CPS-M1-MSE

English

99.828.70 1.2/07/22

Designation

Description

-

Reference potential / negative:

 used as the reference potential for external peripherals (e.g. SHEV operation panel or 

LT).

May not be connected to P-.

The reference potentials of more than one power supply module may not be connected together.

ACB.A x / ACB.B x 

MOT.a x / MOT.b x

Group (ACB):

 used for the connection of bus-capable drives.

ACB.A x and ACB.B x are necessary for communication with the drives.

MOT.a x and MOT.b x are necessary for supplying the connected drives.

The maximum output current of the supply is 10 A.

The supply is permanently short-circuit resistant and the fuse used is self-resetting.

ACN D+ / ACN D-

Shield

AdComNet connection:

 used for interconnecting more than one CPS-M1 and for interconnecting with ACN-CM501, 

ACN-IO501, ACN-BI501-USB and ACN-GW501-MRTU.

If this connection is not used, it must nevertheless be terminated with a resistor (110 Ohm).

BATT+ / BATT-

Battery connection:

 may only be used for connecting the secondary power supply (battery).

COM x / NC x / NO x

(monostable, CRM

Isolated output:

 used for the triggering of external systems.

The maximum contact current is 1 A.

The minimum contact current to ensure permanent safe operation is 10 mA.

The maximum contact voltage is 35 V DC.

The contact is not suitable for switching 230 V AC.

The output can be supplied with emergency power. This is to be taken into consideration in the battery capacity calcula

-

tion.

COM x / NC x / NO x

(bistable, BRM)

Isolated output:

 used for the triggering of external systems.

The maximum contact current is 3 A.

The minimum contact load to ensure permanent safe operation is 5 V / 10 mA.

The maximum contact voltage is 30 V DC or 265 V AC.

DI x.x

Digital input:

 used for the evaluation of switch signals.

The input voltage range is 0 V DC to 28 V DC.

The pull-up resistor for the evaluation of an active negative signal is integrated.

The pull-down resistor for the detection of an active positive signal is integrated.

The switching contact is briefly (< 100 ms) loaded with 16 mA.

The input DI 1.1 of the controller module cannot currently be used.

DO x.x

Digital output:

 used for the triggering of displays or relays.

The output voltage range of an activated output is 17 V DC to 25 V DC.

The output voltage range applies for a maximum output current of 50 mA.

The connection is permanently short-circuit resistant and the fuse used is self-resetting.

If the output is deactivated, the output is open / has a high resistance.

Active negative inputs cannot be switched using the output.

The output can be supplied with emergency power. This is to be taken into consideration in the battery capacity calcula

-

tion.

FE

Functional earth:

 

can be used as the cable shielding connection when connecting a smoke detector line

.

May only be used as a cable shielding connection. 

LINE / RT x

Line connection:

 used for connecting a smoke detector line or an SHEV operation panel line. Furthermore, external 

systems (e.g. fire detectors) can be connected.

LINE / RM x

A maximum of 30 smoke detectors or 10 SHEV operation panels can be connected.

The connection is permanently short-circuit resistant and the fuse used is self-resetting.

Cable monitoring is performed via the EM-L01.

MOT.A x / MOT.B x

E/HS

Group (polarity change):

 used for the connection of conventional pole-changing drives.

MOT.A x and MOT.B x are necessary for the supply and for controlling the direction.

The maximum output current of the supply is 10 A.

The supply is permanently short-circuit resistant and the fuse used is self-resetting.

E/HS is used for cable monitoring and for triggering the high-speed function.

n.c.

The terminal is not connected.

N+

Operating voltage not supplied with emergency power:

 used for the supply of external peripherals.

The output voltage range is 22 V DC to 24 V DC.

The maximum output current is 440 mA.

P-

Group reference potential / group negative:

 used as the reference potential for external drives (e.g. spring return 

actuators).

May not be connected to –.

The group reference potentials of more than one power supply module may not be connected together.

+

Operating voltage supplied with emergency power:

 used for the supply of external peripherals.

The current consumption of the connected peripherals must be taken into consideration in the battery capacity calcula

-

tion.

The output voltage range is 19 V DC to 27 V DC.

The maximum output current is 440 mA.

SGI x

This function has not yet been implemented.

SNT+ / SNT-

Mains power connection:

 may only be used for connecting the primary power supply (power pack).

TCSU1

Temperature sensor connection:

 may only be used for connecting the TCSU1-RJ12.

The maximum cable length to ensure permanent safe operation is 2 m.

TP-C1

Touch panel connection:

 may only be used for connecting the TP-C1-35-RJ12.

Description of the inputs and outputs

Содержание CPS-M1-MSE

Страница 1: ...CPS M1 MSE D H Downloads 99 828 70 1 2 07 22 en Original instructions Page 2...

Страница 2: ...e Safety information 230 V AC operating voltage Risk of injury from electric shock Only an authorised electrically skilled person is allowed to connect the power Keep children away from the controller...

Страница 3: ...arm systems VdS 2221 VDE 0100 for electrical systems DIN 18232 for SHEV systems the provisions of the local fire brigade and of the energy supply compa ny for the mains connection EN 12101 10 Energy s...

Страница 4: ...bracket optional TP C1 35 RJ12 RJ12 socket C o n t r o l m o d u l e C M B T 1 D 4 P 2 C o n t r o l m o d u l e C M B 1 D 4 P 2 M a i n s s u p p l y m o d u l e P S M 1 2 4 0 4 0 2 4 V D C a c t u...

Страница 5: ...26 Ah battery type 6 72 hours of emergency supply time Integrated protection against excessive discharge Temperature controlled charging voltage with external temperature sensor Integrated LED to indi...

Страница 6: ...ated LEDs to indicate a fault yellow and alarm red Connection using removable spring type terminals Conductor cross sections max 1 5 mm flexible Dimensions WxHxD 26x130x125 mm Installation on a 35 mm...

Страница 7: ...30 0 3 Ah Fire detector 0 005 Ah Smoke vent button 0 014 Ah 24 V DC Drives actuators for 180 sec 0 18 Ah for each 1 A nominal current Alarm devices 250 mA for 180 sec 0 045 Ah Devices and digital outp...

Страница 8: ...ght of it Each additional PSM always provides power only to the modules to the right of it This applies also to the emergency battery power Therefore the modules are to be distributed evenly across th...

Страница 9: ...upplying the drive Mot a Mot b For pole changing drives 1 additional wire for cable monitoring through which the SHEV high speed HS signal is also transmitted to the drive For ACB drives 2 additional...

Страница 10: ...PE Connection PSM RJ12 connecting cable CC TP TCSU max 2 m Battery Battery No Name Description X2 1 N Output potential without an emergency supply for ventilation functions max 500 mA X2 2 Reference...

Страница 11: ...T1 L1 L2 L3 T3 T2 T1 Q1 PE 63A T2 T3 X1 2 L1 L2 L3 PE N Q2 1 8 7 Q3 1 2 1 4 3 6 5 F1 L3 L2 L1 T1 8 7 2 1 4 3 6 5 F2 B13A 230V 24V L N PE SNT SNT PS S1 24 40 T1 4 3 2 1 PSM 1 24 40 1 1 2 2 SNT BATT SNT...

Страница 12: ...slave interface X5 2 ACN D X5 3 ACN D X6 5 n c n c X6 4 DI 1 2 Freely configurable digital input 0 to 28 V active minus or plus control panel OPEN factory setting can be pro grammed using SCS X6 3 DI...

Страница 13: ...ry Battery type Lithium cell CR1216 3 Read in parameterization again Termination The AdComNet segment must be terminated with 2 resistors 110 The resistors must in each case be connected at the end of...

Страница 14: ...2 1 2 3 PE M 3 U V W PE 1T1 1T2 1T3 1L3 1L2 1L1 13 14 21 22 HIS HIS HIO HIO PE C13A F1 1 L1 3 L2 5 L3 T1 2 T2 4 T3 6 Q2 2 3 L2 1 L1 5 L3 4 2 6 T2 T1 T3 Q2 3 4 3 2 1 4 3 2 1 BRM 1 COC0006 4 4 4 3 3 3 2...

Страница 15: ...output 2 COM X3 1 NC 3 Floating output 3 normally closed X3 2 COM 3 Floating output 3 COM X3 3 NO 3 Floating output 3 normally open X3 4 COM 3 Floating output 3 COM X4 4 COM 4 Floating output 4 COM X...

Страница 16: ...1 4 3 2 1 BRM 1 COC0006 4 4 4 3 3 3 2 2 2 1 1 1 X1 X2 X3 X6 X5 X4 COM 6 NO 6 NC 6 COM 6 COM 5 NO 5 NC 5 COM 5 COM 4 NO 4 NC 4 COM 4 4 3 2 1 NO 3 COM 3 COM 3 NC 3 COM 2 NO 2 COM 1 COM 1 COM 2 NC 2 NO 1...

Страница 17: ...eely configurable digital output 3 4 X3 2 DO 3 3 freely configurable digital output 3 3 X3 3 Reference potential do not connect to P X3 4 DO 3 2 freely configurable digital output 3 2 X3 5 DO 3 1 free...

Страница 18: ...X5 X4 5 4 3 2 1 DO 1 1 DO 1 2 DO 1 4 DO 1 3 DO 2 4 DO 2 4 DO 2 1 DO 2 3 DO 3 2 DO 3 1 DO 3 4 DO 3 3 DI 3 2 DI 3 3 DI 3 4 DI 3 1 DI 2 2 DI 2 3 DI 2 4 DI 2 1 DI 1 2 DI 1 3 DI 1 4 DI 1 1 F1 95 98 95 96 Q...

Страница 19: ...output 3 1 max 50 mA short circuit proof X4 5 DI AI 1 1 freely configurable multifunctional input 1 1 digital 0 28 V active minus or plus analog 0 10 V X4 4 DI AI 1 2 freely configurable multifunctio...

Страница 20: ...AI 1 4 DI AI 1 1 ADM DO x x X1 X2 X3 ADM DI x x 24 V DC X6 X5 ADM DI AI x x 24 V DC X4 ADM DI AI x x 0 10 V DC X4 24 V DC N in out English 99 828 70 1 2 07 22 Connection ADM either either active plus...

Страница 21: ...ACB interface of drive group 2 X3 4 ACB A 2 X4 4 SGI 1 Position transmitter for drive group 1 not yet implemented X4 3 Reference potential do not connect to P X4 2 SGI 2 Position transmitter for drive...

Страница 22: ...2 ACB B 1 Mot b 2 Mot a 2 Mot b 1 E HS 1 E HS 2 P Mot a 1 P EM 47 K 2x47kW BK BK OG Mot b ACB a HS Mot b ACB a HS Mot a Mot a Mot b ACB a HS Mot b ACB a HS Mot a Mot a EM 47 K 2x47kW BK BK OG X1 1 X1...

Страница 23: ...Mot b 1 E HS 1 E HS 2 P Mot a 1 P EM 47 K 2x47kW BK BK OG Auf Zu 4 3 2 1 4 3 2 1 AM 1 2 10 24 D6 D2 4 4 4 3 3 3 2 2 2 1 1 1 X1 X2 X3 X6 X5 X4 DI 1 1 DI 1 2 DO 1 1 DI 2 1 DI 2 2 DO 2 1 SGI 2 SGI 1 4 3...

Страница 24: ...to P X4 4 ACB Supply of the ACB interface X4 3 ACB A ACB interface of drive group X4 2 ACB B X4 1 SGI Position transmitter for drive group not yet implemented X5 4 DO 1 1 Freely configurable digital...

Страница 25: ...SES DI 1 1 DI 1 2 DO 1 1 L L N L E N L N NSV L N PE L L N PE L 230 V AC 50 Hz L N PE ION O OFF ION O OFF before vor avant Battery Service switch off the battery Batterieschalter auf OFF schalten d bra...

Страница 26: ...AC 50 Hz L N PE ION O OFF ION O OFF before vor avant Battery Service switch off the battery Batterieschalter auf OFF schalten d brancher la batterie ION O OFF L N L N PE K1 K2 K1 K2 K1 1 2 3 4 5 6 7...

Страница 27: ...K Freely configurable digital output 4 1 max 50 mA X6 5 DO 3 2 A Freely configurable digital output 3 2 max 50 mA X6 4 DO 3 3 S Freely configurable digital output 3 3 max 50 mA X6 3 Reference potenti...

Страница 28: ...7 S 6 A 1 K 2 3 5 T 8 5 R 2 3 bu rd EM L01 5 R 2 3 bu rd EM L01 2 8 3 5 T n c 4 Z 7 S 6 A 1 K OK RT 45 4 Z 7 S 6 A 1 K OK 2 8 3 5 T n c RT 45 OK RT 45 OK SD O 371 FD T 271 SD O 371 FD T 271 rd bu EM...

Страница 29: ...Z Z 7 7 S S 6 6 A A 1 1 K K OK rd bu EM L01 X1 1 X1 5 X2 1 X2 5 X3 1 X3 5 5 4 3 2 1 5 4 3 2 1 TMA 1 D4 D12 5 5 5 4 4 4 3 3 3 2 1 2 1 2 1 X1 X2 X3 X6 X5 X4 5 4 3 2 1 A S n c n c T K FE Z R FE n c Z S...

Страница 30: ...rrent of 50 mA The connection is permanently short circuit resistant and the fuse used is self resetting If the output is deactivated the output is open has a high resistance Active negative inputs ca...

Страница 31: ...be used in conjunction with corresponding D H high speed drives If D H drives without high speed or third party drives are connected activation can destroy the drive Standard configurations Controller...

Страница 32: ...ly moves in the CLOSED direction in the event of a mains outage Only the control panel groups move in the CLOSED direction in the event of a mains outage Groups in the same link belonging to another C...

Страница 33: ...puts IOM I O module Display of the module status Display of the status of the inputs and outputs Modules Overview of all modules used Display of the respective statuses similar to the LEDs on the resp...

Страница 34: ...sing the smoke vent button as otherwise there is a risk of wind or water damage If gap ventilation is desired in bad weather the weather automation can be switched off using an optional automatic swit...

Страница 35: ...ration Closing after alarm Manual opening with smoke vent button Automatic opening with fire detector Automatic opening through external control e g central fire alarm For manual triggering using smok...

Страница 36: ...stems etc must not be impaired by stored articles or structural changes Maintenance and cleaning Carried out once a year by a specialist company authorised by the device manufacturer Carry out cleanin...

Отзывы: