Preparation:

Notify user, that the system is out of operation
before starting with inspection.
Notify user about false alarms.
Interrupt or switch off monitored alarm
indication and remote controls.

Inspection:

Check all appliances and cable connections
for outer damage and dirt accumulation.
Fire detectors, smoke vent buttons, smoke
vents and so on must not be impaired in
their function by goods in storage or
structural changings.

Smoke vent button:

Open smoke vent button.
Press red button 

, red display diode 

lightens in button and control panel.
Smoke vent must open.
Press masked button 

 (1 sec.), red display

diode 

 extinguishes in button and control

panel.
Smoke vent must close.

Automatic fire detectors:

Release smoke detector individual by D+H-
smoke detector tester, as an alternative by
cigarette smoke (response delay circa 20
sec.).
Red display diode must lighten.
Smoke vent must open.
For closing wait until there is no more smoke
in detector.
Reset line in control panel (switch off/ switch
on press button), red display diode 
extinguishes in button and control panel.

Press masked button 

 in smoke vent

button. Smoke vent must be closing.
The line can also be directly reset via smoke
vent button, if  Dip switch 9 is switched on OFF.
For this, press masked button 

 in smoke

vent button (for 1 second).
Red display diode 

 extinguishes in button

and in control panel. Smoke vent must close.
At severe dirt accumulation visible from
outside or false alarms, send detector in for
maintenance and install an exchange
detector.

External control (optional):

Release external control.
Smoke vent must open.
Open contact in external system for closing,
for example by resetting of fire detector
system.
Press masked button 

 in smoke vent

button (1 second). Red display diode 
extinguishes in button and control panel.
Smoke vent must close.

Emergency supply:

Detach fuse MAINS on motherboard of
control panel.
Green mains indication diode 

 on control

panel must not lighten.
Repeat functioning testing.
Green control diode 

 in smoke vent

buttons must not lighten. Ventilation is out of
function.
If Dip switch 4 and 5 on ON, the group will be
automatically closing.

Examination

Every six months and after repair by a specialist or staff, who has been introduced to the task.

Eliminate failings at once. Keep control book.

Содержание RZN 4416-M

Страница 1: ...orized by the manufacturer Green control diodes in the buttons must constantly lighten otherwise see Informations for Starting Repair power failure at once Emergency power supply for 72 hours drive gr...

Страница 2: ...Maintenance Guarantee Piktograph explanation 2 Technical Data Accumulator Control TID 3 Introduction 4 View motherboard RZN 4416 K 5 Drives and smoke vent buttons 6 Wiring plan 7 Connection cables 8...

Страница 3: ...al discharge of accumulator the control panel will switch off In this case smoke vent is no longer ensured In this case a malfunction will be no more indicated either Technical Data Rated voltage 230...

Страница 4: ...Insurer against damage of property VdS and the respective local authorities Recommended is that maintenance work should be carried out by authorized specialist companies only Only regular and profess...

Страница 5: ...reset indicator fuse accumulator accumulator connection LED failure accumulator charging voltage control accumulator fire recognition element thermo maximum signal ground short DIP switch S6 control p...

Страница 6: ...hat an escape must not be hindered by the window wing itself by structural facts like offsets or the like Minimum ventilating surface is given by le gal regulations and structural facts The smoke vent...

Страница 7: ...mer Fire detector 24VDC FO 1362 or FT 1262 Wiring Plan Paragon 230 V Supply Provide for separate electric circuit Mark fuses Plug covering cap over mains binder on motherboard of control panel Connect...

Страница 8: ...ause of a large variety on the market Please consult your D H distributor about these The smoke vent control panel is designed for opening smoke vent devices which operate by thermal ascending force a...

Страница 9: ...ector THE 4 RZN 4416 M RM MOT branch box Length of line and cross sections see page 12 last RT 43 N 10kW alarm control line line malfunction closed 2 7 8 3 1 6 4 line control alarm closed 2 3 1 6 4 7...

Страница 10: ...4 5 6 7 8 RZN 4416 M line control alarm closed RM RT Smoke vent button RT 43 H Smoke vent button RT 43 N 10kW alarm alarm control control line line line line malfunction closed closed 2 2 7 8 7 3 3 1...

Страница 11: ...vent button lane 2nd RT 43 H RT 43 H RT 43 N RT 43 N 10kW alarm alarm control control line line line line malfunction malfunction closed closed 2 2 7 7 8 8 3 3 1 1 6 6 4 4 alarm alarm zu zu red red gr...

Страница 12: ...losed open signal optional N open monitoring Mot a Mot b 5 6 7 1 2 3 4 1 1 2 2 optional RM RT LT 3 4 5 6 7 8 line control alarm closed external excitiation vent button LT 43 SD fire detector Typ opera...

Страница 13: ...e vent button 1st lane RT 42 Smoke vent button 2nd lane RT 42 10kW RT 42 RT 42 line line line control control control alarm alarm alarm closed closed closed 7 7 7 2 2 2 3 3 3 1 1 1 6 6 6 4 4 5 4 OK OK...

Страница 14: ...ctor dependency are employed Connection of several fire detectors Connection of one fire detector N N Z M1 M2 D1 D2 interrupter key magnetic clamp terminal resistor line 10K single fire detector 180R...

Страница 15: ...a Mot b derive off in par allel monitoring will be looped through all cables up to group end Example 1 1 lane Simple installation but unfavourable for voltage drop All drives on one line Example 2 2 l...

Страница 16: ...special conditions only Performance check alarm reset and ventilation 10k resistance in smoke vent button 10k resistance in fire detector Stop module 2x47k in conduit box Connect mains mains control l...

Страница 17: ...e limitation be retriggered again Switch 4 on ON Storage operation in CLOSED direction Switch 4 on OFF Key operation in CLOSED direction Switch 5 on ON Storage operation in OPEN direction Switch 5 on...

Страница 18: ...n idle idle idle Bus control Switch 1 on ON Two smoke detectors dependency Attention Switch Smoke detector alarm can be reset only in control panel Dip switch 2 must be switched on OFF when remote res...

Страница 19: ...on Ventilating time limitation OPEN retriggering Duty cycle in CLOSED direction Duty cycle in OPEN direction Group CLOSED in case of alarm Group fault on alarm Alarm re clocking OPEN running time limi...

Страница 20: ...tector Reset line in control panel switch off switch on press button red display diode extinguishes in button and control panel Press masked button in smoke vent button Smoke vent must be closing The...

Отзывы: