CPS-M1

English

99.827.31 1.4/06/18

Control module – CM-BT1-D4-P2

Functions:

•  Central control element of the control panel (segment 

coupler)

•  One CM controller module is required for each CPS-M

• 

Each CM controller module can manage up to 29 addition

-

al modules (PSM, AM, TMA)

• 

AdComNet interfaces for implementing decentralised sys

-

tems in combination with other AdComNet control panels

• 

USB interface for configuring the system and for firmware 

updates of the control panel and the connected drives 

(only ACB)

• 

Integrated LEDs to indicate operation (green), fault 

(yellow), alarm (red) and AdComNet operation

•  Status displays for all modules of the respective CPS-M 

as well as emergency operation of the individual lines and 

groups using the 3.5" TFT touch panel

• 

Three user-programmable digital inputs for connecting 

buttons, switches, external controls etc.

• 

Two user-programmable, isolated change-over contacts, 

for example, for fault and alarm notifications

•  Integrated event memory for system analysis and 

traceability

•  Connection using removable spring-type terminals

•  Conductor cross-sections max. 1.5 mm² Flexible

•  Dimensions WxHxD: 26x130x125 mm

• 

Installation on a 35 mm top hat rail in combination with a 

basic module socket

Supply module – PSM-1-24-40

Functions:

• 

Power supply of the control panel system

•  Max. 40 A load current for each supply module 

depending on the power supply unit

•  If a load current of more than 40 A is required, another 

PSM (including supply module socket) can be used.

• 

The PSM always provides power to the actuator and 

trigger modules used to the right of it

• 

Automatic toggling between mains supply and battery 

supply in case of a mains outage

•  Max. battery capacity 26 Ah (battery type 6)

•  72 hours of emergency supply time

•  Integrated protection against excessive discharge

• 

Temperature-controlled charging voltage with external 

temperature sensor

• 

Integrated LED to indicate a fault (yellow)

• 

Two connections for peripherals that are and are not 

supplied with emergency power

•  Connection using removable spring-type terminals

• 

Conductor cross-sections max. 2.5 mm² flexible or for 

supply and battery 6 mm² flexible

•  Dimensions WxHxD: 26x130x125 mm

• 

Installation on a 35 mm top hat rail in combination with 

a basic module socket or for more than one power 

supply unit with a supply module socket

Actuator module – AM-1-2-10-24-D6-D2

Functions:

• 

Module for connecting 24 V DC actuators

• 

2 independent groups for connecting drives, each with 

a total maximum current of 10 A

• 

The cable is monitored for breaks and short circuits 

via the terminal module EM-47K

• 

Each group is electronically protected against 

overload

•  6 user-programmable digital inputs (e.g. ventilation 

button)

• 

2 user-programmable digital outputs (e.g. NOT 

CLOSED signal)

•  2 integrated ACB interfaces for reading out and 

configuring the connected ACB drives

• 

Can be used with 24 V DC pole-changing drives and 

ACB drives

• 

Virtual groups in connection with ACB drives possible

• 

Adjustable ventilation time and opening width for 

everyday ventilation

• 

Integrated LEDs to indicate a fault (yellow) and alarm 

(red)

•  Connection using removable spring-type terminals

•  Conductor cross-sections max. 2.5 mm² Flexible

•  Dimensions WxHxD: 26x130x125 mm

• 

Installation on a 35 mm top hat rail in combination with 

an expansion module socket

Trigger module – TMA-1-D4-D12

Digital I/O module - IOM-D1-1212

Bistable relay module - BRM-1-COC-0006

Functions: 

•  Module for connecting trigger peripheral devices

• 

Two independent lines for connecting a max. of 10 

SHEV buttons and 30 fire detectors per line (only 

detectors approved by D+H may be used)

• 

Cables are monitored by the EM-L01 terminal module

• 

The SCS software can be used to configure the lines 

also as user-programmable digital inputs and outputs

• 

Integrated LEDs to indicate a fault (yellow) and alarm 

(red)

•  Connection using removable spring-type terminals

•  Conductor cross-sections max. 1.5 mm² Flexible

•  Dimensions WxHxD: 26x130x125 mm

• 

Installation on a 35 mm top hat rail in combination with 

an expansion module socket

Functions: 

•  12 user-programmable digital inputs

•  12 user-programmable digital outputs

• 

The digital inputs can also be parameterised as LT inputs

• 

Integrated LEDs to indicate a fault (yellow) and alarm 

(red)

•  Connection using removable spring-type terminals

•  Conductor cross-sections max. 1.5 mm² Flexible

•  Dimensions WxHxD: 26x130x125 mm

• 

Installation on a 35 mm top hat rail in combination with 

an expansion module socket

Functions: 

•  Six user-programmable, isolated change-over contacts, 

for switching signals with 24 V DC or 230 V AC

•  change-over contacts as bistable version

• 

Definition of a switch-off state in the event of a mains and 

battery failure possible (failsafe function)

• 

Integrated LEDs to indicate a fault (yellow) and alarm 

(red)

•  Connection using removable spring-type terminals

•  Conductor cross-sections max. 2.5 mm² Flexible

•  Dimensions WxHxD: 26x130x125 mm

• 

Installation on a 35 mm top hat rail in combination with 

an expansion module socket

Содержание CPS-M1

Страница 1: ...CPS M1 Anerkennungs Nr approval no G 517002 0786 CPD 50680 EN 12101 10 2005 Corr 1 2007 conform 99 827 31 1 4 06 18 en Original instructions Page 2...

Страница 2: ...operating voltage Risk of injury from electric shock Only an authorised electrically skilled person is allowed to connect the power Keep children away from the controller Only use in dry spaces Only...

Страница 3: ...PS M and further D H AdComNet SHEV control system Simple implementation of complex SHEV scenarios High flexibility and expandability Each control panel functions autonomously when the bus connection f...

Страница 4: ...re control sensor unit TCSU1 RJ12 31 702 70 RJ12 connecting cable 2x CC TP TCSU 1000 1 m 63 502 63 CC TP TCSU 2000 2 m 63 502 64 Touch panel with bracket optional TP C1 35 RJ12 31 702 90 Page 5 Contro...

Страница 5: ...4 V DC actuators 2 independent groups for connecting drives each with a total maximum current of 10 A The cable is monitored for breaks and short circuits via the terminal module EM 47K Each group is...

Страница 6: ...S Can be connected in parallel YES Reverse voltage protected YES Input line connection max 6 mm star max 4 mm flexible Output line connection max 16 mm star max 16 mm flexible Dimensions WxHxD 140x130...

Страница 7: ...eserve must be smaller than the capacity of the battery Standard batteries For each PS S1 24 20 PSM 2 x battery type 5 12 V 18 Ah 15 For each PS S1 24 40 PSM 2 x battery type 6 12 V 26 Ah 15 24 V emer...

Страница 8: ...MA CPS M1 060 xxxx Fig CPS M1 060 0206 Standard equipment 31 700 55 CPS M1 060 0206 CM PSM AM AM PSM AM TMA 31 700 60 CPS M1 060 0208 CM PSM AM AM PSM AM AM TMA 31 700 65 CPS M1 060 0210 CM PSM AM AM...

Страница 9: ...t of it Each additional PSM always provides power only to the modules to the right of it This applies also to the emergency battery power Therefore the modules are to be distributed evenly across the...

Страница 10: ...plying the drive Mot a Mot b For pole changing drives 1 additional wire for cable monitoring through which the SHEV high speed HS signal is also transmitted to the drive For ACB drives 2 additional wi...

Страница 11: ...E Connection PSM RJ12 connecting cable CC TP TCSU max 2 m Battery Battery No Name Description X2 1 N Output potential without an emergency supply for ventilation functions max 500 mA X2 2 Reference po...

Страница 12: ...et slave interface X5 2 ACN D X5 3 ACN D X6 5 n c n c X6 4 DI 1 1 Freely configurable digital input 0 to 28 V active minus or plus control panel OPEN factory setting can be pro grammed using SCS X6 3...

Страница 13: ...puts 24 V DC Each max 50 mA programmable using SCS Battery for the clock of the event memory The CM module has a built in lithium battery on the underside which buffers the internal clock of the event...

Страница 14: ...ly configurable digital output 3 4 X3 2 DO 3 3 freely configurable digital output 3 3 X3 3 Reference potential do not connect to P X3 4 DO 3 2 freely configurable digital output 3 2 X3 5 DO 3 1 freely...

Страница 15: ...utput 2 COM X3 1 NC 3 Floating output 3 normally closed X3 2 COM 3 Floating output 3 COM X3 3 NO 3 Floating output 3 normally open X3 4 COM 3 Floating output 3 COM X4 4 COM 4 Floating output 4 COM X4...

Страница 16: ...X3 2 ACB B 2 ACB interface of drive group 2 X3 1 ACB A 2 X4 4 SGI 1 Position transmitter for drive group 1 not yet implemented X4 3 Reference potential do not connect to P X4 2 SGI 2 Position transmit...

Страница 17: ...4 3 3 3 2 2 2 1 1 1 X1 X2 X3 X6 X5 X4 DI 1 1 DI 1 2 DO 1 1 DI 2 1 DI 2 2 DO 2 1 SGI 2 SGI 1 4 3 2 1 ACB B 2 ACB A 1 ACB A 2 ACB B 1 Mot b 2 Mot a 2 Mot b 1 E HS 1 E HS 2 P Mot a 1 P EM 47 K 2x47kW BK...

Страница 18: ...X2 4 E Monitoring wire X4 5 Reference potential do not connect to P X4 4 ACB Supply of the ACB interface not yet implemented X4 3 ACB A ACB interface of drive group not yet implemented X4 2 ACB B X4 1...

Страница 19: ...0 V AC 50 Hz L N PE ION O OFF ION O OFF before vor avant Battery Service switch off the battery Batterieschalter auf OFF schalten d brancher la batterie ION O OFF L N L N PE K1 K2 K1 K2 K1 1 2 3 4 5 6...

Страница 20: ...Freely configurable digital output 4 1 max 50 mA X6 5 DO 3 2 A Freely configurable digital output 3 2 max 50 mA X6 4 DO 3 3 S Freely configurable digital output 3 3 max 50 mA X6 3 Reference potential...

Страница 21: ...S 6 A 1 K 2 3 5 T 8 5 R 2 3 bu rd EM L01 5 R 2 3 bu rd EM L01 2 8 3 5 T n c 4 Z 7 S 6 A 1 K OK RT 45 4 Z 7 S 6 A 1 K OK 2 8 3 5 T n c RT 45 OK RT 45 OK SD O 371 FD T 271 SD O 371 FD T 271 rd bu EM L0...

Страница 22: ...Z 7 7 S S 6 6 A A 1 1 K K OK rd bu EM L01 X1 1 X1 5 X2 1 X2 5 X3 1 X3 5 5 4 3 2 1 5 4 3 2 1 TMA 1 D4 D12 5 5 5 4 4 4 3 3 3 2 1 2 1 2 1 X1 X2 X3 X6 X5 X4 5 4 3 2 1 A S n c n c T K FE Z R FE n c Z S n...

Страница 23: ...ent of 50 mA The connection is permanently short circuit resistant and the fuse used is self resetting If the output is deactivated the output is open has a high resistance Active negative inputs cann...

Страница 24: ...e by approximately 13 in order to protect the devices F Battery Mode lights up The NSV 401 runs in back up operation AC power supply not present or beyond the tole rance range If necessary the require...

Страница 25: ...x Art Nr 70 200 05 Typ 5 Same as Long WP18 12 Battery capacity 12 Ah 4 x Art Nr 70 200 00 Typ 4 Same as Long WP12 12 Technical Data Safety Notes Operating voltage 230 VAC Risk of injury from electric...

Страница 26: ...ACB B SGI 2 2 1 1 4 3 2 1 AM 1 1 08 230 D4 D2 4 4 3 3 2 2 1 1 X1 X2 X6 X5 DI 2 1 DO 2 1 DI 1 1 DI 1 2 DO 1 1 L L L N E N N L NSV 1 2 3 4 5 6 7 8 9 EM 230 N E L L 1 2 3 4 5 6 7 8 9 E N L L EM 230 L N L...

Страница 27: ...l the enclo sed fuse BF1 80A between battery A and battery B WARNING A short circuit may occur if the cover is removed 2 3 1 BF1 80A 12 V 18 Ah 12 V 18 Ah 12 V 18 Ah 12 V 18 Ah BF1 80A 12 V 12 Ah 12 V...

Страница 28: ...Service and Configuration Suite SCS is used for commissioning and programming Functions programmable via SCS Alarm with HS ATTENTION This function must only be used in conjunction with corresponding D...

Страница 29: ...odule 1 Trigger Line1 Actuator Module 1 Actuator Group 1 2 Trigger Module 1 Trigger Line2 Actuator Module 2 Actuator Group 1 2 Trigger Module 2 Trigger Line1 Actuator Module 3 Actuator Group 1 Trigger...

Страница 30: ...or Group 1 2 Trigger Module 2 Trigger Line2 Actuator Module 4 Actuator Group 1 2 Trigger Module 3 Trigger Line1 Actuator Module 5 Actuator Group 1 Trigger Module 3 Trigger Line2 Actuator Module 5 Actu...

Страница 31: ...the set ventilation time Mains outage CLOSED The group automatically moves in the CLOSED direction in the event of a mains outage Only the control panel groups move in the CLOSED direction in the eve...

Страница 32: ...ts IOM I O module Display of the module status Display of the status of the inputs and outputs Modules Overview of all modules used Display of the respective statuses similar to the LEDs on the respec...

Страница 33: ...using the smoke vent button as otherwise there is a risk of wind or water damage If gap ventilation is desired in bad weather the weather automation can be switched off using an optional automatic sw...

Страница 34: ...tion Closing after alarm Manual opening with smoke vent button Automatic opening with fire detector Automatic opening through external control e g central fire alarm For manual triggering using smoke...

Страница 35: ...ied out once a year by a specialist company authorised by the device manufacturer Carry out cleaning and maintenance work only when the system is de energised Replace the inspection plate maintain the...

Страница 36: ...eorg Sasse Str 28 32 22949 Ammersbek Germany Tel 4940 605 65 239 Fax 4940 605 65 254 E Mail info dh partner com www dh partner com 2016 D H Mechatronic AG Ammersbek Subject to technical modifications...

Отзывы: