FCS - Operation Manual
Rev. C | 2022.02
In the Config Channel Menu (passcode 3022)
Channel Logic
(1-60):
• Assign each Channel (sensor) that needs to be calibrated every 12 months to P4
(Priority 4)
• Assign each Channel (sensor) that needs to be calibrated every 6 months to P5
(Priority 5)
• Press Save
For more information on Channel Logic, refer to Section 12.1 Assign Priority Levels to
Channels.
In the Config Channel Menu /
Priority Logic
:
For Priority 4:
• Choose Calibration Expired
• Use the + button to enter 12
• Press SAVE
For Priority 5:
• Choose Calibration Expired
• Use the + button to enter 6
• Press SAVE
For more information on Priority Logic, refer to Section 12.3.3 Calibration Expiry Priority
Logic.
In the Config Channel Menu /
Relay Logic
:
For Relay 1:
•
Use the + button to enter 4 in the T1 field.
• Set Alarm to F, for Fault
•
Leave the remaining fields their default values
• Press SAVE.
For Relay 2:
•
Use the + button to enter 5 in the T1 field.
• Set Alarm to F, for Fault
•
Leave the remaining fields their default values
• Press SAVE.
For more information on Relay Logic, refer to Section 12.2 Assign Priority Levels to Relay,
Strobe, Horn & Audible