background image

I.B. ATS-SD02

Page 26

Effective 5/98

circuits automatically initiate an immediate transfer of
power from the normal to the emergency source when
the power source fails or the voltage level drops below a
preset value. Transfer back to the normal power source
is automatic upon return of the normal power source.

Monitoring the power source is always performed on the
line side of the power source to which the switch is con-
nected. The normal power source is the preferred
source and the transfer switch will always seek this
source when it is available.

7.3  BYPASSING THE TRANSFER SWITCH

7.3.1  NORMAL TO NORMAL BYPASS

The normal switching device can be bypassed and iso-
lated by the following sequence (Figure 7-2):

1.

Move the generator selector switch to the OFF posi-
tion to avoid nuisance starts.

2.

Remove the key from the emergency switching
device by turning it counterclockwise while pushing
up on the lever next to the key interlock. This will
lock the emergency switching device to prevent it
from closing.

3.

Insert the key in the normal bypass switching device
and turn it clockwise, which will release the lever to
the left of the key interlock. This will unlock the nor-
mal bypass switching device.

4.

Close the normal bypass switch manually. The nor-
mal bypassed light will illuminate.

5.

Open and rack out the normal switching device (see
Section 6). The normal isolated light will illuminate.
The normal position energized light will no longer be
illuminated.

6.

Inspect and/or perform maintenance on the 
normal switching device.

7.

Rack in the normal switching device (see Section 6).
The normal switching device will automatically
recharge and close when it is in the CONNECT
position. The normal isolated light will no longer be
illuminated, but the NORMAL position energized
light will be illuminated.

8.

Open the normal bypass switch. The normal
bypassed light will no longer be illuminated.

9.

Remove the key from the normal bypass switch by
turning the key counterclockwise while pushing up

on the lever next to the key interlock. This will lock
the normal bypass switch to prevent it from closing.

10. Insert the key in the emergency switch and turn the

key clockwise, which will release the lever to the left
of the key interlock. This will unlock the emergency
switching device. 

11.  The normal switching device is now back in auto

matic operation.

7.3.2   EMERGENCY TO EMERGENCY BYPASS

The emergency switching device can be bypassed and
isolated by the following sequence:

1.

Move the generator selector switch to the RUN posi-
tion to avoid loosing power.

2.

Remove the key from the normal switching device
by turning the key counterclockwise while pushing
up on the lever next to the key interlock. This will
lock the normal switching device and prevent it from
closing.

3.

Insert the key in the emergency bypass switching
device and turn the key clockwise to release the
lever to the left of the key interlock. This will unlock
the emergency bypass switching device

4.

Close the emergency bypass switching device man-
ually. The emergency bypass light will illuminate.

5.

Open and rack out the emergency switching device
(see Section 6). The emergency isolated light will
illuminate, and the emergency position energized
light will no longer be illuminated.

6.

Inspect and/or perform maintenance on the emer-
gency switching device.

7.

Rack in the emergency switching device (see
Section 6). The emergency switching device will
automatically recharge and close when in the CON-
NECT position. The emergency isolated light will no
longer be illuminated, and the emergency position
energized light will illuminate.

8.

Open the emergency bypass switch. The emer-
gency bypassed light will no longer be illuminated.

9.

Remove the key from the emergency bypass switch
by turning the key counterclockwise while pushing up
on the lever next to the key interlock. This will lock the
emergency bypass switch and prevent it from closing.

Содержание ATVISPE31000XSU

Страница 1: ...I B ATS SD02 Effective 5 98 Replaces I B ATS SDO1 dated October 1996 Cutler Hammer Instructions for Cutler Hammer Drawout Transfer Switch and Bypass Isolation Switch...

Страница 2: ......

Страница 3: ...THAT CAN CAUSE DEATH OR SEVERE PERSONAL INJURY FOLLOW PROPER INSTALLATION OPERATION AND MAINTENANCE PROCEDURES TO AVOID THESE VOLTAGES WARNING TRANSFER SWITCH EQUIPMENT COVERED BY THIS INSTRUCTION BOO...

Страница 4: ...T DESCRIPTION 3 1 General 7 3 2 Power Panel 7 3 2 1 Main Contacts 7 3 2 2 Switch Interlocks 8 3 2 3 Drawout Interlocks 8 3 2 4 Transfer Mechanism 9 3 2 5 Drawout Mechanism 9 3 3 Voltage Selection Pane...

Страница 5: ...Bypass 26 7 3 3 Normal to Emergency Bypass 29 7 3 4 Emergency to Normal Bypass 29 7 4 Manual Operation when in Bypass Mode 30 7 4 1 Normal Bypass to Emergency Bypass 30 7 4 2 Emergency Bypass to Norm...

Страница 6: ...r Switch NEMA 1 Enclosure 16 4 3 Side View and Rear View of Power Panel 18 4 4 Drawout Stationary 20 4 5 Seismic Tested and Approved Product Mounting Instructions 19 4 6 Secondary Control Block Contac...

Страница 7: ...FAMILIARIZE PERSON NEL WITH THE STYLE OF PRESENTATION THIS WILL HELP TO INSURE THAT PERSONNEL ARE ALERT TO WARNINGS WHICH APPEAR THROUGH OUT THE DOCUMENT IN ADDITION CAUTIONS ARE ALL UPPER CASE AND B...

Страница 8: ...cal operation feature is added The switch electrically transfers power when an appropriate pushbutton on the front of the enclosure is pushed If necessary the switch can also be operated manually In a...

Страница 9: ...e Rating Type kA 800 100 100 85 2000 L 200 1000 100 100 85 2000 L 200 1200 100 100 85 2000 L 200 1600 100 100 85 3000 L 200 2000 100 100 85 3000 L 200 2500 100 100 85 4000 L 200 3000 100 100 85 4000 L...

Страница 10: ...ment catalog numbers provide a significant amount of relevant information that pertains to a particular piece of equipment The catalog number identification table Table 1 2 provides the required inter...

Страница 11: ...e Enclosure Arrangement of Poles Rating Frequency Type Listing Drawout Insulated Case E Two 2 0600 120VAC 60Hz A No Enclosure K UL Listed U Switches both Sources Three 3 0800 208VAC 60Hz B Type 1 S Fo...

Страница 12: ...not discard the packing material until the equipment is ready for installation A plastic bag of documents will be found within the enclosure usually attached to the inside of the door Important docume...

Страница 13: ...tion Panel Logic Panel IQ Transfer Solid State The components comprising the three panels are installed in accordance with the specific requirements of the circuit being controlled Each transfer switc...

Страница 14: ...mechanically interlocked to the drawout mechanism to ensure that the switching device is always open when connecting or disconnecting it from the line and load stabs LIFTING THE PADLOCK LATCH WHILE A...

Страница 15: ...chanism The switching device is closed by energizing a solenoid that releases the spring mechanism A shunt trip will open the switching device if energized 3 2 5 DRAWOUT MECHANISM The drawout mechanis...

Страница 16: ...scription More detailed selections that must be made within a specific option are lettered For available options associated with the logic scheme refer to the specific logic document associated with t...

Страница 17: ...IQ Analyzer Emergency Only Q IQ Analyzer Both N E Selectable R DP 4000 Normal Only S DP 4000 Emergency Only T DP 4000 Both N E Selectable 20A Rear Bus Connections Solderless lugs are furnished as stan...

Страница 18: ...y of lights switches and pushbuttons depending upon the options required for a particular switch All switch doors are supplied with a heavy duty plastic accessory panel in place whether or not externa...

Страница 19: ...rogram which requires an extensive follow up testing program for listed devices Standard UL1008 for automatic transfer switches lists devices under the re examination program which only requires a con...

Страница 20: ...d to retard the action of relays or cover the logic in a way that restricts adjustments Maintain proper electrical clearances between live metal parts and grounded metal For installation and maintenan...

Страница 21: ...ergency Power Cable Connections Normal Power Cable Connections Emergency Power Cable Connections Neutral Cable Connection Grounding Right hand side when facing front switch F I G H F I G H Transfer Di...

Страница 22: ...152 4 23 24 59 0 30 00 76 2 23 24 59 0 28 44 72 2 3400 1542 4 Pole 800 2000A 68 00 172 7 60 00 152 4 29 24 74 3 30 00 76 2 29 24 74 3 28 44 72 2 4000 1814 3 Pole 2500 3000A 82 00 208 3 60 00 152 4 29...

Страница 23: ...plate on the intelli gence panel of transfer switch agree with sys tem current and voltage Step 3 After the transfer switch is mounted provide conduit or cable openings as required Ensure that no meta...

Страница 24: ...R SELECTION AND OR CONNECTION COULD RESULT IN EQUIPMENT DAMAGE 4 6 MOUNTING SWITCHING DEVICE IN THE DRAW OUT MECHANISM When mounting the switching device in the drawout mechanism ensure that the exten...

Страница 25: ...cleats must be ATVISP NTVSSP Figure 4 5 Seismic Tested and Approved Product Mounting Instructions Switch Type Amp Rating Mounting Bolt Torque ATVSSP 600 4000A 50 ft lbs 68 Nm NTVSSP 500 4000A 50 ft l...

Страница 26: ...es up correctly with the indexing lever 4 7 WIRING POWER CONDUCTORS AND CONTROL WIRING MAY HAVE VOLTAGE PRESENT THAT CAN CAUSE SEVERE PERSONAL INJURY OR DEATH DE ENERGIZE ALL POWER OR CONTROL CIRCUIT...

Страница 27: ...e manual handle without first isolating the control circuit causes an automatic transfer 5 2 AUTOMATIC TRANSFER SWITCH The operating sequence of an automatic transfer switch is dictated by the switch...

Страница 28: ...ltage the logic causes the normal relay to pickup The normal relay closes certain contacts while opening others This starts the return to the normal power source and normal transfer switch operation D...

Страница 29: ...CE IS IN THE CONNECTED POSITION The switching device will not close in the WITHDRAWN position 6 2 SWITCH POSITION The drawout mechanism has four positions They are achieved by lifting the padlock latc...

Страница 30: ...H TO SER VICE WITHOUT INSTALLING THE DEADFRONT SHIELD Return the switching device to the desired position Replace the deadfront shield when the switch is in the DISCONNECT position 6 4 OPERATIONAL CHE...

Страница 31: ...e causing the transfer switch to start the transfer sequence If the push button is held down the transfer switch will transfer the load to the emer gency switch Releasing the button will restore regu...

Страница 32: ...sed light will no longer be illuminated 9 Remove the key from the normal bypass switch by turning the key counterclockwise while pushing up on the lever next to the key interlock This will lock the no...

Страница 33: ...0 Operational High Load Communications Trip Time Overcurrent Curve Shape Pickup x In Time Multiplier Pickup x In Time Program Phase Ground I I I RMS Amperes Settings Test Time Trip Cause Test Program...

Страница 34: ...000 Operational High Load Communications Trip Time Overcurrent Curve Shape Pickup x In Time Multiplier Pickup x In Time Program Phase Ground I I I RMS Amperes Settings Test Time Trip Cause Test Progra...

Страница 35: ...k the emergency bypass switching device to prevent it from closing 10 Insert the key in the normal switching device and turn the key clockwise which will release the lever to the left of the key inter...

Страница 36: ...ing 3 Insert the key in the emergency bypass switching device and turn it clockwise to release the lever to the left of the key interlock This will unlock the emergency bypass switching device 4 Open...

Страница 37: ...OBLEM SOLV ING ONLY PROPERLY TRAINED PERSONNEL FAMILIAR WITH THE TRANSFER SWITCH EQUIPMENT AND ITS ASSOCIATED EQUIPMENT SHOULD BE PERMIT TED TO PERFORM THE PROBLEM SOLVING FUNC TION IF AN INDIVIDUAL D...

Страница 38: ...A2 on the normal switching device spring release coil Does the voltage measure 120 VAC 10 volts Record reading If YES Check spring release coil in normal switching device If NO Check wiring to A1 and...

Страница 39: ...ion by this type of equipment inspection and maintenance checks should be made on a regularly scheduled basis Since equipment maintenance will consist mainly of keeping the equipment clean the frequen...

Страница 40: ...ity c Inspect switching devices for dust dirt soot Remove dust dirt soot grease moisture and corrosion grease moisture or corrosion contamination from the surface of the switching device using a dry s...

Страница 41: ...I B ATS SD02 Page 35 Effective 5 98...

Страница 42: ...I B ATS SD02 Page 36 Effective 5 98...

Страница 43: ......

Страница 44: ...tract between the purchaser and Cutler Hammer NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PAR TICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEAL...

Отзывы: