background image

I.B. 48008

Page 6

Effective 11/97

OPTIONS

Each of the six variations rated by field supply output
current and voltage (50, 100, or 200 amperes at either
125 or 250 VDC) will perform with any combination of
user selected options as determined by jumpers inserted
into terminals on the synchronous control board.  See
Figure 5 and Table II.

Supply Frequency

The synchronizing and control circuit board may be
operated from either a 50 or 60 hertz power supply.  To
operate from a 60 hertz power supply add three jumpers
to the 60 hertz terminals located near RLY1 and one
jumper to the 60 hertz terminal located near RLY3.  See
Figure 5 and Table II.

To operate from a 50 hertz supply remove all four jump-
ers from the 60 hertz terminals  and add a single jumper
to the 50 hertz terminal located near RLY3.  See Figure 5
and Table II.

110/120 VAC Operation

To operate the synchronizing and control circuit board
from a 110 or 120 VAC supply, add six jumpers to
the120V terminals located above T1, T2, and T3 and two
jumpers to the 120V terminals located near T4.  Remove
the jumper from the 240V terminal located with TO
terminal near T4.  See Figure 5 and Table II.  (Jumpers
are factory installed, when supplied as part of a complete
motor starter.)

220/240 VAC Operation

To operate the synchronizing and control circuit board
from a 220 or 240 VAC supply, add three jumpers to the
240V terminals above T1, T2, and T3 and one terminal to
the 240V terminal located with the TO terminal near T4.
Remove jumpers from the two 120V terminals located
near T4.  See Figure 5 and Table II.

ADJUSTING THE  MOTOR  FIELD VOLTAGE

To adjust the motor field voltage, use the external 2000
ohm potentiometer (P2) shown in Figure 4.

POWER FACTOR, VAR OR DC FIELD CURRENT
CONTROL (OPTION)

When this option is included, a two-position selector
switch marked AUTO-MAN (SS1) is furnished.  On initial
startup, place SS1 in the MAN (manual) position.  I.B.
48009 explains the automatic operation and the connec-
tion of this additional control panel to terminals VPF and
PSC on the synchronous control board (Figure 5).

INCOMPLETE SEQUENCE – TIME-OUT SHUTDOWN

To utilize the time-out (TO) option which will energize
control relay RLY3, place a jumper onto the two pins
marked TO in the four-pin terminal marked 240V, TO
located to the right of RLY3 on the printed circuit board.
With the TO jumper in place, RLY3 is energized whenever
the motor slip frequency fails to decrease to the synchro-
nizing slip frequency set by SW1 within a period of 34
seconds when operating at 60 hertz or 40 seconds when
operating at 50 hertz.

TABLE II — JUMPER INSTALLATION FOR OPTIONS

FUNCTION

TERMINAL MARKING

PUT JUMPER

JUMPERS NEEDED

AT TERMINALS

TO ACTIVATE

Use a 50 Hertz Supply

50 HZ, 60 HZ

50 HZ

1

60 HZ, 60 HZ, 60 HZ

None

0

Use a 60 Hertz Supply

50 HZ, 60 HZ

60 HZ

1

60 HZ, 60 HZ, 60 HZ

60 HZ, 60 HZ, 60 HZ

3

Use a 110 or 120 VAC

240V, TO

None

0

Supply

120 V, 120V

120 V, 120 V

2

(3) 120 V, 240 V, 120 V

(3) 120 V, 120 V

6

Use a 220 or 240 VAC

240 V, TO

240 V

1

Supply

120 V, 120 V

None

0

(3) 120 V, 240 V, 120 V

(3) 240 V

3

Time-Out Shutdown

240 V, TO

TO

1

Содержание EATON Ampgard Mark V

Страница 1: ...squirrel cage induction bars located in the faces TABLE I REFERENCE MATERIAL Contactor Ampere Instruction Type Rating I L or I B Type SJA 360A I B 48002 Type SJA 720A I B 48005 Type SJD 360A I B 48004...

Страница 2: ...oltage starter includes all of the components of a full voltage starter plus one or two additional contactors and related control components A synchronous motor controller is either a full voltage sta...

Страница 3: ...short out the reactor or to connect and disconnect the autotransformer in the circuit The overload protection relay e g IQ1000 II protects the motor from damage by overcurrent conditions single phasi...

Страница 4: ...erminals KA2 KB2 or KC2 RLY1 will drop out to open the control circuit RLY1 and RLY3 may pulse open and closed during certain types of faults causing the interposing relay MX to drop out insuring that...

Страница 5: ...ower supply cabinet The range of local voltage control adjustment is coordinated with the minimum output voltage adjustment P1 to produce the desired minimum and maximum output voltages Fig 4 Mark V C...

Страница 6: ...terminal located with the TO terminal near T4 Remove jumpers from the two 120V terminals located near T4 See Figure 5 and Table II ADJUSTINGTHE MOTOR FIELDVOLTAGE To adjust the motor field voltage use...

Страница 7: ...N When voltage is applied to terminals 115 and IN the Mark V will go into the synchronizing mode SYSTEM PROTECTION This controller includes circuits that provide a means of shutting down in the event...

Страница 8: ...ed on motor start up while ensuring that proper sequential synchronizing occurs and that motors will operate continu ously in synchronism The protection system must detect and operate for a condition...

Страница 9: ...ith motor voltage HP and FLA Check the torque tightness of all connections Study all applicable instruction material and diagrams Have available the schematic and connection diagrams fur nished with t...

Страница 10: ...use 2 With the motor field disconnected verify that the resistance between F1 and F2 on the terminal strip is 250 ohms 15 ohms 3 Measure the resistance of the starting and discharge resistor S D RES o...

Страница 11: ...th power available on the Ampgard bus system close the controller isolating switch and close the line contactor M 7 Plan to keep the motor field energized with the motor still for not more than two mi...

Страница 12: ...on 4 External Inhibit 7 Field Excitation 2 Frequency Option 6 Full Operation 11 Fuse and Contactor Check 9 Incomplete Sequence 6 Mark V Controller 3 Motor Controller 2 Motor Field Excitation 2 Page Op...

Отзывы: