6/36
CPS-M1
English
99.827.31 1.4/06/18
Power packs PS-S1-24-20 and PS-S1-24-40
Functions:
•
Output: 24 V DC, 20 A or 40 A
• Installation on 35 mm top hat rail
•
Low ripple
• Reverse-voltage protected and short-circuit resistant
•
Multiple power supply units can be combined
•
For each power supply unit, one PSM supply module is needed
Technical data:
Type
PS-S1-24-20
Rated input voltage
230 V AC ± 15%
Frequency
45 to 65 Hz
Nominal power
530 VA / 480 W
Output voltage
24 V DC ± 1%
Ripple
< 50 mVSS
Output current
20 A
Short-circuit resistant
YES
Can be connected in parallel YES
Reverse-voltage protected
YES
Input line connection
max. 6 mm² star / max. 4 mm² flexible
Output line connection
max. 6 mm² star / max. 4 mm² flexible
Dimensions WxHxD
90x130x150 mm
Type
PS-S1-24-40
Rated input voltage
230 V AC ± 15%
Frequency
45 to 65 Hz
Nominal power
1040 VA / 960 W
Output voltage
24 V DC ± 1%
Ripple
< 50 mVss
Output current
40 A
Short-circuit resistant
YES
Can be connected in parallel YES
Reverse-voltage protected
YES
Input line connection
max. 6 mm² star / max. 4 mm² flexible
Output line connection
max. 16 mm² star / max. 16 mm² flexible
Dimensions WxHxD
140x130x150 mm
Connec-
tion
Description
L
Phase
N
Neutral
PE
Protective earth
+
24 V DC output
-
Actuator module - AM-1-1-08-230-D4-D2
Functions:
•
Module for connecting 230 V AC actuators
•
1 group for connecting drives with a total maximum
current of 8 A
•
D+H 230 V AC drives with SHEV fast mode (HS) are
supported
•
The cable is monitored for breaks and short circuits
via the terminal module EM 230
• 2 user-programmable digital inputs (e.g. ventilation
button)
•
1 user-programmable digital output (e.g. NOT CLO
-
SED signal)
•
Can be used with 230 V AC standard drives
•
Adjustable ventilation time and opening width for
everyday ventilation
•
Integrated LEDs to indicate a fault (yellow) and alarm (red)
• Connection using removable spring-type terminals
•
Conductor cross-sections max. 2.5 mm² flexible
(230 V AC) or 1.5 mm² flexible (24 V DC)
• Dimensions WxHxD: 26x130x125 mm
•
Installation on a 35 mm top hat rail in combination with
an expansion module socket