© 2022 All rights reserved. Data subject to change without notice.
49
Rev. C | 2022.02
FCS - Operation Manual
screen will either be a mA value or, the percentage of the maximum Full Speed (Hz) value
entered in the VFD Configuration screen. Refer to Section 9.2.
To enter the Config Analog IO menu, enter code “3032” in the password screen and select
Analog Output Logic.
If you want to review the current priority settings for each output, press the + or - buttons. To
skip ahead by 10 devices at time, press the +10 button. Or press the yellow field and use the
keypad to enter the specific number.
Use the + and - buttons or press on the yellow fields to use the keypad to change the
settings:
A. Output: Choose the analog output for which you want to configure the logic using the
appropriate mode.
Mode: Choose the mode the analog output will operate in. The screen will change depending
on which mode you choose:
• OFF will result in a 0 current or percentage output. The OFF feature allows you to
set any analog outputs you are not using to OFF or to stop the analog output from
controlling whatever it is configured to control.
Press SAVE to save the changes.
•
CHANNEL allows you to choose a specific channel (1 through 128 or 1 through 8 for
the FCS-8) that the analog output will monitor.