5.4
Gas settings
5.4.1.
Adapting to another gas type
WARNING
Only a qualified engineer may carry out the following
operations.
The boiler is preset in the factory to operate on natural gas G20 (Gas
H).
For operation on another group of gases, carry out the following
operations. In case of functioning on propane:
1.
Quinta Pro For conversion to propane
30
Rotate the adjusting screw
A
on the venturi 3½ turns in a
clockwise direction
45
Rotate the adjusting screw
A
on the venturi 4¾ turns in a
clockwise direction
65
Rotate the adjusting screw
A
on the venturi 6½ turns in a
clockwise direction
90
Replace the current gas block with the propane gas block
according to the instructions supplied with the propane
conversion kit
115
First turn the setting screw
A
clockwise until it is closed, then:
Rotate the adjusting screw
A
on the gas block 3½ - 4 turns in
an anticlockwise direction
2. Regulate the fan speed as indicated in the table (if required). The
setting can be modified using parameters
p17
,
p18
,
p19
and
p20
:
¼
See chapter: "Parameter descriptions", page 55
3. Set the air/gas ratio. For more detailed information:
¼
See chapter: "Setting the air/gas ratio (Full load)", page
¼
See chapter: "Setting the air/gas ratio (Part load)", page
T003241-A
A
A
Quinta Pro 30 - 45 - 65 - 90 - 115
5. Commissioning
250413 - 123157-03
49