1 Product Introduction
DGS-1210 series Metro Ethernet Managed Switch User Manual
12
The following section explains how to connect the DPS-200A/500A/500DC to the Switch.
•
Disconnect the Switch from the main AC power source.
•
Insert the 14-pin end of the DPS-CB150-2PS into the DPS-200A/500A/500DC and the 2-pin end into
the receptacle of the RPS port on the Switch.
•
Using a standard AC power cord, connect the DPS-200A/500A/500DC to the main AC power source.
A green LED on the front panel of the DPS-200A/500A/500DC will illuminate to indicate a
successful connection.
•
Make sure that the ON/OFF toggle switch on the rear panel of the Switch is turned on.
•
Re-connect the Switch to the AC power source and power on the DPS-200A/500A/500DC.
No configuration is needed in the Switch software for this installation.
NOTE:
See the DPS-200A/500A/500DC Quick Installation Guide for
more information.
Installing the RPS into a Rack-mount Chassis (for DGS-1210-10/12TS/20/28/28X/28XS/52/ME
only)
The DPS-200A/500A/500DC are the redundant power supply unit designed to conform to the voltage
requirements of the RPS port of the Switch being supported. The DPS-200A/500A/500DC can be installed
into a DPS-800 rack-mount chassis unit.
CAUTION:
DO NOT connect the RPS to the AC power before the DC
power cable is connected. Connecting the AC power before the DC
power is connected might damage the internal power supply.
DPS-800 Rack-mount Chassis
The DPS-800 is a standard-size rack-mount (1 standard unit in height) designed to hold up to three DPS-
200A/500A/500DC redundant power supplies.
Figure 1.32 –Installing the DPS-200A/500A/500DC in the DPS-800
The DPS-800 rack-mount chassis can be mounted into a standard 19" rack. Use the following diagram to
guide you.