SDLC-207-104
9
2.6 Performance
Item
Specification
Setting accuracy (
4
)
±0.1% (% for input span)
Display accuracy (
5
)(
6
) ±0.1% (% for input span) ±1digit
Reproducibility of the
operating point (
4
)
±0.1% (% for input span)
Operating time accuracy
±0.25 seconds of contact delay time set value
(However, in case of set value = 0 second. 0.5±0.25 seconds)
Reset time
Less than 0.5 seconds
Starting delay time
accuracy
±0.25 seconds of starting delay time set value
Influence of temperature 0.2% (For input span) /23±10℃
Influence of auxiliary
supply voltage variation
0.1% (For input span) /Within variation range
Operation period
About 0.1 second
Response time
About 0.5 second
(In case 90 to 110% of step variation of operation value setting is given, in CD=0 second)
Overload
capacity
Voltage input 2 times 10 seconds and 1.5 times continuation of rated voltage.
Current input 10 times 5 seconds and 1.5 times continuation of rated current.
Aux. supply
1.5 times 10 seconds of rated voltage. And upper limit of the variation range is continued.
Insulation resistance
Between electric circuit and case.
Above 50MΩ at DC500V.
Between input, output terminals and auxiliary supply terminals.
Between input terminals and output terminals.
Between AL1 output terminals and AL2 output terminals.
(Only two alarm contact output specification)
Between AL1 output terminals and AL2 output terminals
and AL3 output terminals.
(Only three alarm contact output specification)
Between AL1・AL2 output terminals and AL3・AL4 output terminals.
(Only four alarm contact output specification)
Power frequency
withstand voltage
Between electric circuit and case.
AC2000V (50/60Hz) 1 minute.
There must not be malfunction.
Between input, output terminals and auxiliary supply terminals.
Between input terminals and output terminals.
Between AL1 output terminals and AL2 output terminals.
(Only two alarm contact output specification)
Between AL1 output terminals and AL2 output terminals
and AL3 output terminals.
(Only three alarm contact output specification)
Between AL1・AL2 output terminals and AL3・AL4 output terminals.
(Only four alarm contact output specification)
Impulse withstand
voltage
Between electric circuit and case.
5kV 1.2/50μs.
Positive and negative
polarity for each 3 times.
There must not be malfunction.
Vibration
Vibration of vibration frequency 16.7Hz,Double amplitude 1mm. In the direction of X Y Z for
each 10 minutes. There must not be malfunction.
Shock
Error:98m/s
2
, X, Y, Z direction for each 3 times.
Duration:294m/s
2
, X, Y, Z direction for each 3 times.
Power failure guarantee Each set value is data-saved by non-volatilized memory.
Material of case
Case:Flame resisting ABS resin , Name plate:Polyester film , Socket:Glass filled PBT resin
Appearance color
Case, Socket:Munsell N1.5 (Black) , Name-plate:Gray
Operating temperature
and humidity limits
-10 to +55℃ , 5 to 90%RH (Non condensing)
Storage temperature
limits
-25 to +70℃
Mass
Approx. 350g
Accessories
Socket,Unit symbol sheet,Instruction manual
Note(
4
) Input is DC60mV to less than 1V, DC±60mV to less than ±1V. ±0.2% (% for input span)
Note(
5
) Input is DC60mV to less than 1V, DC±60mV to less than ±1V. ±0.2% (% for input span) ±1digit.
note(
6
) In more than 10000 (5 digits except decimal point), a measurement display span constitutes ±0.1% (%
for input span)±2digit. And, if input is less than 1V and measurement display span is 10000 or more.
±0.2% (% for input span) ±2digit.