
optional
equipment
Wires: 2×(0.75~1.25 mm²). Must be
sheathed.
Maximum length: 200 m
See installation manual of the LAN
adapter
Bizone kit
See:
▪ Installation manual of the bizone kit
▪ Addendum
book
for
optional
equipment
Use the cable delivered with the
bizone kit.
[9.P]
Bizone kit
for room thermostat (wired or wireless):
In case of…
See…
Wireless room thermostat ▪ Installation manual of the wireless
room thermostat
▪ Addendum
book
for
optional
equipment
Wired room thermostat
without multi-zoning base
unit
▪ Installation manual of the wired room
thermostat
▪ Addendum
book
for
optional
equipment
In case of…
See…
Wired room thermostat
with multi-zoning base unit
▪ Installation manual of the wired room
thermostat (digital or analogue) +
multi-zoning base unit
▪ Addendum
book
for
optional
equipment
▪ In this case:
▪ You need to connect the wired
room
thermostat
(digital
or
analogue) to the multi-zoning base
unit
▪ You need to connect the multi-
zoning base unit to the outdoor unit
▪ For cooling/heating operation, you
also need to implement a relay
(field supply, see addendum book
for optional equipment)
6.3.1
To connect the main power supply
1
Open the following (see
"4.2.1 To open the indoor unit"
6]):
1
Top panel
1
2
3
2
User interface panel
3
Upper switch box cover
2
Connect the main power supply.
In case of normal kWh rate power supply
Interconnection cable (= main
power supply)
Wires: (3+GND)×1.5 mm²
—
A
1 2 3
a
B
A
B
1 2 3
X2M
X1A
X11YA
X11YB
X11Y
X1M
a
a
Interconnection cable (=main power supply)