Plug Load Applications (WA100-PM)
Wiring for Combination Plug Load (Aux Relay with Input
Control Signal) and On/Off Light
In the wiring diagram below, the WA100-PM is used to
control both an On/Off light and a plug load circuit.
Perform Installation Test Suite 1
OFF
ON
DIP Switch Positions:
Driver: On/Off
Plug Load: On/Off
1 2 3 4 5 6
O
N
(# 2,4 ON)
DIP Switches
Wired
Sensor:
None
Line Voltage
Wires
WHITE Neutral
RED
Switched
Load
120-277VAC
BLACK Hot 120-277VAC
Hot
Neutral
RED 24VDC Power
GREEN Digital Ouptut LSD
Neutral
SW Hot
Hot
Hot
Low Voltage
Wires
Cap unused
wires.
www.daintree.net
Wireless Adapter with Power Monitoring
Model: WA100-PM
Input: 120-277VAC, 50/60 Hz
Load: 15A@120-277VAC Ballast or Incandescent, 1hp@120-230VAC
Output: +24VDC; 75mA
Ambient Temperature -4° to 149°F (-20° to 65°C)
FOR INDOOR USE ONLY UL 2043 Plenum Rated
Patent: www.daintree.net/company/patents
C
US
IEEE Address:
00228103007-00000
Load
Black
Hot
Neut
Red
White
Blue (Digital In 1)
Yellow (Digital In 2)
Orange (0-10V In)
Red (24VDC Output)
Black (Ground)
Green (Digital Out LSD)
Violet (0-10V Out)
Gray (Ground)
Relay
WA100-PM
15A
15A+45mA
45mA
CONTAINS FCC ID: Z6G-DT357
CONTAINS IC: 10478A-DT357
CAN ICES-3 (B)/NMB-3(B)
RoHS
Ballast
or LED Driver
(non-dimming)
Plug Load
RED 24VDC
RED
RED
BLACK Common
BLUE Control Output
GREEN
Ground
Aux Relay with input
control signal (20A)
**
*0-10V Dimming output, 5 mA available, Up to
10 LED drivers or fluorescent ballasts typical; the
chance of noise on the signal increases with more.
**Relays used to control plug loads must be
compliant with UL498 (Attachment Plug and
Receptacles) or equivalant.
GE is a trademark of the General Electric Company. All other trademarks are the property of their respective owners.
Information provided is subject to change without notice. All values are design or typical values when measured
under laboratory conditions. Current and GE Lighting are businesses of the General Electric Company. © 2017 GE
Call
1 888 694 3533 products.currentbyge.com