CTI 2572-A Installation and Operation Guide V1.3
15
SW8 – 10
are reserved for future use.
SW11- PLC Interface Mode
. When this switch is set to the C
LOSED
position, the module will use the
same PLC interface as the 2572-A. When the switch set to the
OPEN
position, the module will use a
high performance interface that increases the amount of data that can be transferred to and from the
PLC. In most applications you will want to use the high performance mode. However, there may be
some installations where overall system performance is better in compatibility mode.
Interface Mode
Position
SW11
Compatibility Closed
High Performance
Open
SW12 – Diagnostic Start
. When this switch is closed, the module will conduct extensive diagnostic
tests during startup. Because, the tests increase them amount of time to start the module, you will
usually disable the tests unless you are troubleshooting a problem. The results of the test may be
viewed via the web server interface.
Diagnostic Start
Position
SW12
Enabled Closed
Disabled
Open
The module will be shipped with all dipswitches in the Open position. This corresponds to:
Baud Rate ................. 9600
Startup Option............ PLC
Start
Configuration Lock .... Unlocked
Firmware Lock ........... Unlocked
Password ................... Not Bypassed
PLC Interface Mode .. High Performance
Diagnostic Start ......... Disabled
NOTE:
The Option switches are read only at module startup. If you change the switch position after startup,
you must reset the module before the setting will take effect.
2.5. Setting the Module ID Switches
When the Startup Option is set to A
UTO
S
TART
, the Module ID switches are
used to determine the module IP address.
The switches are ignored when
the Startup Option is PLC
S
TART
.
When the Module ID switches are set to a value of 00, the module will use
the network parameters stored in EEPROM. When they are set to a value of
01 through FE, the module will attempt to obtain the Network parameters
from a DHCP server, using the Module ID as a key. See APPENDIX E.
USING DHCP for instructions. Setting the Module ID switches to a value
of FF places the 2572-A in a special configuration mode. A switch value
Содержание 2572-A
Страница 8: ......
Страница 16: ......
Страница 28: ......
Страница 32: ......
Страница 60: ......
Страница 84: ......
Страница 96: ......
Страница 104: ...CTI 2572 A Installation and Operation Guide 96 WX WY Quick Reference...
Страница 112: ......
Страница 116: ......
Страница 126: ......
Страница 130: ...CTI 2572 A Installation and Operation Guide 122 WX WY Quick Reference...