7.3  Trouble shooting 

Abnormal phenomenon 

Cause of estimated 

Method of settlement 

It does not output. 

The power supply input is not applied  Please power supply-input-check and apply. 

An alarm setter trouble 

Repair of alarm setter 

The input is not connected 

Please confirm connection of input. 

Abnormal of input 

Please confirm measurement value. 

The error of setting 

Please confirm set value. 

The output is not connected. 

Please confirm connection of output. 

Power-supply voltage is low. 

Please confirm power-supply voltage. 

Display is abnormal. 
(Large error) 

Power-supply voltage is not regulation 
range. 

Please check power-supply voltage and give as 
regulation range. 

The input is abnormal. 

Please give a measurement value as a check and a  
normal input. 

The error of set value 

Please confirm set value. 

An alarm setter trouble 

Repair of alarm setter 

Display error 
(Small error) 

Secular change of input measurement 

Display is proofread again.  
(Reference of instruction manual 7.2 section) 

Set value cannot be 
changed. 

The error of the setting method 

Please check setting method.   
(Reference of instruction manual 4.5 section.) 

An alarm setter trouble 

Repair of alarm setter 

An error is 
displayed. 

ROM  SUM value error 

Repair of alarm setter 

At the time of an EEP error, if the ENT key is 
pressed, it will become set value change mode.  
Please confirm set value.  

RAM  READ/WRITE error 

EEP  Saving value error 

A/D  A/D conversion error 

 
 

7.4 Countermeasures against troubles 

As our principle, we recall product in question and repair it.  If judged as product failure, have a contact with 
us or sales agent for repairing work (Also have a contact with us or sales agent for specification change). 
Product failure which we are not responsible for (When responsibility in manufacturing process is not recognized, 
when product is disassembled/remodeled, in case of false operation by customer, etc.) is beyond our warranty. 

 

Содержание SDLC-105A

Страница 1: ...SDLC 207 104 INSTRUCTION MANUAL LCD ALARM SETTER SDLC 105A...

Страница 2: ...epting wiring to terminal in order to prevent heat generation ignition Do not get this product near the inflammables combustible chemicals gas to prevent fire Connect specified power supply Connecting...

Страница 3: ...ension drawing 10 3 3 Connection 11 3 4 Cautions on mounting 11 3 5 LCD viewing angle 12 4 Operation method 4 1 The name and function of each part 12 4 2 Each display mode and operation 13 4 3 Measure...

Страница 4: ...e power failure guarantee of the set value Sufficient derating of uses parts and reduction of inside generation of heat improves reliability The back light is turned on at the case of key operation 30...

Страница 5: ...s maximum of each It is monitor lamp turn on the light at the case of relay excitation It is blinking among delay time at the case of the prealarm setting ON Relay and monitor lamp operation At the au...

Страница 6: ...l AL4 AL3 C2 10 9 11 AL2 AL1 C1 2 1 3 Status 3 contact outputs Each 1a contact 3 contact outputs Each 1b contact Auxiliary supply OFF or relay non excitation Terminal AL3 10 9 11 AL1 AL2 2 1 3 Termina...

Страница 7: ...n in shortage input detection Output mode Excitation L Operation value setting Relay action ON OFF Input Contact delay setting time Contact delay setting time Contact delay setting time Dead band Sett...

Страница 8: ...m function constitutes OFF Relay action and pre alarm in over input detection Output mode setting Excitation H Pre alarm setting ON Operation value setting Relay action ON OFF Dead band Setting value...

Страница 9: ...y time CD C D 3 0 0 to 180s 19 AL4 Output mode ALMD4 Low High H operation Low L operation OFF With no operation 20 Operation value COMP4 20 0 It sets in the measurement display range of 25 to 125 and...

Страница 10: ...electric circuit and case AC2000V 50 60Hz 1 minute There must not be malfunction Between input output terminals and auxiliary supply terminals Between input terminals and output terminals Between AL1...

Страница 11: ...the state of a hot line please use UR 1 for a socket connecting converting into a voltage signal UR 1 resistance designation Option Resistance in input signal Input Resistance DC0 1mA DC0 10mA DC0 16m...

Страница 12: ...mm width DIN rail mounting and screw mounting In screw mounting please mount with M4 screw However the screw is not attached And please give the mounting torque of a screw as 1 08 to 1 47N m 11 to 15k...

Страница 13: ...ation Key switch The mode to display is changed Set value check The update of data is performed The shift of set value is performed Monitor lamp AL1 to AL4 The turn on a light by relay excitation If a...

Страница 14: ...ange in set value change mode at the case of combination error occurrence Contents of error Measures ERROR 0 Scaling combination error In order that it may become MAX MIN it sets up again ERROR 1 COMP...

Страница 15: ...UP UP UP UP SHIFT Measurement value display U N I T M I N 0 0 0 0 M A X 1 0 0 0 C B I A S 0 0 0 0 C S P A N 0 0 0 0 S D 0 0 0 s A V E MODE SHIFT C D 1 0 0 0 s A L M D 1 H i g h D B 1 0 3 0 E X M D 1...

Страница 16: ...2 O N C D 2 0 0 0 s A L M D 3 L o w C O M P 3 0 3 0 0 D B 3 0 3 0 E X M D 3 O N C D 3 0 0 0 s A L M D 4 L o w C O M P 4 0 2 0 0 D B 4 0 3 0 E X M D 4 O N C D 4 0 0 0 s UP P R E A L O F F It is made t...

Страница 17: ...umber of the top digit becomes minus after 0 to 9 Note 12 The number of digits other than the top digit becomes decimal point after 0 to 9 However if decimal point is in other digits decimal point doe...

Страница 18: ...e This voltage goes into an amplifier 2 The input is converted into the suitable voltage range in an amplifier This voltage constitutes an input of an A D converter 3 The data converted into digital o...

Страница 19: ...careful of the next item 1 It is checked whether a body and socket combination are normal is a lock a totality 2 It checks for the slack of wiring and the slack of a captive screw 3 It will remove if...

Страница 20: ...m setter Display error Small error Secular change of input measurement Display is proofread again Reference of instruction manual 7 2 section Set value cannot be changed The error of the setting metho...

Страница 21: ...setting change mode and use the seal accessory in combination Unit symbol sheet Accessory If there is no unit symbol you want to use in the above sheet by specifying the unit symbol at the time of or...

Страница 22: ...13 Hitotsuya 1 chome Adachi ku Tokyo 121 8639 JAPAN TEL 81 3 3885 2411 Fax 81 3 3858 3966 Kyoto Office 1 19 Ichinobe Nishikawahara Jyoyou shi Kyoto 610 0114 JAPAN TEL 81 774 55 1391 Fax 81 774 54 1353...

Отзывы: