background image

I.B. 48008

Page 10

Effective 11/97

Synchronous Motor Check

Each Mark V synchronous motor controller has a terminal
strip consisting of seven studs on standoff insulators
mounted on a subpanel and labeled as shown in Figure 8.
Disconnect leads from these stabs as necessary to
conduct the following tests:

1.

With the motor slip rings clean and brushes down (in
operating position) measure and record the cold motor
field resistance between F1 and F2.  Calculate the
field resistance by dividing the nameplate field voltage
by the nameplate field current.  The measured ohms
should be between 70 and 80 percent of calculated
ohms.  If the measured resistance at the terminal strip
(F1 and F2) is more than 80 percent of calculated
resistance measure the field resistance at the motor
slip rings.  This latter reading should be less than the
previous reading.  If resistance readings are still high
determine cause.

2.

With the motor field disconnected verify that the
resistance between F1 and F2 on the terminal strip is
250 ohms, + 15 ohms.

3.

Measure the resistance of the starting and discharge
resistor (S/D RES on schematic diagram, Figure 4) at
terminals R1 to R3 on the terminal strip (Figure 8).
The measured value should be as shown on the
diagram accompanying the order.  Measure the
resistance between terminals VR and KA1 on the
synchronous control board (CB).  The reading should
be 50 ohms + R1-R3 value.

4.

Reconnect all leads.

Controller Check

1.

Verify that the jumpers required for the installation are
properly installed.  See Table II.

2.

Read the ampere ratings of the three fuses supplied
on the secondary side of the transformers providing
power to the solid-state controller.

These fuse ratings are equal to the ampere rating of
the field power supply.

3.

Verify the dial setting of the FLA relay located adja-
cent to the synchronous control board (Fig. 3).  This
dial setting should equal 40% of the motor nameplate
field current divided by the ampere rating of the field
power supply.

Fig. 8  Cubicle Terminal Strip

Содержание EATON Ampgard Mark V

Страница 1: ...squirrel cage induction bars located in the faces TABLE I REFERENCE MATERIAL Contactor Ampere Instruction Type Rating I L or I B Type SJA 360A I B 48002 Type SJA 720A I B 48005 Type SJD 360A I B 48004...

Страница 2: ...oltage starter includes all of the components of a full voltage starter plus one or two additional contactors and related control components A synchronous motor controller is either a full voltage sta...

Страница 3: ...short out the reactor or to connect and disconnect the autotransformer in the circuit The overload protection relay e g IQ1000 II protects the motor from damage by overcurrent conditions single phasi...

Страница 4: ...erminals KA2 KB2 or KC2 RLY1 will drop out to open the control circuit RLY1 and RLY3 may pulse open and closed during certain types of faults causing the interposing relay MX to drop out insuring that...

Страница 5: ...ower supply cabinet The range of local voltage control adjustment is coordinated with the minimum output voltage adjustment P1 to produce the desired minimum and maximum output voltages Fig 4 Mark V C...

Страница 6: ...terminal located with the TO terminal near T4 Remove jumpers from the two 120V terminals located near T4 See Figure 5 and Table II ADJUSTINGTHE MOTOR FIELDVOLTAGE To adjust the motor field voltage use...

Страница 7: ...N When voltage is applied to terminals 115 and IN the Mark V will go into the synchronizing mode SYSTEM PROTECTION This controller includes circuits that provide a means of shutting down in the event...

Страница 8: ...ed on motor start up while ensuring that proper sequential synchronizing occurs and that motors will operate continu ously in synchronism The protection system must detect and operate for a condition...

Страница 9: ...ith motor voltage HP and FLA Check the torque tightness of all connections Study all applicable instruction material and diagrams Have available the schematic and connection diagrams fur nished with t...

Страница 10: ...use 2 With the motor field disconnected verify that the resistance between F1 and F2 on the terminal strip is 250 ohms 15 ohms 3 Measure the resistance of the starting and discharge resistor S D RES o...

Страница 11: ...th power available on the Ampgard bus system close the controller isolating switch and close the line contactor M 7 Plan to keep the motor field energized with the motor still for not more than two mi...

Страница 12: ...on 4 External Inhibit 7 Field Excitation 2 Frequency Option 6 Full Operation 11 Fuse and Contactor Check 9 Incomplete Sequence 6 Mark V Controller 3 Motor Controller 2 Motor Field Excitation 2 Page Op...

Отзывы: