OFF
ON
DIP Switch Positions:
Driver type:
On/Off (no dimming)
1 2 3 4 5 6
↓
O
N
Wired
Sensor:
None
( # 4 O N )
DIP Switches
1
1L1
2
3L2
3
5L3
4
7L4
1
2T1
2
4T2
3
6T3
4
8T4
Line Voltage
Wires
WHITE Neutral
RED
Switched Load
120/277VAC
Hot
BLACK Hot 120/277VAC
CONTACTOR
(120 or 277VAC
Coil Voltage)
Neutral
Low Voltage
Wires
Cap unused
wires.
Wireless Adapter with Power Monitoring
Model: WA100-PM
Input: 120-277VAC, 50/60 Hz
Load: 15A@120-277VAC Ballast or Incandescent, 1hp@120-230VAC
Output: +24VDC; 75mA
Ambient Temperature -4° to 149°F (-20° to 65°C)
FOR INDOOR USE ONLY UL 2043 Plenum Rated
Patent: www.daintree.net/company/patents
C
US
IEEE Address:
00228103007-00000
Load
Black
Hot
Neut
Red
White
Blue (Digital In 1)
Yellow (Digital In 2)
Orange (0-10V In)
Red (24VDC Output)
Black (Ground)
Green (Digital Out LSD)
Violet (0-10V Out)
Gray (Ground)
Relay
WA100-PM
15A
15A+45mA
45mA
CONTAINS FCC ID: Z6G-DT357
CONTAINS IC: 10478A-DT357
CAN ICES-3 (B)/NMB-3(B)
RoHS
Control Input
Neutral
Control Input
Hot
Load Outputs
(Hot)
Line Voltage Supply
Hots
Wireless Adapter (WA100-PM)
This configuration allows the WA100-PM to provide On/Off switching control to an external contactor.
Fig. 15: Switching Contactors:
17