Observe the LED Indicators

Refer to the following table for information about the LED indicators on
the device.

LED Indicator

Color

Meaning

PWR

Amber

The device is booting, factory reset
in process, or the outlets have been
shut off due to a fault condition.

Green

The device is functioning normally.

Blinking Green

The "Identify" search process is
initiated.

FAULT

Red

Surge protection is compromised,
line and neutral are reversed, or no
ground is detected.

PROTECT

Green

Surge protection is functional.

SHUTDOWN

Amber

Power to outlets is shut off due to
an overvoltage, undervoltage,
overcurrent, line input miswire,
missing ground, or compromised
surge protection fault condition.

Per Outlet
Indicator

Green

The outlet is turned on.

Blinking Green

The "Identify" search process is
initiated for the outlet.

LAN

Amber

Indicates Ethernet activity

Green

Indicates Ethernet link status

Configure

Use the web user interface, SIMPL programming, or the Crestron
Home™ setup application to configure and monitor various components
of the PC-350V-12 or PC-350V-18. For more information, refer to the
product manual of the device.

Important Safety Instructions

l

Installation must be completed by a professional.

l

Equipotential bonding must be in place where the equipment is
mounted.

l

The power cord must be connected to an outlet with a properly
earthed ground connection, as the device is earthed through the
power cord connection at the inlet.

WARNING:

The device power plug is designed to be inserted into a

NEMA 5-15 (three-prong grounded) outlet only. Do not force the
plug into an outlet that is not designed to accept it. Never
dismantle the plug or alter the power cord, and do not attempt to
defeat the grounding feature by using a 3-to-2 prong adapter. If
you have questions about grounding, consult your local power
company or a qualified electrician.

l

The device is intended for installation in Information Technology
Equipment Rooms, and not in areas that are generally accessible.

l

Equipment is suitable for installation in Information Technology
Rooms in accordance with Article 645 of the National Electrical Code
and NFPA 75.

15

PC-350V-12 and PC-350V-18

Quick Start

Vertical Networked Power Controller & Conditioner with Surge Protection and Metering

Содержание PC-350V-12

Страница 1: ...nufacturer Reduced Airflow Installation of the equipment in a rack should be such that the amount of airflow required for safe operation of the equipment is not compromised Mechanical Loading Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical loading Circuit Overloading Consideration should be given to the connection of the equi...

Страница 2: ... the Device Without Keyhole Mounts NOTE Unless otherwise indicated in this guide the installation procedure is the same for PC 350V 12 and PC 350V 18 Toolless Mounting 1 Align the keyhole mounts on the rear of the device to the keyhole slots on the rack frame or the accessory channel 2 Insert and slide the device down to lock firmly into position 2 PC 350V 12 and PC 350V 18 Quick Start Vertical Ne...

Страница 3: ...0V 12 and PC 350V 18 is 24 49 in 622 mm and 36 73 in 933 mm respectively Distance between keyhole mounts for PC 350V 12 and PC 350V 18 Brackets can be attached to the rack angle using one of the following three methods Follow the method that is best for your rack deployment to secure the device 2 Align the keyhole mounts on the rear of the device to the keyhole slots on the mounting brackets 3 Ins...

Страница 4: ...thod 1 Attaching brackets to the rack angle Mounting the device onto the brackets 4 PC 350V 12 and PC 350V 18 Quick Start Vertical Networked Power Controller Conditioner with Surge Protection and Metering ...

Страница 5: ...thod 2 Attaching brackets to the rack angle Mounting the device onto the brackets 5 PC 350V 12 and PC 350V 18 Quick Start Vertical Networked Power Controller Conditioner with Surge Protection and Metering ...

Страница 6: ...thod 3 Attaching brackets to the rack angle Mounting the device onto the brackets 6 PC 350V 12 and PC 350V 18 Quick Start Vertical Networked Power Controller Conditioner with Surge Protection and Metering ...

Страница 7: ...ts to the rear of the device Brackets can be attached to the device using one of the following three methods Follow the method that is best for your rack deployment to secure the device 4 Use the rack mounting screws not included and washers not included to attach the assembled device to the rack angle 7 PC 350V 12 and PC 350V 18 Quick Start Vertical Networked Power Controller Conditioner with Sur...

Страница 8: ...1 Attaching brackets to the power controller Attaching the assembly to the rack angle 8 PC 350V 12 and PC 350V 18 Quick Start Vertical Networked Power Controller Conditioner with Surge Protection and Metering ...

Страница 9: ...2 Attaching brackets to the power controller Attaching the assembly to the rack angle 9 PC 350V 12 and PC 350V 18 Quick Start Vertical Networked Power Controller Conditioner with Surge Protection and Metering ...

Страница 10: ...3 Attaching brackets to the power controller Attaching the assembly to the rack angle 10 PC 350V 12 and PC 350V 18 Quick Start Vertical Networked Power Controller Conditioner with Surge Protection and Metering ...

Страница 11: ...ed FAULT LED is not lit If the FAULT LED lights then the connected outlet is not wired correctly Fault details can be viewed in the device web user interface For more information on monitoring and configuring the device parameters refer to the PC 350V Series Product Manual NOTE Do not make any connections to the device until the connected outlet is wired correctly 4 Repeat steps 1 and 2 until the ...

Страница 12: ...r Conditioner with Surge Protection and Metering Make Connections Make the necessary connections as called out in the following illustration Connect power last PC 350V 12 CAUTION The PC 350V 12 must be plugged into a circuit that has a 20 amp or a 15 amp circuit breaker 12 ...

Страница 13: ...ON The PC 350V 18 must be plugged into a circuit that has a 20 amp or a 15 amp circuit breaker 13 PC 350V 12 and PC 350V 18 Quick Start Vertical Networked Power Controller Conditioner with Surge Protection and Metering ...

Страница 14: ... Press and hold the HW R button for at least 3 seconds and release The device will reboot Factory Restore 1 Ensure the device is powered on 2 Press and hold the HW R button for 15 seconds until all status LEDs blink twice to indicate the restore command has been executed successfully The PWR LED blinks amber during the factory restore process The device will then reboot and all factory settings wi...

Страница 15: ...C 350V 12 or PC 350V 18 For more information refer to the product manual of the device Important Safety Instructions l Installation must be completed by a professional l Equipotential bonding must be in place where the equipment is mounted l The power cord must be connected to an outlet with a properly earthed ground connection as the device is earthed through the power cord connection at the inle...

Страница 16: ...at www crestron com legal software_license_agreement The product warranty can be found at www crestron com warranty The specific patents that cover Crestron products are listed at www crestron com legal patents Certain Crestron products contain open source software For specific information visit www crestron com opensource Crestron the Crestron logo and Crestron Home are either trademarks or regis...

Отзывы: