9/12

99.823.83

Rev.: 1.1

1 2

3 4

5 6

7 8

ON

LEDs und Functions

on

off

flashing

off

off

on

LED line fault

LED OK

LED general fault

Line fault

Deactivated line

Servicetimer is up

flashing

flashing

flashing

LED Indication

Line switch-off

hold 3 s to switch off
line /
tip on to switch on

If the LED line fault flashes, the line is
switched off, e.g. for service reasons. You
cannot activate the control panel in this
status.

In case of an actual line error the

LED line fault is permanently on.

DIP switch
factory-set

Programmable by
D+H Distributor with
D+H PDA servicetool

Functions
not changeable

The signalling relay features the following signals:

(factory-set: signalling relais 1="alarm"
signalling relais 2 = "general fault")

Accumulator

Group output

If wind or rain detector is connected.

Do not ventilate via smoke vent button because otherwise there is danger
of damage by wind or water.

optional vent button

LT 43U-W

Gap ventilation

is not possible

if no vent button LT 43U-W is

available

LT 43U-W

pre-alarm, terminated alarm, delayed alarm
general fault, accumulator fault, line fault, group fault, power failure
earth fault, passing on of "central CLOSE", "Reset Alarm" as pulse,
group closed longer = x s

Charge (temperature-guided)
Monitoring: presence, final discharging voltage
Discharge control: In case of power failure and total discharge of accumulator,
the control panel will switch off. In this case, smoke vent is no longer possible.
In this case the LED System O.K. and the LED general fault are not on.

Three minutes after the motor group has been operated in OPEN or CLOSE
direction, the potential between Mot.a and Mot.b is switched to zero potential.

If the respective sensor releases, the group of the control panel will close. Wind
velocities can be adjusted to 4-6 Bft.
If the alarm is released by a smoke and heat vent system, the system will open
regardless of wind and rain.

The weather automatic can be switched-off with an

, if gap ventilation is required in case of bad weather.

in case of bad weather,

. If the weather automatic is switched on via vent button

, the

system will automatically close in case of wind or rain. The system will not
automatically open again, if wind or rain has stopped. Opening of the system for
ventilation via vent button.
For further information see information for use VRS 10 REM 42 and WRG 82.

Содержание RZN 4503-T

Страница 1: ...nnection mounting and functional testing by a specialist company authorized by the manufacturer Green control diodes in the buttons must constantly be on otherwise see Information for Starting Repair...

Страница 2: ...After the maintenance time is expired ca 14 to 16 months the ventilation function OPEN can be interrupted depending on the presetting of the service timer Reset can be carried out by a specialist comp...

Страница 3: ...ensation for damage Therefore regular maintenance and checking of functional readiness is imperative and must be ensured These standard requirements are demanded in accordance with regulations of the...

Страница 4: ...t function CLOSE Fault Charging voltage controller Battery LED system O K DIP switch factory set see p 9 and 11 LED mains LED alarm LED group fault LED battery fault LED earthfault Reset line LED line...

Страница 5: ...BZUG RAUCHABZUG RZN RT 4 click 1 2 4 RAUCHABZUG RAUCHABZUG 3 RZN RT RZN 4503 T Operation Release in case of alarm Manual opening by smoke vent button Automatic opening by fire detector o r a n d Autom...

Страница 6: ...With manual release Opening the housing RZN RT with supplied key Automatic opening by external control see DIP switch S1 page 8 hold for OFF shortly tap for ON 3 s o r o r function is deactivatable b...

Страница 7: ...rtner com Service 12 month 12 month RAUCHABZUG www dh partner com Service 12 month 12 month In case of power failure Emergency closing In case of non resettable alarm hold for OFF 3 s see DIP switch S...

Страница 8: ...and the smoke vent opens e g at an interrupted button line or missing terminal resistor In case of a group fault the control panel will be switched to alarm and the smoke vent opens e g in case of an...

Страница 9: ...tor fault line fault group fault power failure earth fault passing on of central CLOSE ResetAlarm as pulse group closed longer x s Charge temperature guided Monitoring presence final discharging volta...

Страница 10: ...y stage of fire Protected wiring is required with protection against mechanical damages according to DIN 18232 section 2 5 5 paragraph 4 Cable from the smoke vent control panel to connection of drive...

Страница 11: ...ives smoke vent buttons if necessary fire detectors and vent buttons See wiring and connection plans Mounting and Installation Set DIP switch S1 on motherboard as follows Resistor must be cramped in e...

Страница 12: ...detector individual by D H smoke detector tester as an alternative by cigarette smoke response delay circa 20 s Red display diode must be on Smoke vent must open For closing wait until there is no mo...

Страница 13: ...meldezentrale Contact external control e g fire alarm system JY St Y 4x2x0 6 JY St Y 4x2x0 6 JY St Y 2x2x0 6 Zentrale RZN Aufputz 230VAC 24VDC in der N he der RWA Klappe Control panel RZN surface type...

Страница 14: ...cht eingesetzt werden The resistor must not be used when line connections with 2 detector dependency are employed N N A K S Unterbrechertaster Interrupter button Haftmagnet Magnetic clamp Haftmagnete...

Отзывы: