CTI 2572-A Installation and Operation Guide V1.3
41
Offset 10-11
IP Address
–
UDP/Multicast Only
. If you set the IP Address Location bit to 1 (see
offset 4 of the C
REATE
S
OCKET
command block), you must specify the IP address of
the remote device or a multicast address in these words. If the IP Address Location
bit is set to 0, these words are ignored and the IP address contained in the C
REATE
S
OCKET
command block is used. An IP address of 0.0.0.0 (0000 0000 hex) or
greater than 239.255.255.255 (EFFF FFFF hex) will return an error.
Offset 12
UDP port number
–
UDP/Multicast Only
. If you set the IP Address Location bit to 1
(see offset 4 of the C
REATE
S
OCKET
command block), you must specify the UDP
port number of the remote device. If you are accessing another 2572, you will
typically set this value to 1505 (the recommended value for the 2572-A PLC server).
If the IP Address Location bit is set to 0, this word is ignored and the port number
contained in the C
REATE
S
OCKET
command block is used.
Offset 13
Minimum Production Interval
– When uncoupled trigger mode is used, this word
allows you to specify the minimum time interval (in milliseconds) between
successive transmissions of the command message. A value of 0 uses the default of
50 ms. The value may range from 50 to 10,000.
NOTE:
Depending on the PLC scan time, the actual interval may be greater than the interval specified. It
requires two scans to process the command. If the Minimum Production Interval value is greater than
two scan times, you must add one scan time to the interval specified.
Offset 14-15
Unused
- Set to 0.
Содержание 2572-A
Страница 8: ......
Страница 16: ......
Страница 28: ......
Страница 32: ......
Страница 60: ......
Страница 84: ......
Страница 96: ......
Страница 104: ...CTI 2572 A Installation and Operation Guide 96 WX WY Quick Reference...
Страница 112: ......
Страница 116: ......
Страница 126: ......
Страница 130: ...CTI 2572 A Installation and Operation Guide 122 WX WY Quick Reference...