Adjust and Function Specification
§
CE53 Multi-steps all files set to default (settable range 0~1)
The function cannot be modified during revolution
The setting can not be changed while the machine is working.
CE53=0 Data remain unchanged.
CE53=1 Reset data in files 1-6 to default.
§
CE54 Multi-steps memory duplicate function (settable range 1~6)
The function cannot be modified during revolution
The setting cannot be changed while the machine is working.
Duplicate current using file (CE05~CE46) to CE54 .
§
CE55 Yards counter clear (settable range 0~1)
Set CE55=1 to clear Yards counter.
§
CE61 Input terminal for Set Point and PI feedback (settable range 0~7)
The function cannot be modified during revolution
CE61
Target value
PI feedback terminal
0
De-active PI control
1
Set by CE67
IN1
2
Set by CE67
IN2
3
Set by CE67
IN3
4
From terminal IN1
IN2
5
From terminal IN1
IN3
6
From terminal IN3
IN1
7
From terminal IN3
IN2
Note:
1. IN1(4~20mA) scale to 0~100.0 %
,
IN2
、
IN3(0~10V) scale to 0~100.0 %
2. output frequency = PI output fre set frequency
3. Make sure this parameter setting does not conflict with the setting for Cd01
(Set frequency source).
Ex: If Cd01=1 then the parameter CE61 cann’t be modify to 2 ,4 or 7.