NOTE:
This example assumes the Channel gas name and alarm setting configurations and
the Relay configurations for exhaust fans have been set up already.
To use the Title-24 functionality, make sure the Title-24 Faults flag is set to En (enabled). Go
to Set Alarm Menu (passcode 2012) / System STEL/TWA (refer to Section 10.2).
Make sure the Calib. Expired Faults flag is set to En (enabled). Go to Set Alarm Menu
(passcode 2012) / System STEL/TWA (refer to Section 10.2).
Make sure the Calibration Expired Priority is configured and assigned to all the appropriate
channels. Go to Config Channel Menu / Priority Logic (refer to Section 12.3.3).
NOTE:
The priority numbers and relay numbers used in the examples are arbitrarily chosen.
In real life it is common to start with the first unused number and proceed from there.
In the Config Channel Menu /
Priority Logic
:
For Priority 6:
• Choose Title-24 Occupied
• Set S-Hour to 8
• Set S-Minute to 0
• Select M, T, W, T, F (buttons turn green when selected)
• Set E-Hour to 17
• Set E-Min to 0
• Press Save
For Priority 7:
• Choose Title-24 Occupied
• Set S-Hour to 8
• Set S-Minute to 30
•
Select the first S (buttons turn green when selected)
• Set E-Hour to 12
• Set E-Min to 0
• Press Save
For more information on Title-24 Priority Logic, refer to Section 12.3.4 Title-24 Occupied
Priority Logic.
NOTE:
The time (hour and minute) functionality uses a 24 hour clock. (ie. 9am = 9 and
1pm = 13).
In the Config Channel Menu (passcode 3022) / NEXT /
Relay Logic
: