SDLC-207-104
8
2.5 Setting value
№
Contents
Mark
Initial value
Setting range
2 contact
outputs
3 contact
outputs
4 contact
outputs
1 Unit display
UNIT
%
%,m,℃,m
3
/h,ppm,pH,TPm,×10kg,Ω,kW
2 Minimum value scaling
MIN
0.0
-9999 to 9999 -9.99 to 99.99
-99.9 to 999.9 0.000 to 9.999
3 Maximum value scaling
MAX
100.0
4
AL1
Output mode
ALMD1
High
High
High
High:H operation,Low:L operation,
OFF :With no operation
5
Operation value
COMP1
70.0
80.0
80.0
It sets in the measurement display range
of -25 to +125%, and is a real scale.
6
Dead band
D.B.1
3.0
0.5 to 50.0%
7
Excitation mode
EXMD1
0N
ON:Excitation,OFF:Non-excitation
8
Contact delay time (CD) C.D.1
0
0 to 180s
9
AL2
Output mode
ALMD2
Low
High
High
High:H operation,Low:L operation,
OFF :With no operation
10
Operation value
COMP2
30.0
70.0
70.0
It sets in the measurement display range
of -25 to +125%, and is a real scale
11
Dead band
D.B.2
3.0
0.5 to 50.0%
12
Excitation mode
EXMD2
0N
ON:Excitation,OFF:Non-excitation
13
Contact delay time (CD) C.D.2
0
0 to 180s
14
AL3
Output mode
ALMD3
-
Low
Low
High:H operation,Low:L operation,
OFF :With no operation
15
Operation value
COMP3
-
30.0
30.0
It sets in the measurement display range
of -25 to +125%, and is a real scale
16
Dead band
D.B.3
-
3.0
0.5 to 50.0%
17
Excitation mode
EXMD3
-
ON
ON:Excitation,OFF:Non-excitation
18
Contact delay time (CD) C.D.3
-
0
0 to 180s
19
AL4
Output mode
ALMD4
-
Low
High:H operation,Low:L operation,
OFF :With no operation
20
Operation value
COMP4
-
20.0
It sets in the measurement display range
of -25 to +125%, and is a real scale
21
Dead band
D.B.4
-
3.0
0.5 to 50.0%
22
Excitation mode
EXMD4
-
ON
ON:Excitation,OFF:Non-excitation
23
Contact delay time (CD) C.D.4
-
0
0 to 180s
24 Starting delay time (SD)
S.D.
5
1 to 180s
25 Bias point calibration
CBIAS
0.00
-9.99 to 9.99% (% for input span)
26 Span point calibration
CSPAN
0.00
-9.99 to 9.99% (% for input span)
27 Average number
AVE
1
1,4,8,16,32
28 Prealarm
PREAL
OFF
ON:Prealarm ON, OFF:Prealarm OFF
< Notes of setting >
・The decimal point position change of scaling is made by the minimum value scaling.
If the decimal point position is changed, the decimal point position of maximum value scaling and operation values
1 to 4 will also change. If the decimal point position is changed, please be sure to check the set value of
a maximum value scaling and an operation value.
・An operation value can be set up in -25 to +125% of the measurement display range (minimum value scaling to
maximum value scaling).
(Example) Input 4 to 20mA, Operation value -25.0, Output mode is "Low" setting.
It becomes L detection in 0mA of inputs, it is also possible to use it as
disconnection detection.
・After setting change, in case a set value combination error occurs, it becomes a setting error display.
Please push the
key and set up the right set value (in set value change mode).
125%
100%
50%
0%
-25%
24mA
20mA
12mA
4mA
0mA