Adjust and Function Specification
Ex. Motor: 60Hz, 4-pole, 1 horsepower, 220V, no-load current 1.2Arms
Inverter: 1 horsepower, 220V, rated current 4.2Arms, Cd06=100
Cd52 = Motor no-load current / (Inverter rated current
×
Motor rated
current ratio Cd06 )
×
100%
= 1.2 / (4.2
×
100%)
×
100%
= 28.5%
§
Cd53 Motor slip differential compensation (Settable range 0-100)
This function is to compensate speed variation produced by load variation.
This function must accommodate the content of Cd52.
Setting value 0-100 in relative slip differential 0.0-10.0%
Ex. 60HZ, 4-pole
1700 rpm
Synchronous speed = 1800 rpm
Full-load speed
= 1700 rpm
Slip differential speed = 1800-1700=100 rpm
Slip differential % = Slip differential speed / Synchronous speed
×
100%
= 100 / 1800
×
100%
= 5.5%, Setting Cd52=55
Slip differential compensation
Load
variation
Time
Motor
speed
Motor
speed
Output
frequency
Without slip
differential
compensation
With
slip
differential
compensation
With
slip
differential
compensation