7
GG-6
Wiring
(continued)
Sensor Wiring:
4/20 mA, 350 Ohm input impedance.
•
Refer to sensor manual for cable recommendations.
•
Usually 20/3 shielded cable (Belden 8772 or equivalent).
• Length of cable should not exceed 1,500 feet.
Analog Output Wiring: (for optional GG-6-AOB)
• The analog output is 4/20 mA signal for monitoring by plant PLC or other
analog input equipment. It is powered by the GG-6.
•
Use 2-conductor shielded cable compatible with receiving equipment.