Ductwork Equivalent Lengths
For each new elbow and transition, you must subtract “equivalent lengths” from your total
maximum duct run length to compensate for wind resistance.
Piece
Subtract
8” 90° Elbow
7 feet
8” 45° Elbow
3 feet
10” 90° Elbow
5 feet
10” 45° Elbow
2 feet
3” x 10” to Round 90° Transition
25 feet
3 1/4” x 10” to 8”/10” Round Transition
4 feet
Wall Cap w/Damper
Roof Cap
Equivalent lengths of roof and wall caps
vary with model and configuration.
Ductwork Tips
•
Try to minimize transitions/turns/sharp angles (e.g., two staggered 45° angles are better than
one sharp 90° angle).
•
Keep turns as far from the hood exhaust as possible
with
as much space between bends
as
possible.
•
U
se round instead of rectangular ducting, especially when elbows are
needed.
•
If multiple elbows are used, try to keep at least 24 in. of straight duct between each elbow.
•
Avoid using “S” or back-to-back adjacent elbows.
•
In extremely cold-weather regions, use thermal breaks (i.e., short sections of non-metallic duct)
to avoid indoor heat loss. Put the break as close to the outside pass-through point as possible.
•
Do not use flexible metal ducting, or ductwork smaller than what the tables advise.
•
The hood exhaust connects to an 8” round duct. You can increase the duct size over the duct run.
•
To prevent backdraft, never decrease the duct size over the run. If existing ductwork is
under
8
"
in diameter, replace it with 8” ductwork.
•
Join ducting with sheet-metal screws, then seal with certified duct/foil tape. Never join ducting
with tape only.
•
Support the weight of the ducting with sheet-metal screws as needed.
•
To avoid backdraft, a damper at the duct outlet may be required.
WARNING
•
Electricity to the range hood should be installed only by a licensed electrician.
•
Observe all local codes during installation. Con
sul
t
the
local building
department
as needed
.
•
A
nchor the hood to the wall
as instructed to avoid an
injury
hazard
.
•
To avoid electric-shock and property damage, do not drill/cut near in-wall plumbing and wiring.
•
Use the temporary
support
brackets only until the hood is permanently
anchored.