4
Performance
THE PERFORMANCE OF GECKO AND CAMELEON MOTOR PUMPS
depends on the following criteria:
1 -
The
”MINIMUM”
flow range (in litres/minute) is defined by the minimum flow required to
ensure that regulation is stable.
2 -
The
”MAXIMUM”
flow ranges are given according to:
Truck’ water pump performance
The possibilities for transit in supply pipes of
Ø 100 - 125 - 150 - 200 for the
GECKO.
The possibilities for transit in supply pipes of
Ø 45 - 70 - 110 for the CAMELEON.
The ”MAXIMUM” GECKO and CAMELEON volumetric pump performances.
3 -
The flows and concentrations correspond to the use of foaming agents.
CAMELEON 30L Additive
GECKO 120 Foam
concentrate
Type of concentration
keys
Ex. of concentration
0.2%
0.3%
0.4%
0.5%
3 %
6 %
Pre-mix outlet
Flow rate
Minimum
400
260
200
160
Minimum
250
130
Max DN 100
5000
5000
5000
5000
Max DN 100
4000
2000
Содержание Iguane 120-30
Страница 1: ...Version 1 21 01 16 Fire fighting IGUANE Range USER MANUAL IGUANE 120 30...
Страница 2: ...2...
Страница 5: ...5 PRESENTATION OF THE IGUANE...
Страница 8: ...8 HYDRAULIC DRAWING...
Страница 10: ...10 INTERVENTION PROCEDURE...
Страница 21: ...21 ANNEXES...
Страница 22: ...22 Motor OMR80 Option...
Страница 28: ...28 PURGE OF THE FILTER CAMELEON Open the valve of the suction filter Filter valve Cameleon...