Isys i/O
®
Tilt Touchpanel Media Center
Crestron
TPMC-12
QM Network Topology
TPMC-12
QM-TX
QM
QM
QM
QM
QM
Origination Points
Endpoints
QM
Midpoints
QM-FTDC
QM-MD7x2
QM-MD7x2
QM-WMC
TPMC-12
Identity Code
Net ID
The Net ID of the TPMC-12 has been factory set to
03
. The Net IDs of multiple
TPMC-12 devices in the same system must be unique. The Net ID is set using the
internal setup menu (refer to “Cresnet” which starts on page 21). Net ID may also be
set from a personal computer (PC) via Crestron Toolbox™ (refer to “Establishing
Communication” which starts on page 56).
When setting the Net ID, consider the following:
•
The Net ID of each unit must match an ID code specified in the SIMPL™
Windows
®
program.
•
Each network device must have a unique Net ID.
For more details, refer to the Crestron Toolbox help file.
IP ID
The IP ID is set within the TPMC-12’s table using Crestron Toolbox. For
information on setting an IP table, refer to the Crestron Toolbox help file. The IP IDs
of multiple TPMC-12 devices in the same system must be unique.
When setting the IP ID, consider the following:
•
The IP ID of each unit must match an IP ID specified in the SIMPL
Windows program.
•
Each device using IP to communicate with a control system must have a
unique IP ID.
Configuring the Touchpanel
NOTE:
The only connection required to configure the touchpanel is power
(supplied via Cresnet). Refer to “Hardware Hookup” which starts on page 40 for
details.
NOTE:
When booting the TPMC-12, the only USB devices supported are a
keyboard or mouse. Having a USB drive or hub connected will interfere with proper
booting of the touchpanel.
The TPMC-12 is configured from the setup menu.
16
•
Isys i/O
®
Tilt Touchpanel Media Center: TPMC-12
Operations Guide – DOC. 6675A
Содержание TPMC-12 Isys i/O
Страница 1: ...Crestron TPMC 12 Isysi O TiltTouchpanelMediaCenter Operations Guide...
Страница 4: ......