Replacement of batteries located
in an
OPERATOR ACCESS AREA
1. When replacing batteries, replace with the
same number of the following battery:
CyberPower / RB1290 for the
CP850PFCLCD / CP100PFCLCD.
2.
CAUTION!
Risk of Energy Hazard, 12 V,
maximum 9 Ampere-hour battery. Before
replacing batteries, remove conductive
jewelry such as chains, wrist watches, and
rings. High energy conducted through
these materials could cause severe burns.
3.
CAUTION!
Do not dispose of batteries in a
fire. The batteries may explode.
4.
CAUTION!
Do not open or mutilate
batteries. Released material is harmful to
the skin and eyes. It may be toxic.
CAUTION - RISK OF EXPLOSION IF BATTERY
IS REPLACED BY AN INCORRECT TYPE.
DISPOSE OF USED BATTERIES ACCORDING
TO LOCAL REGULATIONS
REPLACING THE BATTERY
BATTERY REPLACEMENT PROCEDUR
E: CP850PFCLCD/CP1000PFCLCD
1.
Turn off and unplug all connected equipment.
2. Turn the UPS off and unplug it from the AC power source.
3. Turn the UPS on its side.
4. Remove the retaining screw located on the bottom of the UPS.
5. Slide the battery compartment cover completely off of the unit.
6. Remove the batteries from the compartment.
7. Disconnect the battery wires from the batteries.
8. Install the replacement batteries by connecting the red wire (+) and black wire (-) to the
same color connectors from the battery pack.
9. Put the batteries back into the compartment.
10. Slide back the battery compartment cover and tighten the retaining screw.
11. Recharge the UPS for 8-16 hours to fully charge the battery.
REMINDER:
Batteries are considered
HAZARDOUS WASTE
and must be disposed of properly. Most retailers that sell lead-acid
batteries collect used batteries for recycling, as required by local regulations.