Wireless Adapter (WA100-PM)

Test Suite 2: 

    Any Occupancy Sensor
    

    1. Press and immediately release the blue Reset button. The red Error LED flashes once, then pauses and repeats.

              2. Check that the connected lights cycle On and Off, or cycle from maximum to minimum brightness then turn    
          Off per the DIP switch configuration.
              3. Press and immediately release the blue Reset button again. The red Error LED flashes twice, 
          then pauses and repeats.
              4. Trigger the occupancy sensor. The light connected to the driver turns On.  When the sensor 
          times out the light turns Off. 
              5. Press and immediately release the Reset button to exit testing.
              6. Press and hold the blue RESET button on the WA100-PM for 3 seconds to reset the unit. Release the button  

 

                  when the green Joined      LED and the red Error      LEDs begin flashing.

Test Suite 3: 

    Dimming Occupancy Photosensor
    

    1. Press and immediately release the blue Reset button. The red Error LED flashes once, then pauses and repeats.

              2. Check that the lights connected to the driver cycle from maximum to minimum brightness then turn Off, 
          then repeat.
        3. Press and immediately release the blue Reset button. The red Error LED flashes twice, then pauses and repeats.
              4. Trigger the occupancy sensor. The green Joined LED turns On and the light connected to the driver turns On.    
                    When the sensor times out the Joined LED and light turns Off.
              5. Press and immediately release the blue Reset button again. The red Error LED flashes three times, then pauses  
          and repeats.
              6. The light connected to the driver turns On.
              7. The light’s output is proportional to the amount of light received by the photosensor.
            

  For dimming lights, shine a bright light at the photosensor – the light gets brighter. 

               Cover the photosensor – the light gets dim. 
            

  For switched lights, cover the photosensor – the light turns Off.

                          Shine a bright light at the photosensor – the light turns On.
              8. Press and immediately release the Reset button to exit testing.
              9. Press and hold the blue RESET button on the WA100-PM for 3 seconds to reset the unit. Release the button  

 

                  when the green Joined      LED and the red Error      LEDs begin flashing.

23

Содержание WA100-PM

Страница 1: ...n to indicate its location 4 Mount the WA100 PM in the driver cavity of the light fixture or external to the light fixture or to a junction box approved for the application See Mounting page 13 5 Conn...

Страница 2: ...xpected operation After you change DIP switch settings you need to press the blue Reset button for 3 seconds to reset the unit Release the button when the green Joined and red Error LEDs begin flashin...

Страница 3: ...0 See Figure 12 No Driver sensors only provides wireless adaptation to connected occupancy sensor and or photosensor only No driver control Sensor To provide wireless adaptation for sensors set DIP sw...

Страница 4: ...Line voltage wiring connects to the electrical supply circuit and to the driver s The Black Hot flying lead and the Red Switched Load flying lead are 14AWG The White Neutral flying lead is 18AWG Low v...

Страница 5: ...7 00000 Load Black Hot Neut Red White Blue Digital In 1 Yellow Digital In 2 Orange 0 10V In Red 24VDC Output Black Ground Green Digital Out LSD Violet 0 10V Out Gray Ground Relay WA100 PM 15A 15A 45mA...

Страница 6: ...cent ballasts typical the chance of low voltage errors increases with more Wireless Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1...

Страница 7: ...ature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blue Digital In 1 Yellow...

Страница 8: ...DC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blu...

Страница 9: ...ltage errors increases with more Wireless Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1hp 120 230VAC Output 24VDC 75mA Ambient Te...

Страница 10: ...e chance of low voltage errors increases with more Wireless Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1hp 120 230VAC Output 24V...

Страница 11: ...ent ballasts typical the chance of low voltage errors increases with more Wireless Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1h...

Страница 12: ...Incandescent 1hp 120 230VAC Output 24VDC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 0...

Страница 13: ...t Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Red Blue Digital In 1 Yellow Digital In 2...

Страница 14: ...Load 15A 120 277VAC Ballast or Incandescent 1hp 120 230VAC Output 24VDC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents...

Страница 15: ...A Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blue Digi...

Страница 16: ...s Adapter with Power Monitoring Model WA100 PM Input 120 277VAC 50 60 Hz Load 15A 120 277VAC Ballast or Incandescent 1hp 120 230VAC Output 24VDC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDO...

Страница 17: ...75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blue D...

Страница 18: ...57 CAN ICES 3 B NMB 3 B RoHS WA100 PM REGULAR Line Voltage 120 277VAC LVS Model RRU X UM NC COM NO WHITE Neutral Hot NC COM NO RED BLACK BLUE RED BLUE YELLOW Connect 120VAC to BLK 277VAC to ORG FIXTUR...

Страница 19: ...r LED Driver 0 10VDC WA100 PM Wireless Adapter WA100 PM Set DIP switches and perform Installation Test appropriate to 0 10v dimming and connected sensors In this application the WA100 PM is powered by...

Страница 20: ...eep them neat out of the way and protected against shorting or interference with other components wiring or devices It is best to trim unused wires to about 5 inches in length isolate them using a wir...

Страница 21: ...The WA100 PM can be secured at the other end using the integral screw tab Alternatively it can be mounted externally to a junction box enclosure or fixture housing through a 1 2 knockout Fig 19 Mounti...

Страница 22: ...aves significant time during the commissioning process Record IEEE Addresses If you have not already done so be sure that each WA100 PM s IEEE address last 4 or 5 digits is recorded on the facility fl...

Страница 23: ...and repeats 2 Check that the lights connected to the driver cycle from maximum to minimum brightness then turn Off then repeat 3 Press and immediately release the blue Reset button The red Error LED f...

Страница 24: ...it testing 4 Press and hold the blue RESET button on the WA100 PM for 3 seconds to reset the unit Release the button when the green Joined LED and the red Error LEDs begin flashing Test Suite 6 Photos...

Страница 25: ...sor the light turns On 6 Press and immediately release the Reset button to exit testing 7 Press and hold the blue RESET button on the WA100 PM for 3 seconds to reset the unit Release the button when t...

Страница 26: ...e Manager application Troubleshooting The Installation Test procedure fails 1 Confirm that the WA100 PM is powered 2 Check the connections from the WA100 PM to the driver s and low voltage control dev...

Страница 27: ...L x 1 7 W x 1 18 H 10 1 L x 1 7 W x 1 18 H with mounting bracket Driver references include ballasts unless otherwise noted FCC warning message This equipment has been tested and found to comply with t...

Страница 28: ...t 24VDC 75mA Ambient Temperature 4 to 149 F 20 to 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red Whit...

Страница 29: ...o 65 C FOR INDOOR USE ONLY UL 2043 Plenum Rated Patent www daintree net company patents C US IEEE Address 00228103007 00000 Load Black Hot Neut Red White Blue Digital In 1 Yellow Digital In 2 Orange 0...

Страница 30: ...ss 00228103007 00000 Load Black Hot Neut Red White Blue Digital In 1 Yellow Digital In 2 Orange 0 10V In Red 24VDC Output Black Ground Green Digital Out LSD Violet 0 10V Out Gray Ground Relay WA100 PM...

Отзывы: