background image

 

1.

 

 Short Description 

 

Uninterruptib

 

le Power Supply Units for Buffering 

Long-Term Power Interruptions

 

 

Saves space thanks to the compact, uniform design

• Integrated diode saves money through isolation of 

loads

• Maximum system availability through optimum 

battery management and reliable signaling

• Minimum installation time due to ready-to-use 

plug-in bridges and integrated timeout
QUINT-DC-UPS uninterruptible power supply units 

with long-life lead-acid batteries provide long buffer 
times at high currents. Even in the event of a longer 
supply voltage failure, the units ensure that all 
connected devices continue to operate without 
interruption. 

The devices have a narrow and uniform design, 

which makes them ideal for use on the DIN rail where 
space is limited. In addition, short wiring paths ensure 
order and clarity in the control cabinet. 

The high level of availability and the particularly long 

service life of the battery modules are achieved 
through professional battery management. An 
automatic presence check (every minute), automatic 
quality test (once a week), temperature-determined 
charging, and electronic overcurrent protection ensure 
the battery modules are ready to operate at all times. 
Power is therefore available in the event of an error and 
the service life of the battery module is maximized.

The actual state must be determined quickly so that 

the right decision can be made in an emergency. 
Optimum signaling is thus required for maximum 
system availability. Three 

fl

oating PDT contacts and 

three LEDs are provided for function monitoring, which 
indicate all the operating states clearly.

So that relay signaling is more reliable and more 

durable than before, an additional positive supply 
output has been provided. The contact, which is 
current-limited and resistant to continued short circuits, 
is located next to the relay connections and enables 
easy bridging. In the event of wiring errors, the short-
circuit protection prevents any welding of the relay 
contacts. This ensures that the user can rely on an OK 
signal. Even in the event of connection errors, currents 
remain below 100 mA, which prevents damage to the 
relay contacts.

A system is switched off after a speci

fi

c time that can 

be set on the device or by an external signal. No 
additional installation is required for shutdown. In 
addition, ready-to-use plug-in bridges minimize the 
installation time.

The connected devices can be divided into buffered 

and unbuffered loads using the isolated input. This 
extends the buffer time, which depends on the output 
current. If only critical devices are protected using 
fuses, smaller battery modules can be used that save 
money and space in the control cabinet. In addition, the 
isolated input protects the connected devices against 
errors in the internal network.

 

Uninterruptib

 

le Power Supply Unit  

for Universal Use QUINT-DC-UPS/24DC/40

 

Headquar

 

ters: © Phoenix Contact GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany

Phone +49 - 52 35 - 30 0 • Fax +49 - 52 35 - 34 12 00 • www.phoenixcontact.com

Local Contact: www.phoenixcontact.com/salesnetwork

Содержание QUINT-DC-UPS/24DC/40

Страница 1: ...g is thus required for maximum system availability Three floating PDT contacts and three LEDs are provided for function monitoring which indicate all the operating states clearly So that relay signali...

Страница 2: ...harge current Battery presence check time interval Battery quality test time interval Memory Medium Nominal voltage Nominal capacity Charge current QUINT DC UPS 24DC 40 DC UPS Module U u F Type Order...

Страница 3: ...cations Signaling Power In OK Alarm Battery Mode Battery Charge Approvals Standards Electrical equipment of machines Electrical safety of IT equipment Industrial control equipment Shipbuilding Electro...

Страница 4: ...ully The QUINT DC UPS is a built in device Installation and startup must only be carried out by qualified personnel The relevant country specific regulations e g VDE DIN must also be observed Before s...

Страница 5: ...4 DC OK 24V 0 2A 11 21 12 13 2 11 Alarm Bat M ode Bat C harg e QUIN T D C U PS 24DC 20 Ord er No 28 66 23 9 Input Opera tional Voltage Output 24VDC 22A 22 5 3 0VDC 24VDC 20A APPROVALS Read in sta llat...

Страница 6: ...onnected For reliable and safe to touch connections Strip 10 mm 0 39 in from the input and output side connector ends and 7 mm 0 28 in from the signal connector ends To maintain UL approvals use coppe...

Страница 7: ...24DC type battery modules The following battery modules are recommended QUINT BAT 24DC 3 4AH Order No 2866349 QUINT BAT 24DC 7 2AH Order No 2866352 QUINT BAT 24DC 12AH Order No 2866365 When using QUIN...

Страница 8: ...ce remains off until remote shutdown is deactivated Connected loads are supplied as long as the supply voltage is present 6 Setting Options on the Device Fig 13 6 1 Buffer Time Setting Buffer mode can...

Страница 9: ...idling proof 7 2 Signaling Three floating PDT contacts and three indicators are provided for function monitoring xx xx Contact closed 1x Alarm 2x Battery Mode 3x Battery Charge x1 group contact x2 N C...

Отзывы: