background image

I.B. 48008

Page 3

Effective 11/97

the field has not yet been energized by the DC power
supply, or the converse, the motor coasting to a stop with
the field deenergized.

The controller protective functions include:

1.

Locked-rotor protection

2.

Incomplete-sequence protection

3.

Failure-to-synchronize protection

4.

Loss-of-synchronization (pull-out) protection

5.

Open-phase protection

6.

DC loss (field loss) protection

Automatic power factor regulation is not included with the
standard unit, but is available as an option.

Functions

Mark V controllers for synchronous motors consist of the
basic components shown in Figure 4.  Their functions are
as follows:

The line contactor (M) operates to connect the motor to
the AC line.  Additional contactors are required in reduced-
voltage starters to short out the reactor or to connect and
disconnect the autotransformer in the circuit.

The overload protection relay (e.g., IQ1000-II) protects the
motor from damage by overcurrent conditions, single
phasing, or other abnormal conditions such as phase
reversal or ground fault.  It operates to trip the line
contactor M.

The starting and field-discharge resistor (S/D RES) is
used to improve the motor starting torque and to limit the
induced field voltage during starting or when the field
excitation is removed.  The resistor current and ohmic
values are determined by the motor designer.  The motor
controller is designed to operate motors with less than
1,500 volts rms in the field during starting.  The current
flowing to the resistor is controlled by diode D1 and SCR
Q4 (Fig. 4).  Voltage feedback (VR on the synchronizing
control board) provides information about the induced field
voltage, frequency, and phase angle.

Fig. 2  Mark V Field Power Supply Panel

Fig. 3  Synchronizing Control Board

Содержание EATON Ampgard Mark V

Страница 1: ...squirrel cage induction bars located in the faces TABLE I REFERENCE MATERIAL Contactor Ampere Instruction Type Rating I L or I B Type SJA 360A I B 48002 Type SJA 720A I B 48005 Type SJD 360A I B 48004...

Страница 2: ...oltage starter includes all of the components of a full voltage starter plus one or two additional contactors and related control components A synchronous motor controller is either a full voltage sta...

Страница 3: ...short out the reactor or to connect and disconnect the autotransformer in the circuit The overload protection relay e g IQ1000 II protects the motor from damage by overcurrent conditions single phasi...

Страница 4: ...erminals KA2 KB2 or KC2 RLY1 will drop out to open the control circuit RLY1 and RLY3 may pulse open and closed during certain types of faults causing the interposing relay MX to drop out insuring that...

Страница 5: ...ower supply cabinet The range of local voltage control adjustment is coordinated with the minimum output voltage adjustment P1 to produce the desired minimum and maximum output voltages Fig 4 Mark V C...

Страница 6: ...terminal located with the TO terminal near T4 Remove jumpers from the two 120V terminals located near T4 See Figure 5 and Table II ADJUSTINGTHE MOTOR FIELDVOLTAGE To adjust the motor field voltage use...

Страница 7: ...N When voltage is applied to terminals 115 and IN the Mark V will go into the synchronizing mode SYSTEM PROTECTION This controller includes circuits that provide a means of shutting down in the event...

Страница 8: ...ed on motor start up while ensuring that proper sequential synchronizing occurs and that motors will operate continu ously in synchronism The protection system must detect and operate for a condition...

Страница 9: ...ith motor voltage HP and FLA Check the torque tightness of all connections Study all applicable instruction material and diagrams Have available the schematic and connection diagrams fur nished with t...

Страница 10: ...use 2 With the motor field disconnected verify that the resistance between F1 and F2 on the terminal strip is 250 ohms 15 ohms 3 Measure the resistance of the starting and discharge resistor S D RES o...

Страница 11: ...th power available on the Ampgard bus system close the controller isolating switch and close the line contactor M 7 Plan to keep the motor field energized with the motor still for not more than two mi...

Страница 12: ...on 4 External Inhibit 7 Field Excitation 2 Frequency Option 6 Full Operation 11 Fuse and Contactor Check 9 Incomplete Sequence 6 Mark V Controller 3 Motor Controller 2 Motor Field Excitation 2 Page Op...

Отзывы: