42
Note 1)
1
Neither indoor unit nor outdoor unit runs.
Check the following points first. (There are following case in normal operation)
a. Is the timer mode set the "timer ON".
b. Is the timer mode set the "timer-OFF" and the time had passed?
2
Neither outdoor fan nor compressor runs while indoor fan runs.
Check following points first. (There are following cases in normal operation)
a. Is the temperature set point suitable?
b. Has the 3 minutes time guard for compressor operated?
Self-Diagnostic Function
Error CODE
Display
Check point
1
ON+Air clean LAMP
I/D Sensor Registance check
1 time blink
I/D Sensor Connection check
2
Timer LAMP
O/D Sensor Registance check
1 time blink
O/D Sensor Connection check
3
ON+Air clean LAMP
Compressor and its electrical parts check
2 times blink
Leakage check.
I/D Sensor assembly check
4
Timer LAMP
Communication wire check
2 times blink
(between I.D.U and O.D.U)
5
ON+Air clean LAMP
4-way and its electrical parts check
3 times blink
Leakage check.
6
ON+Air clean LAMP
check operation mode each two Indoor units.
and Quick+Timer LAMP blink
Содержание DMB-1812LH
Страница 36: ...36 5 WIRING DIAGRAM ...
Страница 47: ...PCBDRIVINGDESCRIPTION ...
Страница 48: ...1 PCB CIRCUIT DIAGRAM DMB 1812LH Outdoor ...
Страница 49: ......
Страница 50: ...DMB 1812LH 12K ...
Страница 51: ......
Страница 52: ...DMB 1812LH 9K ...
Страница 53: ......
Страница 77: ...74 6 U9 KIA7042P RESET IC KIA70 42P OUTLINE INPUT GROUND OUTPUT VCC 1 3 2 OUT GND ...
Страница 81: ...78 3 EXPLODED DIAGRAM Indoor Unit DMB 1812LH 9K ...
Страница 83: ...80 DMB 1812LH 12K ...
Страница 86: ...83 4 EXPLODED DIAGRAM Outdoor Unit DMB 1812LH ...
Страница 88: ...85 5 CONTROL BOX ASSEMBLY DMB 1812LH 9K ...
Страница 90: ...87 DMB 1812LH 12K ...
Страница 92: ...89 DMB 1812LH Outdoor ...