CTI 2572-A Installation and Operation Guide V1.3
87
HEX
DEC
DESCRIPTION
SOLUTION
The protocol manager received a command number
which is not valid.
a valid Command Code.
Check to be sure that the Command Slot points to
the correct V memory Address for the Command
Block.
Make sure that you have specified the correct
protocol manager number in the Create Connection
command and that you are using the right
connection number.
249B
9371
ERROR READING ETHERNET PORT
An error was encountered reading from the Ethernet
port.
If the problem persists, contact CTI.
249C
9372
ERROR WRITING ETHERNET PORT
An error was encountered writing to the Ethernet
port.
If the problem persists, contact CTI.
249D
9373
CMD TIMEOUT ERROR
The time to process the requested command
exceeded the Command Timeout value. Command
processing has been halted.
Note that the timeout value may have been explicitly
set in the Command Block or the default may have
been used (timeout = 0).
In some circumstances, you may occasionally get a
timeout error, especially with heavy network traffic or
remote modem data links. In these circumstances,
your logic should retry the command.
This error may indicate a bad connection (faulty
cable, loose connector, etc.). Check all cabling
carefully.
If the error persists and you have explicitly set the
timeout value, it is possible that you have set the
timeout value too small. Try increasing the value or
using the default value.
249E
9374
PROTOCOL MANAGER BUSY
The protocol manager received a new command
prior to completing the previous command.
You can cause this error by using two command
slots to send concurrent commands to the same
connection number. Don’t do this.
249F
9375
INVALID CLIENT CONNECTION NO.
The connection number used during Create Socket
was out of the valid range. The valid range of
connection numbers is 19221 –19228.
Correct the command block data.
24AC
9388
MEMORY READ ERROR
The 2572-A was unable to read the requested V
memory.
When this error occurs, it is usually due to an invalid
memory address specification in the command
block. Check the command block and make
corrections if necessary.
Check to ensure that the PLC you are addressing is
configured for the address you are trying to access.
24AD
9389
MEMORY WRITE ERROR
The 2572-A was unable to write to the requested
PLC memory.
Check the command block to ensure a valid V
memory address has been specified.
2572-A Internal Errors
Error codes whose lower byte is greater than C8 hex are internal code errors. If you should experience
one of these errors, contact CTI for assistance.
Содержание 2572-A
Страница 8: ......
Страница 16: ......
Страница 28: ......
Страница 32: ......
Страница 60: ......
Страница 84: ......
Страница 96: ......
Страница 104: ...CTI 2572 A Installation and Operation Guide 96 WX WY Quick Reference...
Страница 112: ......
Страница 116: ......
Страница 126: ......
Страница 130: ...CTI 2572 A Installation and Operation Guide 122 WX WY Quick Reference...