4.8 Fault Diagnosis
Spark Failure
The gap between the pilot electrode and the pilot should be 3.5 – 4.5mm and normally
adjustment is not necessary (the electrode is very brittle). The spark should jump across
the gap between the electrode and the gas outlet on the pilot head. If the ignitor fails, a
lighted taper can be inserted into the pilot area to check that gas is reaching the pilot.