18/20
RZN 4416-M Rev.:1.1
Codification of Control Panel S6
Codification of Line S1, S3
Switch 1 on ON
= Line 2 on group 3
“OFF“
Line 2 is also effective on group 3
In case of alarm of one line, the other line will be set on alarm as well
Factory-setting must be on
Actuate DIP-switch (ON / OFF).
LED’s will light up for 3 seconds in control panel
Switch 1 on OFF
=
Switch 2 on ON
= Central alarm
Switch 3 on ON
= Power failure-CLOSED
ON
Switch 4 on ON
=
Switch 5
=
Switch 6 on ON
= LED Test / Reset WDT error (Watch Dog Timer)
Switch 7
=
Switch 8
=
Group 3 is independent of line 2
If the power supply breaks down, the drive will close.
Only when group-DIP switch 4 (key operation in CLOSED-direction) =
idle
idle
idle
Bus control
Switch 1 on ON =
Two-smoke detectors dependency
Attention!
Switch
Smoke detector alarm can be reset only in control panel
Dip switch 2 must be switched on OFF, when remote reset is desired of smoke detectors by the
smoke vent button.
Switch
Switch
Alarm will be triggered only, if at least two smoke detectors of one line respond.
False alarm of one smoke detector will be prevented.
Two smoke detectors in one room must be always installed.
If only one smoke detector is connected to one line, switch is on OFF!
Smoke detector alarm can
be reset by single pressing on button in smoke
vent button.
(Only in conjunction with FO 1362)
See also page 14 about this.
2 on ON
=
3 on ON
= Line fault = alarm
smoke vent opens
line fault
4
=
The control panel will be switched on alarm, that means the
at
a
(e.g. at an interrupted detector line or short circuit).
idle
not