SDLC-207-104 

 

 
 

2.6  Performance  

Item 

Specification 

Setting accuracy (

±0.1% (% for input span) 

Display accuracy (

)(

)  ±0.1% (% for input span) ±1digit 

Reproducibility of the 
operating point  (

±0.1% (% for input span) 

Operating time accuracy 

±0.25 seconds of contact delay time set value  
(However, in case of set value = 0 second. 0.5±0.25 seconds)  

Reset time 

Less than 0.5 seconds 

Starting delay time 
accuracy 

±0.25 seconds of starting delay time set value 

Influence of temperature  0.2% (For input span) /23±10℃ 
Influence of auxiliary 
supply voltage variation 

0.1% (For input span) /Within variation range 

Operation period 

About 0.1 second 

Response time 

About 0.5 second  
(In case 90 to 110% of step variation of operation value setting is given, in CD=0 second)  

Overload 
capacity 

Voltage input  2 times 10 seconds and 1.5 times continuation of rated voltage. 
Current input  10 times 5 seconds and 1.5 times continuation of rated current. 
Aux. supply 

1.5 times 10 seconds of rated voltage.  And upper limit of the variation range is continued. 

Insulation resistance 

Between electric circuit and case. 

Above 50MΩ at DC500V. 

Between input, output terminals and auxiliary supply terminals. 
Between input terminals and output terminals. 
Between AL1 output terminals and AL2 output terminals. 
(Only two alarm contact output specification) 
Between AL1 output terminals and AL2 output terminals  
and AL3 output terminals. 
(Only three alarm contact output specification)  
Between AL1・AL2 output terminals and AL3・AL4 output terminals. 
(Only four alarm contact output specification) 

Power frequency 
withstand voltage 

Between electric circuit and case. 

AC2000V (50/60Hz) 1 minute. 
There must not be malfunction. 

Between input, output terminals and auxiliary supply terminals. 
Between input terminals and output terminals. 
Between AL1 output terminals and AL2 output terminals. 
(Only two alarm contact output specification) 
Between AL1 output terminals and AL2 output terminals  
and AL3 output terminals. 
(Only three alarm contact output specification)  
Between AL1・AL2 output terminals and AL3・AL4 output terminals. 
(Only four alarm contact output specification) 

Impulse withstand 
voltage 

Between electric circuit and case. 

5kV 1.2/50μs.   
Positive and negative 
polarity for each 3 times. 
There must not be malfunction. 

Vibration 

Vibration of vibration frequency 16.7Hz,Double amplitude 1mm.  In the direction of X Y Z for 
each 10 minutes.  There must not be malfunction. 

Shock 

Error:98m/s

2

,  X, Y, Z direction for each 3 times. 

Duration:294m/s

2

,  X, Y, Z direction for each 3 times. 

Power failure guarantee  Each set value is data-saved by non-volatilized memory. 
Material of case 

Case:Flame resisting ABS resin , Name plate:Polyester film , Socket:Glass filled PBT resin 

Appearance color 

Case, Socket:Munsell N1.5 (Black) , Name-plate:Gray 

Operating temperature 
and humidity limits 

-10 to +55℃ , 5 to 90%RH (Non condensing) 

Storage temperature 
limits 

-25 to +70℃ 

Mass 

Approx. 350g 

Accessories 

Socket,Unit symbol sheet,Instruction manual 

Note(

) Input is DC60mV to less than 1V, DC±60mV to less than ±1V. ±0.2% (% for input span) 

Note(

) Input is DC60mV to less than 1V, DC±60mV to less than ±1V. ±0.2% (% for input span) ±1digit. 

note(

) In more than 10000 (5 digits except decimal point), a measurement display span constitutes ±0.1% (%  

for input span)±2digit.  And, if input is less than 1V and measurement display span is 10000 or more.  
±0.2% (% for input span) ±2digit. 

 

Содержание SDLC-105A

Страница 1: ...SDLC 207 104 INSTRUCTION MANUAL LCD ALARM SETTER SDLC 105A...

Страница 2: ...epting wiring to terminal in order to prevent heat generation ignition Do not get this product near the inflammables combustible chemicals gas to prevent fire Connect specified power supply Connecting...

Страница 3: ...ension drawing 10 3 3 Connection 11 3 4 Cautions on mounting 11 3 5 LCD viewing angle 12 4 Operation method 4 1 The name and function of each part 12 4 2 Each display mode and operation 13 4 3 Measure...

Страница 4: ...e power failure guarantee of the set value Sufficient derating of uses parts and reduction of inside generation of heat improves reliability The back light is turned on at the case of key operation 30...

Страница 5: ...s maximum of each It is monitor lamp turn on the light at the case of relay excitation It is blinking among delay time at the case of the prealarm setting ON Relay and monitor lamp operation At the au...

Страница 6: ...l AL4 AL3 C2 10 9 11 AL2 AL1 C1 2 1 3 Status 3 contact outputs Each 1a contact 3 contact outputs Each 1b contact Auxiliary supply OFF or relay non excitation Terminal AL3 10 9 11 AL1 AL2 2 1 3 Termina...

Страница 7: ...n in shortage input detection Output mode Excitation L Operation value setting Relay action ON OFF Input Contact delay setting time Contact delay setting time Contact delay setting time Dead band Sett...

Страница 8: ...m function constitutes OFF Relay action and pre alarm in over input detection Output mode setting Excitation H Pre alarm setting ON Operation value setting Relay action ON OFF Dead band Setting value...

Страница 9: ...y time CD C D 3 0 0 to 180s 19 AL4 Output mode ALMD4 Low High H operation Low L operation OFF With no operation 20 Operation value COMP4 20 0 It sets in the measurement display range of 25 to 125 and...

Страница 10: ...electric circuit and case AC2000V 50 60Hz 1 minute There must not be malfunction Between input output terminals and auxiliary supply terminals Between input terminals and output terminals Between AL1...

Страница 11: ...the state of a hot line please use UR 1 for a socket connecting converting into a voltage signal UR 1 resistance designation Option Resistance in input signal Input Resistance DC0 1mA DC0 10mA DC0 16m...

Страница 12: ...mm width DIN rail mounting and screw mounting In screw mounting please mount with M4 screw However the screw is not attached And please give the mounting torque of a screw as 1 08 to 1 47N m 11 to 15k...

Страница 13: ...ation Key switch The mode to display is changed Set value check The update of data is performed The shift of set value is performed Monitor lamp AL1 to AL4 The turn on a light by relay excitation If a...

Страница 14: ...ange in set value change mode at the case of combination error occurrence Contents of error Measures ERROR 0 Scaling combination error In order that it may become MAX MIN it sets up again ERROR 1 COMP...

Страница 15: ...UP UP UP UP SHIFT Measurement value display U N I T M I N 0 0 0 0 M A X 1 0 0 0 C B I A S 0 0 0 0 C S P A N 0 0 0 0 S D 0 0 0 s A V E MODE SHIFT C D 1 0 0 0 s A L M D 1 H i g h D B 1 0 3 0 E X M D 1...

Страница 16: ...2 O N C D 2 0 0 0 s A L M D 3 L o w C O M P 3 0 3 0 0 D B 3 0 3 0 E X M D 3 O N C D 3 0 0 0 s A L M D 4 L o w C O M P 4 0 2 0 0 D B 4 0 3 0 E X M D 4 O N C D 4 0 0 0 s UP P R E A L O F F It is made t...

Страница 17: ...umber of the top digit becomes minus after 0 to 9 Note 12 The number of digits other than the top digit becomes decimal point after 0 to 9 However if decimal point is in other digits decimal point doe...

Страница 18: ...e This voltage goes into an amplifier 2 The input is converted into the suitable voltage range in an amplifier This voltage constitutes an input of an A D converter 3 The data converted into digital o...

Страница 19: ...careful of the next item 1 It is checked whether a body and socket combination are normal is a lock a totality 2 It checks for the slack of wiring and the slack of a captive screw 3 It will remove if...

Страница 20: ...m setter Display error Small error Secular change of input measurement Display is proofread again Reference of instruction manual 7 2 section Set value cannot be changed The error of the setting metho...

Страница 21: ...setting change mode and use the seal accessory in combination Unit symbol sheet Accessory If there is no unit symbol you want to use in the above sheet by specifying the unit symbol at the time of or...

Страница 22: ...13 Hitotsuya 1 chome Adachi ku Tokyo 121 8639 JAPAN TEL 81 3 3885 2411 Fax 81 3 3858 3966 Kyoto Office 1 19 Ichinobe Nishikawahara Jyoyou shi Kyoto 610 0114 JAPAN TEL 81 774 55 1391 Fax 81 774 54 1353...

Отзывы: