8/12
99.823.83
Rev.: 1.1
Extended Functions
The following functions are set by the DIP switch S1 on the PCB at the control panel, or can be set by a
D+H distributor with the D+H PDA service tool:
S1.1 ON =
CLOSE
S1.2 ON =
OPEN
S1.2 OFF=
OPEN
Storage operation
S1.1 OFF= Key operation
CLOSE
Storage operation
Key operation
S1.3 ON = activated
S1.3 OFF = deactivated
S1.4 ON = activated
S1.4 OFF = deactivated
S1.5 ON = activated
S1.5 OFF = deactivated
S1.6 ON = activated
S1.6 OFF = deactivated
S1.7 ON = activated
S1.7 OFF = deactivated
S1.8 ON
S1.8 OFF
Programmable by
D+H Distributor with
D+H PDA servicetool
Storage operation
Key operation
Line fault = alarm
Group fault on alarm
OPEN-running time limitation in ventilation operation
Ventilation time limitation
Power failure CLOSED
vent buttons
activitated
vent buttons
deactivitated
deactivated
deactivated
deactivated
activated
activated
Press ventilating button 1 x shortly. The drives/ NSHEVs will open to
their final position.
The drives/NSHEVs will open only as long as the ventilating button is
pressed.
In case of a line fault the control panel will be switched to alarm and the
smoke vent opens (e.g. at an interrupted button line or missing
terminal resistor).
In case of a group fault the control panel will be switched to alarm and
the smoke vent opens (e.g. in case of an interrupted drive line or
missing terminal module).
If the vent button is actuated in direction OPEN, the drives/ NSHEVs
open for 30 s (factory-set). This running time can be edited by D+H
PDA servicetool. Only possible in conjunction with storage operation
in CLOSE-direction.
The drives/ NSHEVs will automatically close again after the time set
(factory-set 10 min). This time can be edited by the D+H PDA
servicetool. Only possible in conjunction with storage operation in
CLOSE direction!
In case of power failure the drives will close. Only possible in
conjunction with storage operation in CLOSE direction!
Integrated
are
Integrated
are
OPEN running time retriggering (factory-set:
)
Group CLOSE in case of alarm (factory-set:
)
Two smoke detectors dependency (factory-set:
)
Smoke detector alarm remote reset (factory-set:
)
Lamp test
Alarm re-clocking (factory-set:
)
Hint: In case of alarm the smoke vent is triggered with an OPEN pulse
every 2 minutes for a duration of 30 minutes according to VdS 2581.
For this, the drive must be protected against blockage according to
VdS 2580 par. 4.7. . All D+H drives meet this precondition.