1-8

AspectFT-Matrix MAX Area Controller Installation Guide (1/05/2015)

1.4.2 EIA-485 N

ETWORK

The EIA-485 network ports are used to accommodate serial network protocols that utilize two-wire, 
shielded-twisted pair cabling - such as BACnet MS/TP, American Auto-Matrix PUP, and Modbus RTU. 
Terminals for EIA-485 network connections are located on the left side of the controller board and are 
labeled 

J2

 and 

J3

. Each terminal has a connection for Network Positive (

N+

), Network Negative (

N-

), and 

Signal Ground Reference Wire (

SG,

 commonly used for serial networks that utilize a reference wire for 

electrical stability).

The Matrix Area Controller should be installed at an electrical end of the EIA-485 network. Avoid network 
topologies where the network is “t-tapped” or “starred”.

1.4.2.1 C

ONNECTING

 EIA-485 N

ETWORKS

Connect the serial network to the determined EIA-485 port. Be sure to maintain network polarity at all 
times. Failure to do so can result in loss of network communications. For protection against ground loops 
or noise, connect the drain wire of the 485 network wire to a reliable earth ground.

N+

N-

Figure 1-8 MS/TP Network Connection

1.4.2.2 N

ETWORK

 T

ERMINATION

 

AND

 B

IASING

Adjacent to each EIA-485 port is a two-position switch block, which applies termination and biasing to your 
485 network.   To enable either termination (

TERM

) or biasing (

BIAS

), configure the respective switch 

towards the ON (Up) position.

When applying termination, be certain that it is applied at both ends of your EIA-485 network at the two 
end devices. In termination applications, biasing should also be enabled to ensure proper idle state 
voltage.

TERM    BIAS

SW2

Figure 1-9 Termination and Biasing Switches and LED Indicators

Содержание American Auto-Matrix Aspect Matrix MAX

Страница 1: ...Matrix MAX Hardware Installation Guide...

Страница 2: ...ctors Drill for mounting the product onto a wall Wire strippers for terminating EIA 485 connections 1 1 2 SAFETY PRECAUTIONS NOTE All equipment must be installed in accordance with NEC and local codes...

Страница 3: ...ject Do not handle the printed circuit board PCB without proper protection against static discharge Users should handle PCB components while wearing a ground bracelet or strap connected to Earth groun...

Страница 4: ...cation that allows clearance for ease of wiring and service Use the two keyhole style screw holes located on the back of the enclosure for assistance with mounting The product is capable of being moun...

Страница 5: ...1 4 AspectFT Matrix MAX Area Controller Installation Guide 1 05 2015 Figure 1 2 AspectFT Matrix MAX enclosure Figure 1 3 Enclosure cover removal...

Страница 6: ...out of the product The device includes connection ports for Main Power EIA 485 network connectivity and Ethernet connectivity Depending on the model of Matrix MAX Area Controller you have purchased yo...

Страница 7: ...nds using 18AWG cable for power wiring 24VAC Output J1 PWR PWR Figure 1 5 Connecting Power to Matrix MAX Area Controller WARNING Do not share the power source for AspectFT Matrix MAX MAX Area Controll...

Страница 8: ...sers communicate with the device for product setup as well as for building automation routines and applications The Ethernet network interface is located on the single board computer card The on board...

Страница 9: ...apped or starred 1 4 2 1 CONNECTING EIA 485 NETWORKS Connect the serial network to the determined EIA 485 port Be sure to maintain network polarity at all times Failure to do so can result in loss of...

Страница 10: ...will flash upon the event a parity error occurs on the network A parity error is caused by a mismatch between the calculated checksum and value received with the packet The most common reason for a pa...

Страница 11: ...ns apply 1 5 2 ETHERNET CONNECTION Termination Count 1 connection Connection Type RJ 45 female Speed 10 100Mb auto sensing 1 5 3 PRODUCT SETUP AND CONFIGURATION Software AspectStudio with USB Copy Pro...

Страница 12: ...ce marks or logos contained herein are the property of their respective owners and are only used to describe the product s being listed in this document Every effort has been made to properly capitali...

Отзывы: