Set-up and installation
Installation and operating instructions
17
Daikin/ROTEX A2 F
Oil condensing boiler A2 F
008.1546499_02 – 04/2018 – EN
Installation ver-
sion
(according to im-
age 9)
Max. permissible height of the flue gas line
DN 80
A2 F 18H
A2 F 24H
A2 F 32H
1
(3)
(4)
8
12
18
2
(5)
10
14
20
3
(5)
10
14
20
4
(5)
(4)
7
7
10
5
(3)
(4)
25
25
25
6
(3)
(4)
25
25
25
Tab. 4-5
Maximum height for the flue gas line in m
Any restriction on the output range may require a recalculation of the
maximum permitted height for the flue gas duct. The characteristics
for the flue gas calculation can be obtained from
Fig. 4-6
and the
Chap. 14
.
Fig. 4-6
Flue gas mass flow in relation to the burner load (all
types)
Item
Designation
m
AG
Flue gas mass flow
P
Burner loading
Tab. 4-6
Legend for
Fig. 4-6
The flue gas mass flow of the system depends on the set burner out-
put of the A2 F.
4.5.2
Connecting a flue gas line
INFORMATION
The specialised company carrying out the work must come
to an agreement with the district chimney sweep before be-
ginning the work. Even in regions where it is not legally
specified, we recommend documenting the participation of
the district chimney sweep on a form.
Requirements
▪ The flue gas system fulfils the requirements described in
Chap.
4.5.1
.
▪ The flue gas system fulfils any required other national or regional
safety requirements.
▪ The A2 F is installed correctly.
Connection
INFORMATION
We recommend use of the associated LAS construction
sets (see
Chap. 4.5.3
). They satisfy all requirements and
are also fitted with special acid-proof seals.
The associated assembly instructions must be observed
for installing the flue gas and supply air holding system
components or their means of attachment.
1
Connect the A2 F to the flue gas system inside the installation
room (
Fig. 4-1
).
2
Place the nameplate of the flue gas duct in the installation room.
Fig. 4-7
Connection dimensions - flue gas pipe
Item
Designation
A
Boiler connection
B
Flue gas connection
Tab. 4-7
Legend for
Fig. 4-7
Connection side
Connection
Connection dimen-
sion in mm
A
Boiler side
A1
Flue gas DN 80
Collar
Inner diameter = 80.4
+0.8
A2
Supply air DN 125
Collar
Inner diameter =
127.0
-0.5
B
Flue gas side
B1
Flue gas DN 80
Inner diameter = 80.0
+0.3
B2
Supply air DN 125 Inner diameter =
126.0
+0.3
Tab. 4-8
Connection dimensions for the LAS connection of the A2
F
INFORMATION
In some cases, the resonance in the flue gas system can
amplify the noise at the mouth of the flue gas duct. The
noise level can be effectively reduced by using a silencer
(
E8 MSD
or
E11 MSD
).
(3)
Shaft cross-section of DN 80: 135 mm x 135 mm
(4)
A horizontal connecting cable with a length of 2 m and an 87° deflection are taken into account
(5)
Concentric flue gas/supply line DN 80/125