background image

2/12

99.823.83

Rev.: 1.1

Once a year by a specialist company
authorised by the equipment manufacturer.
Renew test badge. Update logbook.

The respective current D+H maintenance
instructions should be followed.
A D+H authorised company has been specially
trained by D+H for carrying out this
maintenance competently and will be
automatically provided with the latest
maintenance instructions.
Following tests must be carried out during
maintenance:
-

External examination and inspection of
system components

-

Measuring of insulation resistances

-

Checking of all relevant power supply
units.

-

Functional testing of connected system
components.

-

Logging of competent execution of
maintenance and identification in
accordance with directions.

Information

An overdue maintenance of the system will be
indicated by the control panel after about
14 to 16 months. The yellow diode in the
control panel and in the smoke vent button
RT 43-H will start flashing.
A malfunction in the smoke vent system will be
continually indicated by the extinguished
green control diodes in the smoke vent
buttons.
After the maintenance time is expired (ca. 14 to
16 months), the ventilation function OPEN can
be interrupted depending on the presetting of
the service timer. Reset can be carried out by a
specialist company only who has been
authorized by the appliance manufacturer.

Content

Maintenance

Rated voltage

: 230 VAC, 50 Hz

(+10%, -15%)

Rated capacity

: 100 VA

Capacity con

-

tion standby

: < 5 W

Interfering

emission

: EN 61000-6-3 (08.02)

Res. to jamming : EN 61000-6-2 (08.02)
Protective

category

: I

Fire resistance

: -5 to +40 °C

Protective system : IP30
Class of rating
- Monitoring

: Continuous duty

- Emergency

state/ ventilation : Short-time duty

Output voltage

: 24 VDC / res. ripple <5%

Safe output
- rated current

: 3 A (30% power-on time)

Dimensions

: 156x83x232 (W x D x H)

D+H Highspeed (HS) drives will be

sump

maximum no. of fire detectors: 14 pcs.
maximum no. of smoke vent buttons: 8 pcs.

Technical Data

1 x pre-assembled control panel
1 x

housing

1 x breaking glas
3 x hanger bolt
6 x hexagonal nut M5 DIN 6923-8
1 x mounting tool
1 x sheet "smoke vent" different languages
2 x key

pre-assembled

Scope of delivery

Guarantee
Technical Data, Maintenance, Scope of delivery

..................8

LEDs und functions

..................................................................................................................................1

..........................................................................2

Introduction................................................................................................................................3
Overview operating elements.....................................................................................................4
Operating...............................................................................................................................5-7
Extended functions...................................................................................................

.....................................................................................................................9

Cable und Emergency Supply...................................................................................................10
Starting.....................................................................................................................................11
Examination.............................................................................................................................12

Содержание RZN 4503-T

Страница 1: ...nnection mounting and functional testing by a specialist company authorized by the manufacturer Green control diodes in the buttons must constantly be on otherwise see Information for Starting Repair...

Страница 2: ...After the maintenance time is expired ca 14 to 16 months the ventilation function OPEN can be interrupted depending on the presetting of the service timer Reset can be carried out by a specialist comp...

Страница 3: ...ensation for damage Therefore regular maintenance and checking of functional readiness is imperative and must be ensured These standard requirements are demanded in accordance with regulations of the...

Страница 4: ...t function CLOSE Fault Charging voltage controller Battery LED system O K DIP switch factory set see p 9 and 11 LED mains LED alarm LED group fault LED battery fault LED earthfault Reset line LED line...

Страница 5: ...BZUG RAUCHABZUG RZN RT 4 click 1 2 4 RAUCHABZUG RAUCHABZUG 3 RZN RT RZN 4503 T Operation Release in case of alarm Manual opening by smoke vent button Automatic opening by fire detector o r a n d Autom...

Страница 6: ...With manual release Opening the housing RZN RT with supplied key Automatic opening by external control see DIP switch S1 page 8 hold for OFF shortly tap for ON 3 s o r o r function is deactivatable b...

Страница 7: ...rtner com Service 12 month 12 month RAUCHABZUG www dh partner com Service 12 month 12 month In case of power failure Emergency closing In case of non resettable alarm hold for OFF 3 s see DIP switch S...

Страница 8: ...and the smoke vent opens e g at an interrupted button line or missing terminal resistor In case of a group fault the control panel will be switched to alarm and the smoke vent opens e g in case of an...

Страница 9: ...tor fault line fault group fault power failure earth fault passing on of central CLOSE ResetAlarm as pulse group closed longer x s Charge temperature guided Monitoring presence final discharging volta...

Страница 10: ...y stage of fire Protected wiring is required with protection against mechanical damages according to DIN 18232 section 2 5 5 paragraph 4 Cable from the smoke vent control panel to connection of drive...

Страница 11: ...ives smoke vent buttons if necessary fire detectors and vent buttons See wiring and connection plans Mounting and Installation Set DIP switch S1 on motherboard as follows Resistor must be cramped in e...

Страница 12: ...detector individual by D H smoke detector tester as an alternative by cigarette smoke response delay circa 20 s Red display diode must be on Smoke vent must open For closing wait until there is no mo...

Страница 13: ...meldezentrale Contact external control e g fire alarm system JY St Y 4x2x0 6 JY St Y 4x2x0 6 JY St Y 2x2x0 6 Zentrale RZN Aufputz 230VAC 24VDC in der N he der RWA Klappe Control panel RZN surface type...

Страница 14: ...cht eingesetzt werden The resistor must not be used when line connections with 2 detector dependency are employed N N A K S Unterbrechertaster Interrupter button Haftmagnet Magnetic clamp Haftmagnete...

Отзывы: