APP Interface
43 / 79
Parameter name
Description
Range
Grid code
IEEE-1547
Grid code
RULE-21
Grid code
ISO-NE
Unit
VoltMaxMovAvgE
n
max voltage move
average enable
{Disable, Enable}
Disable
Disable
Disable
VoltMinMovAvg
Threshold min
voltage move
average
{80.00%, 100.00%}
88.00%
87.99%
88.00%
%
MinTripVMovAvg
T
Trip time of min
voltage move
average
{0, 655}
600
600
600
Secs
VoltMinMovAvgE
n
min voltage move
average enable
{Disable, Enable}
Disable
Disable
Disable
Voltage Unbalance
GridVoltUnbalanc
e
Threshold grid
voltage unbalance
{0.01%, 10%}
10%
10%
10%
%
GridVoltUnbalanc
eEn
grid voltage
unbalance enable
{Disable, Enable}
Enable
Enable
Enable
PhaseLose and Phase-PE parameters
PhaseLoseCoeff
Phase lose protection
trigger value
{0.5%,30.0%}
3.0%
3.0%
3.0%
%
PhaseLoseRcvCo
eff
Phase lose protection
recovery value
{0.5%,30.0%}
2.0%
2.0%
2.0%
%
PhaseLoseVUnba
lance
PhaseLose Voltage
Unbalance
{0.1%,10.0%}
10.0%
10.0%
10.0%
%
PhasLoseCoeffEn
able
Phase lose protection {Disable, Enable}
Disable
Disable
Disable
Phase-PETripVolt
Phase-PE Trip
Voltage
{0.01,100.00}
45%
45%
45%
%
Phase-PERcvVolt
Phase-PE grid
recovery
{0.01,100.00}
35%
35%
35%
%
Phase-PEEnable
Enable Phase-PE
protection
{Disable, Enable}
Disable
Disable
Disable
Table 6-1 Protection Parameters (IEEE1547 2018, Rule21 and ISO-NE)