background image

6/36

CPS-M1-MSE

English

99.828.70 1.2/07/22

Power packs PS-S1-24-20 and PS-S1-24-40

Functions:

• 

Output: 24 V DC, 20 A or 40 A

•  Installation on 35 mm top hat rail

• 

Low ripple

•  Reverse-voltage protected and short-circuit resistant

• 

Multiple power supply units can be combined

• 

For each power supply unit, one PSM supply module is needed

Technical data:

Type 

 

 

PS-S1-24-20 

PS-S1-24-40

Rated input voltage  

230 V AC ± 15%

Frequency 

 

45 to 65 Hz 

Nominal power 

 

530 VA / 480 W 

1040 VA / 960 W

Output voltage 

 

24 V DC ± 1%

Ripple 

 

 

< 50 mVSS

Output current 

 

20 A 

 

40 A

Short-circuit resistant 

YES

Can be connected in parallel  YES

Reverse-voltage protected 

YES

Input line connection  

max. 6 mm² star / max. 4 mm² flexible

Output line connection 

max. 6 mm² star / max. 4 mm² flexible

   

max. 16 mm² star / max. 16 mm² flexible

Dimensions WxHxD  

90x130x150 mm 

140x130x150 mm

Bistable relay module - BRM-1-COC-0006

•  Six user-programmable, isolated change-over contacts, 

for switching signals with 24 V DC or 230 V AC

•  change-over contacts as bistable version

• 

Definition of a switch-off state in the event of a mains and 

battery failure possible (failsafe function)

• 

Integrated LEDs to indicate a fault (yellow) and alarm 

(red)

•  Connection using removable spring-type terminals

• 

Conductor cross-sections max. 2.5 mm² flexible

•  Dimensions WxHxD: 26x130x125 mm

• 

Installation on a 35 mm top hat rail in combination with 

an expansion module socket

Digital I/O module - IOM-D1-1212

•  12 user-programmable digital inputs

•  12 user-programmable digital outputs

• 

The digital inputs can also be parameterised as LT inputs

• 

Integrated LEDs to indicate a fault (yellow) and alarm 

(red)

•  Connection using removable spring-type terminals

• 

Conductor cross-sections max. 1.5 mm² flexible

•  Dimensions WxHxD: 26x130x125 mm

• 

Installation on a 35 mm top hat rail in combination with 

an expansion module socket

Actuator module - AM-1-1-08-230-D4-D2

• 

Module for connecting 230 V AC actuators

• 

1 group for connecting drives with a total maximum 

current of 8 A

•  Up to 45 drives per AM 230 connectable

• 

D+H 230 V AC drives with SHEV fast mode (HS) are 

supported

• 

The cable is monitored for breaks and short circuits 

via the terminal module EM 230

•  2 user-programmable digital inputs (e.g. ventilation 

button)

• 

1 user-programmable digital output (e.g. NOT 

CLOSED signal)

• 

Can be used with 230 V AC standard drives

• 

Adjustable ventilation time and opening width for 

everyday ventilation

• 

Integrated LEDs to indicate a fault (yellow) and alarm (red)

•  Connection using removable spring-type terminals

• 

Conductor cross-sections max. 2.5 mm² flexible

 

(230 V AC) or 1.5 mm² flexible (24 V DC)

•  Dimensions WxHxD: 26x130x125 mm

• 

Installation on a 35 mm top hat rail in combination with 

an expansion module socket

AD I/O module - ADM-AD1-1212-4

•  4 user-programmable multifunctional inputs (digital or 

analog)

•  8 user-programmable digital inputs

•  12 user-programmable digital outputs

• 

4 virtual adjustable threshold switches per analog input 

from which a virtual user-configurable digital input is set 

or reset

• 

The digital inputs can also be parameterised as LT inputs

• 

Integrated LEDs to indicate a fault (yellow) and alarm 

(red)

•  Connection using removable spring-type terminals

• 

Conductor cross-sections max. 1.5 mm² flexible

•  Dimensions WxHxD: 26x130x125 mm

• 

Installation on a 35 mm top hat rail in combination with 

an expansion module socket

Содержание CPS-M1-MSE

Страница 1: ...CPS M1 MSE D H Downloads 99 828 70 1 2 07 22 en Original instructions Page 2...

Страница 2: ...e Safety information 230 V AC operating voltage Risk of injury from electric shock Only an authorised electrically skilled person is allowed to connect the power Keep children away from the controller...

Страница 3: ...arm systems VdS 2221 VDE 0100 for electrical systems DIN 18232 for SHEV systems the provisions of the local fire brigade and of the energy supply compa ny for the mains connection EN 12101 10 Energy s...

Страница 4: ...bracket optional TP C1 35 RJ12 RJ12 socket C o n t r o l m o d u l e C M B T 1 D 4 P 2 C o n t r o l m o d u l e C M B 1 D 4 P 2 M a i n s s u p p l y m o d u l e P S M 1 2 4 0 4 0 2 4 V D C a c t u...

Страница 5: ...26 Ah battery type 6 72 hours of emergency supply time Integrated protection against excessive discharge Temperature controlled charging voltage with external temperature sensor Integrated LED to indi...

Страница 6: ...ated LEDs to indicate a fault yellow and alarm red Connection using removable spring type terminals Conductor cross sections max 1 5 mm flexible Dimensions WxHxD 26x130x125 mm Installation on a 35 mm...

Страница 7: ...30 0 3 Ah Fire detector 0 005 Ah Smoke vent button 0 014 Ah 24 V DC Drives actuators for 180 sec 0 18 Ah for each 1 A nominal current Alarm devices 250 mA for 180 sec 0 045 Ah Devices and digital outp...

Страница 8: ...ght of it Each additional PSM always provides power only to the modules to the right of it This applies also to the emergency battery power Therefore the modules are to be distributed evenly across th...

Страница 9: ...upplying the drive Mot a Mot b For pole changing drives 1 additional wire for cable monitoring through which the SHEV high speed HS signal is also transmitted to the drive For ACB drives 2 additional...

Страница 10: ...PE Connection PSM RJ12 connecting cable CC TP TCSU max 2 m Battery Battery No Name Description X2 1 N Output potential without an emergency supply for ventilation functions max 500 mA X2 2 Reference...

Страница 11: ...T1 L1 L2 L3 T3 T2 T1 Q1 PE 63A T2 T3 X1 2 L1 L2 L3 PE N Q2 1 8 7 Q3 1 2 1 4 3 6 5 F1 L3 L2 L1 T1 8 7 2 1 4 3 6 5 F2 B13A 230V 24V L N PE SNT SNT PS S1 24 40 T1 4 3 2 1 PSM 1 24 40 1 1 2 2 SNT BATT SNT...

Страница 12: ...slave interface X5 2 ACN D X5 3 ACN D X6 5 n c n c X6 4 DI 1 2 Freely configurable digital input 0 to 28 V active minus or plus control panel OPEN factory setting can be pro grammed using SCS X6 3 DI...

Страница 13: ...ry Battery type Lithium cell CR1216 3 Read in parameterization again Termination The AdComNet segment must be terminated with 2 resistors 110 The resistors must in each case be connected at the end of...

Страница 14: ...2 1 2 3 PE M 3 U V W PE 1T1 1T2 1T3 1L3 1L2 1L1 13 14 21 22 HIS HIS HIO HIO PE C13A F1 1 L1 3 L2 5 L3 T1 2 T2 4 T3 6 Q2 2 3 L2 1 L1 5 L3 4 2 6 T2 T1 T3 Q2 3 4 3 2 1 4 3 2 1 BRM 1 COC0006 4 4 4 3 3 3 2...

Страница 15: ...output 2 COM X3 1 NC 3 Floating output 3 normally closed X3 2 COM 3 Floating output 3 COM X3 3 NO 3 Floating output 3 normally open X3 4 COM 3 Floating output 3 COM X4 4 COM 4 Floating output 4 COM X...

Страница 16: ...1 4 3 2 1 BRM 1 COC0006 4 4 4 3 3 3 2 2 2 1 1 1 X1 X2 X3 X6 X5 X4 COM 6 NO 6 NC 6 COM 6 COM 5 NO 5 NC 5 COM 5 COM 4 NO 4 NC 4 COM 4 4 3 2 1 NO 3 COM 3 COM 3 NC 3 COM 2 NO 2 COM 1 COM 1 COM 2 NC 2 NO 1...

Страница 17: ...eely configurable digital output 3 4 X3 2 DO 3 3 freely configurable digital output 3 3 X3 3 Reference potential do not connect to P X3 4 DO 3 2 freely configurable digital output 3 2 X3 5 DO 3 1 free...

Страница 18: ...X5 X4 5 4 3 2 1 DO 1 1 DO 1 2 DO 1 4 DO 1 3 DO 2 4 DO 2 4 DO 2 1 DO 2 3 DO 3 2 DO 3 1 DO 3 4 DO 3 3 DI 3 2 DI 3 3 DI 3 4 DI 3 1 DI 2 2 DI 2 3 DI 2 4 DI 2 1 DI 1 2 DI 1 3 DI 1 4 DI 1 1 F1 95 98 95 96 Q...

Страница 19: ...output 3 1 max 50 mA short circuit proof X4 5 DI AI 1 1 freely configurable multifunctional input 1 1 digital 0 28 V active minus or plus analog 0 10 V X4 4 DI AI 1 2 freely configurable multifunctio...

Страница 20: ...AI 1 4 DI AI 1 1 ADM DO x x X1 X2 X3 ADM DI x x 24 V DC X6 X5 ADM DI AI x x 24 V DC X4 ADM DI AI x x 0 10 V DC X4 24 V DC N in out English 99 828 70 1 2 07 22 Connection ADM either either active plus...

Страница 21: ...ACB interface of drive group 2 X3 4 ACB A 2 X4 4 SGI 1 Position transmitter for drive group 1 not yet implemented X4 3 Reference potential do not connect to P X4 2 SGI 2 Position transmitter for drive...

Страница 22: ...2 ACB B 1 Mot b 2 Mot a 2 Mot b 1 E HS 1 E HS 2 P Mot a 1 P EM 47 K 2x47kW BK BK OG Mot b ACB a HS Mot b ACB a HS Mot a Mot a Mot b ACB a HS Mot b ACB a HS Mot a Mot a EM 47 K 2x47kW BK BK OG X1 1 X1...

Страница 23: ...Mot b 1 E HS 1 E HS 2 P Mot a 1 P EM 47 K 2x47kW BK BK OG Auf Zu 4 3 2 1 4 3 2 1 AM 1 2 10 24 D6 D2 4 4 4 3 3 3 2 2 2 1 1 1 X1 X2 X3 X6 X5 X4 DI 1 1 DI 1 2 DO 1 1 DI 2 1 DI 2 2 DO 2 1 SGI 2 SGI 1 4 3...

Страница 24: ...to P X4 4 ACB Supply of the ACB interface X4 3 ACB A ACB interface of drive group X4 2 ACB B X4 1 SGI Position transmitter for drive group not yet implemented X5 4 DO 1 1 Freely configurable digital...

Страница 25: ...SES DI 1 1 DI 1 2 DO 1 1 L L N L E N L N NSV L N PE L L N PE L 230 V AC 50 Hz L N PE ION O OFF ION O OFF before vor avant Battery Service switch off the battery Batterieschalter auf OFF schalten d bra...

Страница 26: ...AC 50 Hz L N PE ION O OFF ION O OFF before vor avant Battery Service switch off the battery Batterieschalter auf OFF schalten d brancher la batterie ION O OFF L N L N PE K1 K2 K1 K2 K1 1 2 3 4 5 6 7...

Страница 27: ...K Freely configurable digital output 4 1 max 50 mA X6 5 DO 3 2 A Freely configurable digital output 3 2 max 50 mA X6 4 DO 3 3 S Freely configurable digital output 3 3 max 50 mA X6 3 Reference potenti...

Страница 28: ...7 S 6 A 1 K 2 3 5 T 8 5 R 2 3 bu rd EM L01 5 R 2 3 bu rd EM L01 2 8 3 5 T n c 4 Z 7 S 6 A 1 K OK RT 45 4 Z 7 S 6 A 1 K OK 2 8 3 5 T n c RT 45 OK RT 45 OK SD O 371 FD T 271 SD O 371 FD T 271 rd bu EM...

Страница 29: ...Z Z 7 7 S S 6 6 A A 1 1 K K OK rd bu EM L01 X1 1 X1 5 X2 1 X2 5 X3 1 X3 5 5 4 3 2 1 5 4 3 2 1 TMA 1 D4 D12 5 5 5 4 4 4 3 3 3 2 1 2 1 2 1 X1 X2 X3 X6 X5 X4 5 4 3 2 1 A S n c n c T K FE Z R FE n c Z S...

Страница 30: ...rrent of 50 mA The connection is permanently short circuit resistant and the fuse used is self resetting If the output is deactivated the output is open has a high resistance Active negative inputs ca...

Страница 31: ...be used in conjunction with corresponding D H high speed drives If D H drives without high speed or third party drives are connected activation can destroy the drive Standard configurations Controller...

Страница 32: ...ly moves in the CLOSED direction in the event of a mains outage Only the control panel groups move in the CLOSED direction in the event of a mains outage Groups in the same link belonging to another C...

Страница 33: ...puts IOM I O module Display of the module status Display of the status of the inputs and outputs Modules Overview of all modules used Display of the respective statuses similar to the LEDs on the resp...

Страница 34: ...sing the smoke vent button as otherwise there is a risk of wind or water damage If gap ventilation is desired in bad weather the weather automation can be switched off using an optional automatic swit...

Страница 35: ...ration Closing after alarm Manual opening with smoke vent button Automatic opening with fire detector Automatic opening through external control e g central fire alarm For manual triggering using smok...

Страница 36: ...stems etc must not be impaired by stored articles or structural changes Maintenance and cleaning Carried out once a year by a specialist company authorised by the device manufacturer Carry out cleanin...

Отзывы: