background image

2.4

Operation

1.) Connect RF cables to the 1584-45 (See Section 2.2).
2.) IF DC VOLTAGE IS REQUIRED ON THE SPLITTER RF INPUT CENTER CONDUCTOR, 
install  1/4”, 1 amp fast blo fuses in Fuse 3 and/or Fuse 4 holders.

CAUTION!  -- IF FUSES ARE INSTALLED IN THE Fuse 1, 2, 3, or 4 HOLDERS, +22 VDC 

WILL APPEAR ON THE CORRESPONDING SPLITTER INPUT CONNECTOR CENTER 
PINS.

3.) Connect 100-240 ±10% VAC, 47 - 63 Hz to AC A and AC B on the back panel and observe 
A and B LEDs are lit on the front panel.
4.) Monitor RF signals on the front panel monitors and DC voltage to the external amplifiers (Front 
panel Green ON LEDs should be lit if LNB fuses are installed in the rear panel fuse holders) to 
insure proper signals and voltages.

NOTE: FOR OPTIMUM PERFORMANCE, THE MONITOR PORT AND SPLITTER PORTS 

SHOULD BE TERMINATED WITH 75 OHM TYPE F TERMINATIONS WHEN NOT USED.

5.) AC Fuse - The fuse is a 5mm, 2 amp fast blo and is inserted in the far slot in the drawer below 
the AC input as shown in Figure 2.6. There is a spare fuse in the near slot. If a fuse continues to 
open, the power supply is most likely defective. Note that each power supply module within the 
chassis also has a fuse but failure of this fuse indicates the power supply may be defective.

AC Fuse - 2 amp slow blow (Type T), 
5 mm X 20 mm

FUSE DRAWER

SPARE FUSE

~

INPUT

100-240± 10%VAC

47-63 Hz

2A MAX

FUSE

TYPE T 2A GDC

250 VOLT

FOR 100 - 240 V~

~

FIGURE 2.4   FUSE LOCATION AND SPARE FUSE

1584-45 Manual, Rev C

          Page 7

     

 

           4/24/13

Содержание 1584-45

Страница 1: ...are proprietary to Cross Technologies Inc but may be reproduced or duplicated without the prior permission of Cross Technologies Inc for purposes of operating the equipment When ordering parts from C...

Страница 2: ...s Technologies Inc s obligation under this warranty is limited to repairing or at Cross Technologies Inc s option replacing parts subassemblies or entire assemblies Cross Technologies Inc shall not be...

Страница 3: ...puts are AC coupled so no DC appears on their center conductors On the front panel green LEDs indicate presence of 22 VDC at each LNB power supply output and DC voltage test points allow monitoring th...

Страница 4: ...B min 40 dB typical Coupler to Coupler Iso n 0 dB 1 0 dB Gain 75 50 Option D Impedance 20 dBm total maximum Input Level 12 dB min 14 dB typical Return Loss 75 50 Option D Input Impedance TABLE 1 0 158...

Страница 5: ...e front panel Figure 2 1 shows how the 1584 45 is assembled J28 J27 J26 and J25 connect DC Power to the fuses as shown and J30 and J29 connect the DC voltage from the power supplies to the PCB as show...

Страница 6: ...0 240 10 VAC 47 60 HZ Uses 2 amp Fast Blo 5mm fuse FIGURE 2 2 1584 45 REAR PANEL 2 3 Front Panel Monitors and Indicators Figure 2 3 shows the front panel monitors and indicators GROUND TEST POINT LNB...

Страница 7: ...stalled in the rear panel fuse holders to insure proper signals and voltages NOTE FOR OPTIMUM PERFORMANCE THE MONITOR PORT AND SPLITTER PORTS SHOULD BE TERMINATED WITH 75 OHM TYPE F TERMINATIONS WHEN...

Страница 8: ...e equipment is not compromised Additional space between unit may be required E Circuit Overloading Consideration should be given to the connection of the equipment to the supply circuit and the effect...

Страница 9: ...HNOLOGIES INC 6170 Shiloh Road Alpharetta Georgia 30005 770 886 8005 FAX 770 886 7964 Toll Free 888 900 5588 WEB www crosstechnologies com E MAIL info crosstechnologies com 1584 45 Manual Rev C Page 9...

Отзывы: