ENGLISH
52
Water alarm =
represents an alarm linked with dry running (overflow, system excess pressure, etc.).
Pump alarm =
represents an alarm linked with pump protection (pump thermal protection, current
overload, etc.).
Self-resettable
alarm =
the control unit reactivates the pump if the cause that generated the alarm is removed,
or in cases where this is not possible it makes attempts at intervals.
Blocking alarm =
the control unit keeps the pump stopped until it is manually reset.
14.1 Protection/Alarm coming from the digital inputs R and N.
Digital
inputs
Pressure boosting function
Filling function
Draining function
R
Max. Pressure
The 2 pumps stop with:
- general alarm signal,
-
remote signal
Q1
Min. Level (in tank)
The 2 pumps start with:
- general alarm signal,
- remote signal
Q1
Intervention and reset after 0.5
seconds.
Max. Level
The 2 pumps start with:
- general alarm signal,
- remote signal
Q1
Intervention and reset after 0.5
seconds.
N
Min. Pressure
The 2 pumps stop with:
- general alarm signal,
- alarm signal against
dry running.
- remote signal
Q1
Max. Level
(in tank)
The 2 pumps stop with:
- general alarm signal,
- remote signal
Q1
Min. Level (water reserve)
The 2 pumps stop with:
- general alarm signal,
- indication against dry
running
.
- remote signal
Q1
Intervention and reset after 1
second.
**
Min. Level
The 2 pumps stop with:
- general alarm signal,
- alarm signal against
dry running,
- remote signal
Q1
Intervention and reset after 1
second.
Attention!
If not used, a jumper
must be fitted on terminals
R
and
N
.
Attention!
If not used, a jumper
must be fitted on terminal
N.
Attention!
If not used, a jumper
must be fitted on termina
l N.
** only in the case of a water reserve must the float be in this position:
14.2 Pressure sensor alarm
If the panel detects a pressure sensor with a dip-
switch configuration incoherent with the device
installed, an alarm signal is given
.
However it is
possible to operate the panel.
If sensor operation is selected with a dip-switch, but
the panel does not detect the sensor, the pumps are
deactivated and an alarm signal is given.
If the pressure sensor has been correctly installed,
but the sensor signal is outside the measuring
range, the pumps are deactivated and an alarm
signal is given.
14.3 Dip-Switch alarm
The Dip Switch alarm is activated in the following
cases:
Incoherence of the Dip Switch with the respective
functions (incorrect regulation).
To reset the alarm:
Return the Dip Switches to the correct position.
Press the RESET key.
Dip Switch regulation with the panel live.
To reset the alarm:
Press the RESET key.
NO
Содержание E-BOX 2G M
Страница 133: ...129 7 QS1 OFF 0 L1 L2 L3 L N 230 400 7 1 L1 L2 L3 L1 L2 L3...
Страница 137: ...133 9 0 OFF I ON 1 2 3 4 5 6 7 8 9 1 2 3 1 4 5 1 6 1 3 2 7 8 2 9 2 3...
Страница 141: ...137 24 DS_A2 2 12 12 1 2 2 1 2 1 2 12 2 3 3 1 2 1 2...
Страница 142: ...138 3 12 3 SP DP SP LMAX DP LMIN DP 1 2 SP 1 2 DP 1 5 DP SP SP 2 24 DS_A2 2 95 5 DP P1 P2 OFF P1 P2 ON DP 25 1 SP 4...
Страница 143: ...139 13 13 1 2 2 1 2 1 2 13 2 3 3 1 2 1 2...
Страница 144: ...140 13 3 SP DP SP LMAX DP LMIN SP 1 5 2 DP 1 2 SP 1 5 SP DP DP 2 24 DS_A2 2 95 5 DP P1 P2 ON P1 P2 OFF DP 25 1 SP 4...
Страница 146: ...142 14 1 R N R 2 Q1 2 Q1 0 5 2 Q1 0 5 N 2 Q1 2 Q1 2 Q1 1 2 Q1 1 R N N N 14 2 14 3 RESET RESET NO...
Страница 147: ...143 14 4 1 2 8 5 8 6 10 24 14 5 1 DS_A4 0 5 10 9 5 8 1 1 30 14 6 8 9 5 8 8 14 7 1 2 9 5 8 1 60 1 2 3 60 14 8 30 14 9...
Страница 148: ...144 15 EXP 1 16 8 2 5x20 T 100 3 4 230 10 5 EXP 1 2 3 4 5...
Страница 169: ...165 7 OFF 0 L1 L2 L3 L N QS1 230V 400V 7 1 L1 L2 L3 L1 L2 L3...
Страница 173: ...169 9 0 OFF I ON 1 2 3 4 5 6 7 8 9 1 2 3 RESET P1 4 5 P1 6 P1 3 P2 7 8 P2 9 P2 3...
Страница 177: ...173 24 DS_A2 2 12 12 1 2 2 P1 B P2 C B P1 P2 B C B B C 12 2 3 3 P1 B P2 C A B C P1 P2 B C A B C A B C...
Страница 179: ...175 13 13 1 2 2 P1 B P2 C B P1 P2 B C B C B C 13 2 3 3 P1 B P2 C P1 P2 B C A B C A B C 13 3...
Страница 180: ...176 SP DP SP LMAX DP LMIN SP P1 5 P2 DP P1 P2 SP P1 5 SP DP DP 2 24 DS_A2 2 DP m 25 1 SP 4 m 95 5 DP P1 P2 ON P1 P2 OFF...
Страница 184: ...180 15 EXP EXP 1 16 8 2 5x20 T 100mA 3 4 230VAC 10VA 5 EXP 1 2 3 4 5...
Страница 186: ......
Страница 187: ......
Страница 188: ......
Страница 189: ......
Страница 190: ......
Страница 191: ......