FCS - Operation Manual
Rev. C | 2022.02
• Check that local area network wiring is correct, especially the A and B lines to make sure
they are not swapped between devices on the network.
• Check that the remote device is working properly itself.
RDM constantly shows “Connection Lost”.
Check that the # of RDMs is set correctly. Refer
to Section 8.5 Set Number of RDM Remote Display(s) for more information.
Changes made to the RDM standard or selected channels display and priority
configurations are not working as expected.
After a change in configuration, it is
recommended to do a restart of the FCS. Push and hold the button on the FCS circuit board
until the buzzer chirps (approximately a count of 12), let go and the FCS will do a restart.
NOTE:
Restarting the FCS only resets the FCS, the transmitters and peripherals are not
affected.
NOTE:
If you know that the power to the system is without issue, the 2 minute countdown
upon start-up may be sped up. When you see ‘Waiting for stable power’, press the Rest/
Restart button on the circuit board on the inside of the door for approximately 15 seconds,
then let go. The device will turn off /on and after 10 seconds will start the regular warm-up
process.
Touch response of the screen is not working as well as it used to.
Recalibrate the display. Refer to Section 7.10 Recalibrating the Display for Improved
Response.