40
Culligan® Premier Series Automatic Deionizer
40
Cat. No. 01024000
Screen Display
Range
Description/Changing the Setting
PRE FR CAT
>2
MINUTES
0–99 Minutes
(default=2)
The duration of the rinse preceding the cation fast rinse. Press
and
or
then
to change the setting.
FAST RINSE CAT
>20
MINUTES
0–99 Minutes
(default=20)
The duration of the cation fast rinse. Press
and
or
then
to change the setting.
BACKWASH ANI
>10
MINUTES
0–99 Minutes
(default=10)
Press
and
or
then
to change the setting.
CAUSTIC DRAW
>60
MINUTES
0–99 Minutes
(default=60)
The duration that the caustic pump is on. Press
and
or
then
for setting information.
SLOW RINSE ANI
>60
MINUTES
0–99 Minutes
(default=60)
This cycle allows water to flow down through the resin, rinsing away
the excess caustic and remaining anions. Press
and
or
then
to change the setting.
PRE FR ANI
>2
MINUTES
0–99 Minutes
(default=2)
The duration of the rinse preceding the anion fast rinse. Press
and
or
then
to change the setting.
FAST RINSE ANI
>20
MINUTES
0–99 Minutes
(default=20)
The duration of the anion fast rinse. Press
and
or
then
to change the setting.
QUALITY RINSE
5
MINUTES
0–99 Minutes
(default=5)
This is the final cycle of regeneration. Press
and
or
then
to change the setting.
QUALITY DELAY
15
SECONDS
0–600 Seconds
(default=15)
Specifies the pause/delay to begin the quality rinse cycle. Press
and
or
then
to change the setting.
SERVICE
FEB-01-13 12:11P
10.0GPM 161PPM
8. Press
until the deionizer controller displays the home screen.