Uninterruptible Power Supply Unit for Universal Use – QUINT-DC-UPS/24DC/40
5.9. Remote Shutdown
("Remote", Fig. 12)
The device has a UPS remote shutdown function for
speci
fi
c shutdown.
Remote shutdown must be deactivated for the device
to switch to buffer mode in the event of a supply voltage
failure.
Remote Shutdown Off
• The "Remote shutdown R1" and "Remote
shutdown R2" terminal points are short circuited
(e.g., with a plug-in bridge) OR
The "Remote shutdown R2" terminal point is
supplied with a 24 V DC voltage
• The QUINT-DC-UPS switches to buffer mode in the
event of a supply voltage failure
Remote Shutdown On
• The "Remote shutdown R1" and "Remote
shutdown R2" terminal points are not connected
• All LEDs are off
• The QUINT-DC-UPS does not switch to buffer mode
in the event of a supply voltage failure, instead the
device is shut down. When the supply voltage is
reapplied, the battery module is charged and the
device remains off until remote shutdown is
deactivated.
• Connected loads are supplied as long as the supply
voltage is present
6. Setting Options on the Device
(Fig. 13)
6.1. Buffer Time Setting
Buffer mode can be exited after a prede
fi
ned time
has elapsed or by external
shutdown (see 6.9).
If the device is to be shut down after a speci
fi
c time
has elapsed, the time can be set via the
selector switch
§
on the front of the device.
When the supply voltage is reapplied, the device
can switch to buffer mode again.
6.2. Battery Module Setting
Before startup, the capacity of the battery module
used must be set on the device via the selector switch
$
. When replacing the battery, the selector switch
must be set to "Service" (see also 6.7).
V 40
A
Output
+
–
Bat.-Mode
Bat.-Charge
Alar
m
Power In OK
Bat.-Mode
Bat.-Charge
Batter
y
rm
Power In
OK
+ –
10
15
5
3
2
1
0,5
20
30
∞
t
max
[min]
Service
≤
3,4
≥
12
7,2
Bat.-Select
[Ah]
$
$
$
$
§
§
§
§
Figure 13
3 14
DC
OK
+ +
13 14
DC
OK
+ +
13 14
DC
OK
+ +
V 0,2A
11
21
12 13 2
11
Alarm
Bat
.-Mode
Cha
rge
QUI
Ord
e
Inp
u
Op
e
Out
p
AP
P
U
Alarm
Bat.-Mode
Bat.-Cha
rge
3 1
4 DC
OK
+ + –
Alarm
31 R1 R2
2 23 32 33
21
Bat.-
Mode
31
Bat.-
Charge
R1 R2
Remote
OFF
ON
8
8
8
8
Figure 12