CPS-M1

English

99.827.31 1.4/06/18

Designation

Description

-

Reference potential / negative:

 used as the reference potential for external peripherals (e.g. SHEV operation panel or 

LT).

May not be connected to P-.

The reference potentials of more than one power supply module may not be connected together.

ACB.A x / ACB.B x 

MOT.a x / MOT.b x

Group (ACB):

 used for the connection of bus-capable drives.

ACB.A x and ACB.B x are necessary for communication with the drives.

MOT.a x and MOT.b x are necessary for supplying the connected drives.

The maximum output current of the supply is 10 A.

The supply is permanently short-circuit resistant and the fuse used is self-resetting.

ACN D+ / ACN D-

Shield

AdComNet connection:

 used for interconnecting more than one CPS-M1 and for interconnecting with ACN-CM501, 

ACN-IO501, ACN-BI501-USB and ACN-GW501-MRTU.

If this connection is not used, it must nevertheless be terminated with a resistor (110 Ohm).

BATT+ / BATT-

Battery connection:

 may only be used for connecting the secondary power supply (battery).

COM x / NC x / NO x

(monostable, CRM

Isolated output:

 used for the triggering of external systems.

The maximum contact current is 1 A.

The minimum contact current to ensure permanent safe operation is 10 mA.

The maximum contact voltage is 35 V DC.

The contact is not suitable for switching 230 V AC.

The output can be supplied with emergency power. This is to be taken into consideration in the battery capacity calcula

-

tion.

COM x / NC x / NO x

(bistable, BRM)

Isolated output:

 used for the triggering of external systems.

The maximum contact current is 3 A.

The minimum contact load to ensure permanent safe operation is 5 V / 10 mA.

The maximum contact voltage is 30 V DC or 265 V AC.

DI x.x

Digital input:

 used for the evaluation of switch signals.

The input voltage range is 0 V DC to 28 V DC.

The pull-up resistor for the evaluation of an active negative signal is integrated.

The pull-down resistor for the detection of an active positive signal is integrated.

The switching contact is briefly (< 100 ms) loaded with 16 mA.

The input DI 1.1 of the controller module cannot currently be used.

DO x.x

Digital output:

 used for the triggering of displays or relays.

The output voltage range of an activated output is 17 V DC to 25 V DC.

The output voltage range applies for a maximum output current of 50 mA.

The connection is permanently short-circuit resistant and the fuse used is self-resetting.

If the output is deactivated, the output is open / has a high resistance.

Active negative inputs cannot be switched using the output.

The output can be supplied with emergency power. This is to be taken into consideration in the battery capacity calcula

-

tion.

FE

Functional earth:

 

can be used as the cable shielding connection when connecting a smoke detector line

.

May only be used as a cable shielding connection. 

LINE / RT x

Line connection:

 used for connecting a smoke detector line or an SHEV operation panel line. Furthermore, external 

systems (e.g. fire detectors) can be connected.

LINE / RM x

A maximum of 30 smoke detectors or 10 SHEV operation panels can be connected.

The connection is permanently short-circuit resistant and the fuse used is self-resetting.

Cable monitoring is performed via the EM-L01.

MOT.A x / MOT.B x

E/HS

Group (polarity change):

 used for the connection of conventional pole-changing drives.

MOT.A x and MOT.B x are necessary for the supply and for controlling the direction.

The maximum output current of the supply is 10 A.

The supply is permanently short-circuit resistant and the fuse used is self-resetting.

E/HS is used for cable monitoring and for triggering the high-speed function.

n.c.

The terminal is not connected.

N+

Operating voltage not supplied with emergency power:

 used for the supply of external peripherals.

The output voltage range is 22 V DC to 24 V DC.

The maximum output current is 440 mA.

P-

Group reference potential / group negative:

 used as the reference potential for external drives (e.g. spring return 

actuators).

May not be connected to –.

The group reference potentials of more than one power supply module may not be connected together.

+

Operating voltage supplied with emergency power:

 used for the supply of external peripherals.

The current consumption of the connected peripherals must be taken into consideration in the battery capacity calcula

-

tion.

The output voltage range is 19 V DC to 27 V DC.

The maximum output current is 440 mA.

SGI x

This function has not yet been implemented.

SNT+ / SNT-

Mains power connection:

 may only be used for connecting the primary power supply (power pack).

TCSU1

Temperature sensor connection:

 may only be used for connecting the TCSU1-RJ12.

The maximum cable length to ensure permanent safe operation is 2 m.

TP-C1

Touch panel connection:

 may only be used for connecting the TP-C1-35-RJ12.

Description of the inputs and outputs

Содержание CPS-M1

Страница 1: ...CPS M1 Anerkennungs Nr approval no G 517002 0786 CPD 50680 EN 12101 10 2005 Corr 1 2007 conform 99 827 31 1 4 06 18 en Original instructions Page 2...

Страница 2: ...operating voltage Risk of injury from electric shock Only an authorised electrically skilled person is allowed to connect the power Keep children away from the controller Only use in dry spaces Only...

Страница 3: ...PS M and further D H AdComNet SHEV control system Simple implementation of complex SHEV scenarios High flexibility and expandability Each control panel functions autonomously when the bus connection f...

Страница 4: ...re control sensor unit TCSU1 RJ12 31 702 70 RJ12 connecting cable 2x CC TP TCSU 1000 1 m 63 502 63 CC TP TCSU 2000 2 m 63 502 64 Touch panel with bracket optional TP C1 35 RJ12 31 702 90 Page 5 Contro...

Страница 5: ...4 V DC actuators 2 independent groups for connecting drives each with a total maximum current of 10 A The cable is monitored for breaks and short circuits via the terminal module EM 47K Each group is...

Страница 6: ...S Can be connected in parallel YES Reverse voltage protected YES Input line connection max 6 mm star max 4 mm flexible Output line connection max 16 mm star max 16 mm flexible Dimensions WxHxD 140x130...

Страница 7: ...eserve must be smaller than the capacity of the battery Standard batteries For each PS S1 24 20 PSM 2 x battery type 5 12 V 18 Ah 15 For each PS S1 24 40 PSM 2 x battery type 6 12 V 26 Ah 15 24 V emer...

Страница 8: ...MA CPS M1 060 xxxx Fig CPS M1 060 0206 Standard equipment 31 700 55 CPS M1 060 0206 CM PSM AM AM PSM AM TMA 31 700 60 CPS M1 060 0208 CM PSM AM AM PSM AM AM TMA 31 700 65 CPS M1 060 0210 CM PSM AM AM...

Страница 9: ...t of it Each additional PSM always provides power only to the modules to the right of it This applies also to the emergency battery power Therefore the modules are to be distributed evenly across the...

Страница 10: ...plying the drive Mot a Mot b For pole changing drives 1 additional wire for cable monitoring through which the SHEV high speed HS signal is also transmitted to the drive For ACB drives 2 additional wi...

Страница 11: ...E Connection PSM RJ12 connecting cable CC TP TCSU max 2 m Battery Battery No Name Description X2 1 N Output potential without an emergency supply for ventilation functions max 500 mA X2 2 Reference po...

Страница 12: ...et slave interface X5 2 ACN D X5 3 ACN D X6 5 n c n c X6 4 DI 1 1 Freely configurable digital input 0 to 28 V active minus or plus control panel OPEN factory setting can be pro grammed using SCS X6 3...

Страница 13: ...puts 24 V DC Each max 50 mA programmable using SCS Battery for the clock of the event memory The CM module has a built in lithium battery on the underside which buffers the internal clock of the event...

Страница 14: ...ly configurable digital output 3 4 X3 2 DO 3 3 freely configurable digital output 3 3 X3 3 Reference potential do not connect to P X3 4 DO 3 2 freely configurable digital output 3 2 X3 5 DO 3 1 freely...

Страница 15: ...utput 2 COM X3 1 NC 3 Floating output 3 normally closed X3 2 COM 3 Floating output 3 COM X3 3 NO 3 Floating output 3 normally open X3 4 COM 3 Floating output 3 COM X4 4 COM 4 Floating output 4 COM X4...

Страница 16: ...X3 2 ACB B 2 ACB interface of drive group 2 X3 1 ACB A 2 X4 4 SGI 1 Position transmitter for drive group 1 not yet implemented X4 3 Reference potential do not connect to P X4 2 SGI 2 Position transmit...

Страница 17: ...4 3 3 3 2 2 2 1 1 1 X1 X2 X3 X6 X5 X4 DI 1 1 DI 1 2 DO 1 1 DI 2 1 DI 2 2 DO 2 1 SGI 2 SGI 1 4 3 2 1 ACB B 2 ACB A 1 ACB A 2 ACB B 1 Mot b 2 Mot a 2 Mot b 1 E HS 1 E HS 2 P Mot a 1 P EM 47 K 2x47kW BK...

Страница 18: ...X2 4 E Monitoring wire X4 5 Reference potential do not connect to P X4 4 ACB Supply of the ACB interface not yet implemented X4 3 ACB A ACB interface of drive group not yet implemented X4 2 ACB B X4 1...

Страница 19: ...0 V AC 50 Hz L N PE ION O OFF ION O OFF before vor avant Battery Service switch off the battery Batterieschalter auf OFF schalten d brancher la batterie ION O OFF L N L N PE K1 K2 K1 K2 K1 1 2 3 4 5 6...

Страница 20: ...Freely configurable digital output 4 1 max 50 mA X6 5 DO 3 2 A Freely configurable digital output 3 2 max 50 mA X6 4 DO 3 3 S Freely configurable digital output 3 3 max 50 mA X6 3 Reference potential...

Страница 21: ...S 6 A 1 K 2 3 5 T 8 5 R 2 3 bu rd EM L01 5 R 2 3 bu rd EM L01 2 8 3 5 T n c 4 Z 7 S 6 A 1 K OK RT 45 4 Z 7 S 6 A 1 K OK 2 8 3 5 T n c RT 45 OK RT 45 OK SD O 371 FD T 271 SD O 371 FD T 271 rd bu EM L0...

Страница 22: ...Z 7 7 S S 6 6 A A 1 1 K K OK rd bu EM L01 X1 1 X1 5 X2 1 X2 5 X3 1 X3 5 5 4 3 2 1 5 4 3 2 1 TMA 1 D4 D12 5 5 5 4 4 4 3 3 3 2 1 2 1 2 1 X1 X2 X3 X6 X5 X4 5 4 3 2 1 A S n c n c T K FE Z R FE n c Z S n...

Страница 23: ...ent of 50 mA The connection is permanently short circuit resistant and the fuse used is self resetting If the output is deactivated the output is open has a high resistance Active negative inputs cann...

Страница 24: ...e by approximately 13 in order to protect the devices F Battery Mode lights up The NSV 401 runs in back up operation AC power supply not present or beyond the tole rance range If necessary the require...

Страница 25: ...x Art Nr 70 200 05 Typ 5 Same as Long WP18 12 Battery capacity 12 Ah 4 x Art Nr 70 200 00 Typ 4 Same as Long WP12 12 Technical Data Safety Notes Operating voltage 230 VAC Risk of injury from electric...

Страница 26: ...ACB B SGI 2 2 1 1 4 3 2 1 AM 1 1 08 230 D4 D2 4 4 3 3 2 2 1 1 X1 X2 X6 X5 DI 2 1 DO 2 1 DI 1 1 DI 1 2 DO 1 1 L L L N E N N L NSV 1 2 3 4 5 6 7 8 9 EM 230 N E L L 1 2 3 4 5 6 7 8 9 E N L L EM 230 L N L...

Страница 27: ...l the enclo sed fuse BF1 80A between battery A and battery B WARNING A short circuit may occur if the cover is removed 2 3 1 BF1 80A 12 V 18 Ah 12 V 18 Ah 12 V 18 Ah 12 V 18 Ah BF1 80A 12 V 12 Ah 12 V...

Страница 28: ...Service and Configuration Suite SCS is used for commissioning and programming Functions programmable via SCS Alarm with HS ATTENTION This function must only be used in conjunction with corresponding D...

Страница 29: ...odule 1 Trigger Line1 Actuator Module 1 Actuator Group 1 2 Trigger Module 1 Trigger Line2 Actuator Module 2 Actuator Group 1 2 Trigger Module 2 Trigger Line1 Actuator Module 3 Actuator Group 1 Trigger...

Страница 30: ...or Group 1 2 Trigger Module 2 Trigger Line2 Actuator Module 4 Actuator Group 1 2 Trigger Module 3 Trigger Line1 Actuator Module 5 Actuator Group 1 Trigger Module 3 Trigger Line2 Actuator Module 5 Actu...

Страница 31: ...the set ventilation time Mains outage CLOSED The group automatically moves in the CLOSED direction in the event of a mains outage Only the control panel groups move in the CLOSED direction in the eve...

Страница 32: ...ts IOM I O module Display of the module status Display of the status of the inputs and outputs Modules Overview of all modules used Display of the respective statuses similar to the LEDs on the respec...

Страница 33: ...using the smoke vent button as otherwise there is a risk of wind or water damage If gap ventilation is desired in bad weather the weather automation can be switched off using an optional automatic sw...

Страница 34: ...tion Closing after alarm Manual opening with smoke vent button Automatic opening with fire detector Automatic opening through external control e g central fire alarm For manual triggering using smoke...

Страница 35: ...ied out once a year by a specialist company authorised by the device manufacturer Carry out cleaning and maintenance work only when the system is de energised Replace the inspection plate maintain the...

Страница 36: ...eorg Sasse Str 28 32 22949 Ammersbek Germany Tel 4940 605 65 239 Fax 4940 605 65 254 E Mail info dh partner com www dh partner com 2016 D H Mechatronic AG Ammersbek Subject to technical modifications...

Отзывы: