Designation

Connection

Description

Digital output

Output inverted

The output issues the status of the link inverted.

Functionality selection

SHEV link: Alarm / Alarm Reset / Alarm Pulse / Fault / Not Closed
Ventilation link: Not Closed / LT Open forwarding / LT Closed forwarding

Supplied with emergency power The output is also triggered in the event of a mains outage. An additional 0.072 Ah 

is to be taken into consideration in the battery capacity calculation. Furthermore, the 

current consumption of the connected peripherals is to be taken into consideration.

Functionality

SHEV link: Alarm / Alarm Pulse / Alarm Reset and RT Closed / Alarm and Alarm 

Reset with RT Closed / Fault
Ventilation link: LT Open / LT Closed / LT Stop / LT Open pulse / LT Closed pulse / 

LT Open and Closed pulse / LT Closed and Open pulse / LT Open pulse and Closed 

pulse

Digital input

Inverted

The status of the input is forwarded to the link inverted.

Active negative

The input is activated if switched to -.

Active positive

The input is activated if switched to P+ or N+.

Group

Actuator type

The group is used for triggering ACB drives or pole-changing drives. The type used 

must be selected for each group.

Alarm re-clocking

The group will be triggered every 2 minutes for 30 minutes in the event of an alarm. 

This function is a requirement of VdS 2581.

Open – running time limit

The group moves in the OPEN direction for the set time if the ventilation button is 

switched to the OPEN direction.

Open – retriggering

The group once more moves in the OPEN direction for the set time if the ventilation 

button is again switched to the OPEN direction.

For alarm Closed

The group moves in the CLOSED direction if the SHEV link to which the group is 

assigned is triggered.

For communication fault Closed

The group moves in the CLOSED direction if a communication fault occurs within a 

link to which the group is assigned.

Group fault triggers alarm

In the event of a group fault (e.g. a monitoring cable is interrupted or an addressed 

ACB drive is not available), the SHEV link to which the group is assigned is trig

-

gered.

Ventilation time active

The group automatically moves in the CLOSED direction upon expiry of the set 

ventilation time.

Mains outage CLOSED

The group automatically moves in the CLOSED direction in the event of a mains 

outage. Only the control panel groups move in the CLOSED direction in the event 

of a mains outage. Groups in the same link belonging to another CPS-M are not 

affected by this.

Storage operation OPEN

The group moves in the OPEN direction when a ventilation button of the ventilation 

link is pressed once.

Storage operation CLOSED

The group moves in the CLOSED direction when a ventilation button of the ventila

-

tion link is pressed once.

Stop-hold function

The supply cables MOT.A x and MOT.B x are short-circuited in the Stop status. A 

short circuit between these two cables can no longer be recognized as being a fault 

in this status.

Button operation OPEN

The group moves in the OPEN direction for as long as the ventilation button of the 

ventilation link is pressed.

Button operation CLOSED

The group moves in the CLOSED direction for as long as a ventilation button of the 

ventilation link is pressed.

Line

Line fault triggers alarm

In the event of a line fault (e.g. an interrupted cable), the SHEV link to which the line is 

assigned is triggered.

Smoke detector can only be 

locally reset

A smoke detector alarm cannot be reset by pressing the “SHEV CLOSED” button on 

the SHEV button panel. It is possible to reset the alarm via the touch panel.

Two-detector dependency

(Only with SD-O 371/FO 1362) Alarm will be triggered only, if at least two smoke 

detectors of one line respond. False alarm of one smoke detector will be prevent

-

ed. Two smoke detectors in one room must be always installed. If only one smoke 

detector is connected to one line, switch must be on OFF!

Isolated output

Output inverted

The output issues the status of the link inverted.

Functionality selection

SHEV link: Alarm / Alarm Reset / Alarm Pulse / Fault / Not Closed

Ventilation link: Not Closed / LT Open forwarding / LT Closed forwarding

Supplied with emergency power

(monostable, CM)

The output is also triggered in the event of a mains outage. This must be taken into 

consideration in the battery capacity calculation.

Failsafe in case of power failure

(bistable, BRM)

With this the state of the potential-free contact can be defined, which is to be taken 

in case of a failure of the mains and battery supply.

If the "None" configuration is selected, the last status is retained.

Event log

internal

All status changes of the CPS-M are written with time stamp in an event log. These 

can be read out via the SCS software.

Description of the software functions

Содержание CPS-M1-MSE

Страница 1: ...CPS M1 MSE D H Downloads 99 828 70 1 2 07 22 en Original instructions Page 2...

Страница 2: ...e Safety information 230 V AC operating voltage Risk of injury from electric shock Only an authorised electrically skilled person is allowed to connect the power Keep children away from the controller...

Страница 3: ...arm systems VdS 2221 VDE 0100 for electrical systems DIN 18232 for SHEV systems the provisions of the local fire brigade and of the energy supply compa ny for the mains connection EN 12101 10 Energy s...

Страница 4: ...bracket optional TP C1 35 RJ12 RJ12 socket C o n t r o l m o d u l e C M B T 1 D 4 P 2 C o n t r o l m o d u l e C M B 1 D 4 P 2 M a i n s s u p p l y m o d u l e P S M 1 2 4 0 4 0 2 4 V D C a c t u...

Страница 5: ...26 Ah battery type 6 72 hours of emergency supply time Integrated protection against excessive discharge Temperature controlled charging voltage with external temperature sensor Integrated LED to indi...

Страница 6: ...ated LEDs to indicate a fault yellow and alarm red Connection using removable spring type terminals Conductor cross sections max 1 5 mm flexible Dimensions WxHxD 26x130x125 mm Installation on a 35 mm...

Страница 7: ...30 0 3 Ah Fire detector 0 005 Ah Smoke vent button 0 014 Ah 24 V DC Drives actuators for 180 sec 0 18 Ah for each 1 A nominal current Alarm devices 250 mA for 180 sec 0 045 Ah Devices and digital outp...

Страница 8: ...ght of it Each additional PSM always provides power only to the modules to the right of it This applies also to the emergency battery power Therefore the modules are to be distributed evenly across th...

Страница 9: ...upplying the drive Mot a Mot b For pole changing drives 1 additional wire for cable monitoring through which the SHEV high speed HS signal is also transmitted to the drive For ACB drives 2 additional...

Страница 10: ...PE Connection PSM RJ12 connecting cable CC TP TCSU max 2 m Battery Battery No Name Description X2 1 N Output potential without an emergency supply for ventilation functions max 500 mA X2 2 Reference...

Страница 11: ...T1 L1 L2 L3 T3 T2 T1 Q1 PE 63A T2 T3 X1 2 L1 L2 L3 PE N Q2 1 8 7 Q3 1 2 1 4 3 6 5 F1 L3 L2 L1 T1 8 7 2 1 4 3 6 5 F2 B13A 230V 24V L N PE SNT SNT PS S1 24 40 T1 4 3 2 1 PSM 1 24 40 1 1 2 2 SNT BATT SNT...

Страница 12: ...slave interface X5 2 ACN D X5 3 ACN D X6 5 n c n c X6 4 DI 1 2 Freely configurable digital input 0 to 28 V active minus or plus control panel OPEN factory setting can be pro grammed using SCS X6 3 DI...

Страница 13: ...ry Battery type Lithium cell CR1216 3 Read in parameterization again Termination The AdComNet segment must be terminated with 2 resistors 110 The resistors must in each case be connected at the end of...

Страница 14: ...2 1 2 3 PE M 3 U V W PE 1T1 1T2 1T3 1L3 1L2 1L1 13 14 21 22 HIS HIS HIO HIO PE C13A F1 1 L1 3 L2 5 L3 T1 2 T2 4 T3 6 Q2 2 3 L2 1 L1 5 L3 4 2 6 T2 T1 T3 Q2 3 4 3 2 1 4 3 2 1 BRM 1 COC0006 4 4 4 3 3 3 2...

Страница 15: ...output 2 COM X3 1 NC 3 Floating output 3 normally closed X3 2 COM 3 Floating output 3 COM X3 3 NO 3 Floating output 3 normally open X3 4 COM 3 Floating output 3 COM X4 4 COM 4 Floating output 4 COM X...

Страница 16: ...1 4 3 2 1 BRM 1 COC0006 4 4 4 3 3 3 2 2 2 1 1 1 X1 X2 X3 X6 X5 X4 COM 6 NO 6 NC 6 COM 6 COM 5 NO 5 NC 5 COM 5 COM 4 NO 4 NC 4 COM 4 4 3 2 1 NO 3 COM 3 COM 3 NC 3 COM 2 NO 2 COM 1 COM 1 COM 2 NC 2 NO 1...

Страница 17: ...eely configurable digital output 3 4 X3 2 DO 3 3 freely configurable digital output 3 3 X3 3 Reference potential do not connect to P X3 4 DO 3 2 freely configurable digital output 3 2 X3 5 DO 3 1 free...

Страница 18: ...X5 X4 5 4 3 2 1 DO 1 1 DO 1 2 DO 1 4 DO 1 3 DO 2 4 DO 2 4 DO 2 1 DO 2 3 DO 3 2 DO 3 1 DO 3 4 DO 3 3 DI 3 2 DI 3 3 DI 3 4 DI 3 1 DI 2 2 DI 2 3 DI 2 4 DI 2 1 DI 1 2 DI 1 3 DI 1 4 DI 1 1 F1 95 98 95 96 Q...

Страница 19: ...output 3 1 max 50 mA short circuit proof X4 5 DI AI 1 1 freely configurable multifunctional input 1 1 digital 0 28 V active minus or plus analog 0 10 V X4 4 DI AI 1 2 freely configurable multifunctio...

Страница 20: ...AI 1 4 DI AI 1 1 ADM DO x x X1 X2 X3 ADM DI x x 24 V DC X6 X5 ADM DI AI x x 24 V DC X4 ADM DI AI x x 0 10 V DC X4 24 V DC N in out English 99 828 70 1 2 07 22 Connection ADM either either active plus...

Страница 21: ...ACB interface of drive group 2 X3 4 ACB A 2 X4 4 SGI 1 Position transmitter for drive group 1 not yet implemented X4 3 Reference potential do not connect to P X4 2 SGI 2 Position transmitter for drive...

Страница 22: ...2 ACB B 1 Mot b 2 Mot a 2 Mot b 1 E HS 1 E HS 2 P Mot a 1 P EM 47 K 2x47kW BK BK OG Mot b ACB a HS Mot b ACB a HS Mot a Mot a Mot b ACB a HS Mot b ACB a HS Mot a Mot a EM 47 K 2x47kW BK BK OG X1 1 X1...

Страница 23: ...Mot b 1 E HS 1 E HS 2 P Mot a 1 P EM 47 K 2x47kW BK BK OG Auf Zu 4 3 2 1 4 3 2 1 AM 1 2 10 24 D6 D2 4 4 4 3 3 3 2 2 2 1 1 1 X1 X2 X3 X6 X5 X4 DI 1 1 DI 1 2 DO 1 1 DI 2 1 DI 2 2 DO 2 1 SGI 2 SGI 1 4 3...

Страница 24: ...to P X4 4 ACB Supply of the ACB interface X4 3 ACB A ACB interface of drive group X4 2 ACB B X4 1 SGI Position transmitter for drive group not yet implemented X5 4 DO 1 1 Freely configurable digital...

Страница 25: ...SES DI 1 1 DI 1 2 DO 1 1 L L N L E N L N NSV L N PE L L N PE L 230 V AC 50 Hz L N PE ION O OFF ION O OFF before vor avant Battery Service switch off the battery Batterieschalter auf OFF schalten d bra...

Страница 26: ...AC 50 Hz L N PE ION O OFF ION O OFF before vor avant Battery Service switch off the battery Batterieschalter auf OFF schalten d brancher la batterie ION O OFF L N L N PE K1 K2 K1 K2 K1 1 2 3 4 5 6 7...

Страница 27: ...K Freely configurable digital output 4 1 max 50 mA X6 5 DO 3 2 A Freely configurable digital output 3 2 max 50 mA X6 4 DO 3 3 S Freely configurable digital output 3 3 max 50 mA X6 3 Reference potenti...

Страница 28: ...7 S 6 A 1 K 2 3 5 T 8 5 R 2 3 bu rd EM L01 5 R 2 3 bu rd EM L01 2 8 3 5 T n c 4 Z 7 S 6 A 1 K OK RT 45 4 Z 7 S 6 A 1 K OK 2 8 3 5 T n c RT 45 OK RT 45 OK SD O 371 FD T 271 SD O 371 FD T 271 rd bu EM...

Страница 29: ...Z Z 7 7 S S 6 6 A A 1 1 K K OK rd bu EM L01 X1 1 X1 5 X2 1 X2 5 X3 1 X3 5 5 4 3 2 1 5 4 3 2 1 TMA 1 D4 D12 5 5 5 4 4 4 3 3 3 2 1 2 1 2 1 X1 X2 X3 X6 X5 X4 5 4 3 2 1 A S n c n c T K FE Z R FE n c Z S...

Страница 30: ...rrent of 50 mA The connection is permanently short circuit resistant and the fuse used is self resetting If the output is deactivated the output is open has a high resistance Active negative inputs ca...

Страница 31: ...be used in conjunction with corresponding D H high speed drives If D H drives without high speed or third party drives are connected activation can destroy the drive Standard configurations Controller...

Страница 32: ...ly moves in the CLOSED direction in the event of a mains outage Only the control panel groups move in the CLOSED direction in the event of a mains outage Groups in the same link belonging to another C...

Страница 33: ...puts IOM I O module Display of the module status Display of the status of the inputs and outputs Modules Overview of all modules used Display of the respective statuses similar to the LEDs on the resp...

Страница 34: ...sing the smoke vent button as otherwise there is a risk of wind or water damage If gap ventilation is desired in bad weather the weather automation can be switched off using an optional automatic swit...

Страница 35: ...ration Closing after alarm Manual opening with smoke vent button Automatic opening with fire detector Automatic opening through external control e g central fire alarm For manual triggering using smok...

Страница 36: ...stems etc must not be impaired by stored articles or structural changes Maintenance and cleaning Carried out once a year by a specialist company authorised by the device manufacturer Carry out cleanin...