Installation
11
Cat. No. 01024000
Installation
Preinstallation Information
Read the entire instruction manual before you begin installation. Failure to install and operate the system as required will
void the warranty. The system will perform at maximum efficiency, when installed and operated as designed.
Obtain all the materials and tools needed for the installation before beginning. Always use the correct tools to install and
maintain the system. The installation must conform to local plumbing and electrical codes. Code compliance is the respon-
sibility of the installer or contractor.
WARNING! Vacuum breakers are required on both tanks. Failure to install vacuum breakers can
result in serious equipment and facility damage and pose a significant hazard to
personnel.
Operating Parameters
Parameter
Minimum
Maximum
Hardness
—
35 grains per gallon
Iron
—
5 ppm
Flow Rate
0.5 gpm/ft
3
5 gpm/ft
3
Chlorine
—
0.1 ppm
Turbidity
—
<5 NTU
Water Pressure
40 psi
60 psi*
Water Temperature
45°F
100°F**
pH
6.8
—
Oil
—
0
*Maximum pressure dependent on components.
**Higher temperature systems available on special order—consult factory.
•
Protect the system from positive and vacuum pressure extremes. Do not expose the system to surging pressures or water hammer.
Water hammer will cause damage to the control valves, mineral tanks, and plumbing. If a condition of this type exists, a Water Ham-
mer Arrestor must be installed to prevent damage.
•
Protect the system against backpressure caused by a pump or any type of water storage system. If pressure on outlet exceeds inlet
pressure, resin can be flushed into the inlet water supply during the service cycle.
•
When routing the outlet piping to an atmospheric storage tank, a valve or flow control must be installed in the outlet piping to prevent
over running of the system. A backpressure of 15 to 20 psi should be maintained on the system during service.
•
Protect the system from freezing weather conditions. Temperatures at and below freezing will cause damage to tanks, valves and
plumbing. Water expands when it freezes and can cause the tanks and plumbing to burst.
•
Protect the system from high temperatures in excess of 100°F. Some of the components used in the manufacture of the system will
not withstand high temperatures. Do not connect the system down stream of a hot water system. Also protect the outlet of the system
from backup of hot water from a water heater or boiler.
•
The system operates on 120 Volts from a normal 15 Amp wall outlet receptacle, which is properly grounded. Conformance to local and
National Electrical Codes must be observed and are the responsibility of the installer. The Premier Auto DI Equipment is designed for
indoor operation only.
•
The system must be located within 10 feet of an open floor drain or sump, which is connected to a neutralization or other waste treat-
ment system. The drains from the system must contain vents, in accordance with the local plumbing codes. The flow of drain water
should be observable. Back-pressure from overhead drain systems can affect the system, therefore; it is not recommended to run the
drains any higher that eight (8) feet above the tanks. On overhead drains, an air gap must be installed in the highest point of the drain
line, and local plumbing codes and regulations should be followed.
•
It is recommended that inlet and outlet valves be installed on the unit for future service ability. The inlet and outlet valves are utilized to
turn off the water to the unit so that the valves and other components can be serviced.
•
Threading compounds and other contaminating materials from the installation of the piping; must be flushed from the piping prior to
allowing water to enter the system. These foreign materials can cause damage to the valves.
•
The caustic regenerate should maintain a temperature of 80-100 degrees F. The caustic can solidify at temperatures in the 50-60
degrees F range. It is recommended to add a band heater to the chemical drum or heating element in the chemical storage container.